PhaseTapChangerAsymmetrical
Describes the tap model for an asymmetrical phase shifting transformer in which the difference voltage vector adds to the in-phase winding. The out-of-phase winding is the transformer end where the tap changer is located. The angle between the in-phase and out-of-phase windings is named the winding connection angle. The phase shift depends on both the difference voltage magnitude and the winding connection angle.
URI: cim:PhaseTapChangerAsymmetrical
Type: Class
classDiagram
class PhaseTapChangerAsymmetrical
click PhaseTapChangerAsymmetrical href "../PhaseTapChangerAsymmetrical"
PhaseTapChangerNonLinear <|-- PhaseTapChangerAsymmetrical
click PhaseTapChangerNonLinear href "../PhaseTapChangerNonLinear"
PhaseTapChangerAsymmetrical : IdentifiedObject.description
PhaseTapChangerAsymmetrical : IdentifiedObject.energyIdentCodeEic
PhaseTapChangerAsymmetrical : TapChanger.highStep
PhaseTapChangerAsymmetrical : TapChanger.lowStep
PhaseTapChangerAsymmetrical : TapChanger.ltcFlag
PhaseTapChangerAsymmetrical : IdentifiedObject.mRID
PhaseTapChangerAsymmetrical : IdentifiedObject.name
PhaseTapChangerAsymmetrical : TapChanger.neutralStep
PhaseTapChangerAsymmetrical : TapChanger.neutralU
PhaseTapChangerAsymmetrical --> Voltage : TapChanger.neutralU
click Voltage href "../Voltage"
PhaseTapChangerAsymmetrical : TapChanger.normalStep
PhaseTapChangerAsymmetrical : IdentifiedObject.shortName
PhaseTapChangerAsymmetrical : TapChanger.TapChangerControl
PhaseTapChangerAsymmetrical --> TapChangerControl : TapChanger.TapChangerControl
click TapChangerControl href "../TapChangerControl"
PhaseTapChangerAsymmetrical : TapChanger.TapSchedules
PhaseTapChangerAsymmetrical --> TapSchedule : TapChanger.TapSchedules
click TapSchedule href "../TapSchedule"
PhaseTapChangerAsymmetrical : PhaseTapChanger.TransformerEnd
PhaseTapChangerAsymmetrical --> TransformerEnd : PhaseTapChanger.TransformerEnd
click TransformerEnd href "../TransformerEnd"
PhaseTapChangerAsymmetrical : PhaseTapChangerNonLinear.voltageStepIncrement
PhaseTapChangerAsymmetrical --> PerCent : PhaseTapChangerNonLinear.voltageStepIncrement
click PerCent href "../PerCent"
PhaseTapChangerAsymmetrical : PhaseTapChangerAsymmetrical.windingConnectionAngle
PhaseTapChangerAsymmetrical --> AngleDegrees : PhaseTapChangerAsymmetrical.windingConnectionAngle
click AngleDegrees href "../AngleDegrees"
PhaseTapChangerAsymmetrical : PhaseTapChangerNonLinear.xMax
PhaseTapChangerAsymmetrical --> Reactance : PhaseTapChangerNonLinear.xMax
click Reactance href "../Reactance"
PhaseTapChangerAsymmetrical : PhaseTapChangerNonLinear.xMin
PhaseTapChangerAsymmetrical --> Reactance : PhaseTapChangerNonLinear.xMin
click Reactance href "../Reactance"
Inheritance
- IdentifiedObject
- PowerSystemResource
- TapChanger
- PhaseTapChanger
- PhaseTapChangerNonLinear
- PhaseTapChangerAsymmetrical
- PhaseTapChangerNonLinear
- PhaseTapChanger
- TapChanger
- PowerSystemResource
Attributes
Name | URI | Cardinality and Range | Description | Inheritance |
---|---|---|---|---|
windingConnectionAngle | cim:PhaseTapChangerAsymmetrical.windingConnectionAngle | 1 AngleDegrees |
The phase angle between the in-phase winding and the out-of -phase winding us... | direct |
voltageStepIncrement | cim:PhaseTapChangerNonLinear.voltageStepIncrement | 1 PerCent |
The voltage step increment on the out of phase winding (the PowerTransformerE... | PhaseTapChangerNonLinear |
xMax | cim:PhaseTapChangerNonLinear.xMax | 1 Reactance |
The reactance depends on the tap position according to a "u" shaped curve | PhaseTapChangerNonLinear |
xMin | cim:PhaseTapChangerNonLinear.xMin | 1 Reactance |
The reactance depend on the tap position according to a "u" shaped curve | PhaseTapChangerNonLinear |
TransformerEnd | cim:PhaseTapChanger.TransformerEnd | 1 TransformerEnd |
Transformer end to which this phase tap changer belongs | PhaseTapChanger |
TapSchedules | cim:TapChanger.TapSchedules | * TapSchedule |
A TapChanger can have TapSchedules | TapChanger |
highStep | cim:TapChanger.highStep | 1 integer |
Highest possible tap step position, advance from neutral | TapChanger |
lowStep | cim:TapChanger.lowStep | 1 integer |
Lowest possible tap step position, retard from neutral | TapChanger |
ltcFlag | cim:TapChanger.ltcFlag | 1 boolean |
Specifies whether or not a TapChanger has load tap changing capabilities | TapChanger |
neutralStep | cim:TapChanger.neutralStep | 1 integer |
The neutral tap step position for this winding | TapChanger |
neutralU | cim:TapChanger.neutralU | 1 Voltage |
Voltage at which the winding operates at the neutral tap setting | TapChanger |
normalStep | cim:TapChanger.normalStep | 1 integer |
The tap step position used in "normal" network operation for this winding | TapChanger |
TapChangerControl | cim:TapChanger.TapChangerControl | 0..1 TapChangerControl |
The regulating control scheme in which this tap changer participates | TapChanger |
description | cim:IdentifiedObject.description | 0..1 string |
The description is a free human readable text describing or naming the object | IdentifiedObject |
energyIdentCodeEic | eu:IdentifiedObject.energyIdentCodeEic | 0..1 string |
The attribute is used for an exchange of the EIC code (Energy identification ... | IdentifiedObject |
mRID | cim:IdentifiedObject.mRID | 1 string |
Master resource identifier issued by a model authority | IdentifiedObject |
name | cim:IdentifiedObject.name | 1 string |
The name is any free human readable and possibly non unique text naming the o... | IdentifiedObject |
shortName | eu:IdentifiedObject.shortName | 0..1 string |
The attribute is used for an exchange of a human readable short name with len... | IdentifiedObject |
Identifier and Mapping Information
Schema Source
- from schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile
Mappings
Mapping Type | Mapped Value |
---|---|
self | cim:PhaseTapChangerAsymmetrical |
native | this:PhaseTapChangerAsymmetrical |