A shunt capacitor or reactor or switchable bank of shunt capacitors or reactors. A section of a shunt compensator is an individual capacitor or reactor. A negative value for bPerSection indicates that the compensator is a reactor. ShuntCompensator is a single terminal device. Ground is implied.

URI: cim:ShuntCompensator
Type: Class

 classDiagram
    class ShuntCompensator
    click ShuntCompensator href "../ShuntCompensator"
      RegulatingCondEq <|-- ShuntCompensator
        click RegulatingCondEq href "../RegulatingCondEq"


      ShuntCompensator <|-- LinearShuntCompensator
        click LinearShuntCompensator href "../LinearShuntCompensator"
      ShuntCompensator <|-- NonlinearShuntCompensator
        click NonlinearShuntCompensator href "../NonlinearShuntCompensator"


      ShuntCompensator : Equipment.aggregate

      ShuntCompensator : ShuntCompensator.aVRDelay

          ShuntCompensator --> Seconds : ShuntCompensator.aVRDelay
          click Seconds href "../Seconds"

      ShuntCompensator : ConductingEquipment.BaseVoltage

          ShuntCompensator --> BaseVoltage : ConductingEquipment.BaseVoltage
          click BaseVoltage href "../BaseVoltage"

      ShuntCompensator : IdentifiedObject.description

      ShuntCompensator : IdentifiedObject.energyIdentCodeEic

      ShuntCompensator : Equipment.EquipmentContainer

          ShuntCompensator --> EquipmentContainer : Equipment.EquipmentContainer
          click EquipmentContainer href "../EquipmentContainer"

      ShuntCompensator : ShuntCompensator.grounded

      ShuntCompensator : ShuntCompensator.maximumSections

      ShuntCompensator : IdentifiedObject.mRID

      ShuntCompensator : IdentifiedObject.name

      ShuntCompensator : ShuntCompensator.nomU

          ShuntCompensator --> Voltage : ShuntCompensator.nomU
          click Voltage href "../Voltage"

      ShuntCompensator : Equipment.normallyInService

      ShuntCompensator : ShuntCompensator.normalSections

      ShuntCompensator : Equipment.OperationalLimitSet

          ShuntCompensator --> OperationalLimitSet : Equipment.OperationalLimitSet
          click OperationalLimitSet href "../OperationalLimitSet"

      ShuntCompensator : RegulatingCondEq.RegulatingControl

          ShuntCompensator --> RegulatingControl : RegulatingCondEq.RegulatingControl
          click RegulatingControl href "../RegulatingControl"

      ShuntCompensator : IdentifiedObject.shortName

      ShuntCompensator : ConductingEquipment.Terminals

          ShuntCompensator --> Terminal : ConductingEquipment.Terminals
          click Terminal href "../Terminal"

      ShuntCompensator : ShuntCompensator.voltageSensitivity

          ShuntCompensator --> VoltagePerReactivePower : ShuntCompensator.voltageSensitivity
          click VoltagePerReactivePower href "../VoltagePerReactivePower"

Inheritance

Attributes

Name URI Cardinality and Range Description Inheritance
aVRDelay cim:ShuntCompensator.aVRDelay 0..1
Seconds
An automatic voltage regulation delay (AVRDelay) which is the time delay from... direct
grounded cim:ShuntCompensator.grounded 0..1
boolean
Used for Yn and Zn connections direct
maximumSections cim:ShuntCompensator.maximumSections 1
integer
The maximum number of sections that may be switched in direct
nomU cim:ShuntCompensator.nomU 1
Voltage
The voltage at which the nominal reactive power may be calculated direct
normalSections cim:ShuntCompensator.normalSections 1
integer
The normal number of sections switched in direct
voltageSensitivity cim:ShuntCompensator.voltageSensitivity 0..1
VoltagePerReactivePower
Voltage sensitivity required for the device to regulate the bus voltage, in v... direct
RegulatingControl cim:RegulatingCondEq.RegulatingControl 0..1
RegulatingControl
The regulating control scheme in which this equipment participates RegulatingCondEq
BaseVoltage cim:ConductingEquipment.BaseVoltage 0..1
BaseVoltage
Base voltage of this conducting equipment ConductingEquipment
Terminals cim:ConductingEquipment.Terminals *
Terminal
Conducting equipment have terminals that may be connected to other conducting... ConductingEquipment
aggregate cim:Equipment.aggregate 0..1
boolean
The aggregate flag provides an alternative way of representing an aggregated ... Equipment
normallyInService cim:Equipment.normallyInService 0..1
boolean
Specifies the availability of the equipment under normal operating conditions Equipment
EquipmentContainer cim:Equipment.EquipmentContainer 0..1
EquipmentContainer
Container of this equipment Equipment
OperationalLimitSet cim:Equipment.OperationalLimitSet *
OperationalLimitSet
The operational limit sets associated with this equipment Equipment
description cim:IdentifiedObject.description 0..1
string
The description is a free human readable text describing or naming the object IdentifiedObject
energyIdentCodeEic eu:IdentifiedObject.energyIdentCodeEic 0..1
string
The attribute is used for an exchange of the EIC code (Energy identification ... IdentifiedObject
mRID cim:IdentifiedObject.mRID 1
string
Master resource identifier issued by a model authority IdentifiedObject
name cim:IdentifiedObject.name 1
string
The name is any free human readable and possibly non unique text naming the o... IdentifiedObject
shortName eu:IdentifiedObject.shortName 0..1
string
The attribute is used for an exchange of a human readable short name with len... IdentifiedObject

Identifier and Mapping Information

Schema Source

  • from schema: http://iec.ch/TC57/ns/CIM/CoreEquipment-EU#Package_CoreEquipmentProfile

Mappings

Mapping Type Mapped Value
self cim:ShuntCompensator