Cut
A cut separates a line segment into two parts. The cut appears as a switch inserted between these two parts and connects them together. As the cut is normally open there is no galvanic connection between the two line segment parts. But it is possible to close the cut to get galvanic connection.
The cut terminals are oriented towards the line segment terminals with the same sequence number. Hence the cut terminal with sequence number equal to 1 is oriented to the line segment's terminal with sequence number equal to 1.
The cut terminals also act as connection points for jumpers and other equipment, e.g. a mobile generator. To enable this, connectivity nodes are placed at the cut terminals. Once the connectivity nodes are in place any conducting equipment can be connected at them.
URI: cim:Cut
Type: Class
classDiagram
class Cut
click Cut href "../Cut"
Switch <|-- Cut
click Switch href "../Switch"
Cut : Cut.ACLineSegment
Cut --> ACLineSegment : Cut.ACLineSegment
click ACLineSegment href "../ACLineSegment"
Cut : Equipment.aggregate
Cut : ConductingEquipment.BaseVoltage
Cut --> BaseVoltage : ConductingEquipment.BaseVoltage
click BaseVoltage href "../BaseVoltage"
Cut : IdentifiedObject.description
Cut : IdentifiedObject.energyIdentCodeEic
Cut : Equipment.EquipmentContainer
Cut --> EquipmentContainer : Equipment.EquipmentContainer
click EquipmentContainer href "../EquipmentContainer"
Cut : Cut.lengthFromTerminal1
Cut --> Length : Cut.lengthFromTerminal1
click Length href "../Length"
Cut : IdentifiedObject.mRID
Cut : IdentifiedObject.name
Cut : Equipment.normallyInService
Cut : Switch.normalOpen
Cut : Equipment.OperationalLimitSet
Cut --> OperationalLimitSet : Equipment.OperationalLimitSet
click OperationalLimitSet href "../OperationalLimitSet"
Cut : Switch.ratedCurrent
Cut --> CurrentFlow : Switch.ratedCurrent
click CurrentFlow href "../CurrentFlow"
Cut : Switch.retained
Cut : IdentifiedObject.shortName
Cut : Switch.SwitchSchedules
Cut --> SwitchSchedule : Switch.SwitchSchedules
click SwitchSchedule href "../SwitchSchedule"
Cut : ConductingEquipment.Terminals
Cut --> Terminal : ConductingEquipment.Terminals
click Terminal href "../Terminal"
Inheritance
Attributes
Name | URI | Cardinality and Range | Description | Inheritance |
---|---|---|---|---|
ACLineSegment | cim:Cut.ACLineSegment | 1 ACLineSegment |
The line segment to which the cut is applied | direct |
lengthFromTerminal1 | cim:Cut.lengthFromTerminal1 | 0..1 Length |
The length to the place where the cut is located starting from side one of th... | direct |
normalOpen | cim:Switch.normalOpen | 1 boolean |
The attribute is used in cases when no Measurement for the status value is pr... | Switch |
ratedCurrent | cim:Switch.ratedCurrent | 0..1 CurrentFlow |
The maximum continuous current carrying capacity in amps governed by the devi... | Switch |
retained | cim:Switch.retained | 1 boolean |
Branch is retained in the topological solution | Switch |
SwitchSchedules | cim:Switch.SwitchSchedules | * SwitchSchedule |
A Switch can be associated with SwitchSchedules | Switch |
BaseVoltage | cim:ConductingEquipment.BaseVoltage | 0..1 BaseVoltage |
Base voltage of this conducting equipment | ConductingEquipment |
Terminals | cim:ConductingEquipment.Terminals | * Terminal |
Conducting equipment have terminals that may be connected to other conducting... | ConductingEquipment |
aggregate | cim:Equipment.aggregate | 0..1 boolean |
The aggregate flag provides an alternative way of representing an aggregated ... | Equipment |
normallyInService | cim:Equipment.normallyInService | 0..1 boolean |
Specifies the availability of the equipment under normal operating conditions | Equipment |
EquipmentContainer | cim:Equipment.EquipmentContainer | 0..1 EquipmentContainer |
Container of this equipment | Equipment |
OperationalLimitSet | cim:Equipment.OperationalLimitSet | * OperationalLimitSet |
The operational limit sets associated with this equipment | Equipment |
description | cim:IdentifiedObject.description | 0..1 string |
The description is a free human readable text describing or naming the object | IdentifiedObject |
energyIdentCodeEic | eu:IdentifiedObject.energyIdentCodeEic | 0..1 string |
The attribute is used for an exchange of the EIC code (Energy identification ... | IdentifiedObject |
mRID | cim:IdentifiedObject.mRID | 1 string |
Master resource identifier issued by a model authority | IdentifiedObject |
name | cim:IdentifiedObject.name | 1 string |
The name is any free human readable and possibly non unique text naming the o... | IdentifiedObject |
shortName | eu:IdentifiedObject.shortName | 0..1 string |
The attribute is used for an exchange of a human readable short name with len... | IdentifiedObject |
Usages
used by | used in | type | used |
---|---|---|---|
ACLineSegment | Cut | range | Cut |
Identifier and Mapping Information
Schema Source
- from schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
Mappings
Mapping Type | Mapped Value |
---|---|
self | cim:Cut |
native | this:Cut |