TurbLCFB1
Turbine load controller model developed by WECC. This model represents a supervisory turbine load controller that acts to maintain turbine power at a set value by continuous adjustment of the turbine governor speed-load reference. This model is intended to represent slow reset 'outer loop' controllers managing the action of the turbine governor.
URI: cim:TurbLCFB1
Type: Class
classDiagram
class TurbLCFB1
click TurbLCFB1 href "../TurbLCFB1"
TurbineLoadControllerDynamics <|-- TurbLCFB1
click TurbineLoadControllerDynamics href "../TurbineLoadControllerDynamics"
TurbLCFB1 : TurbLCFB1.db
TurbLCFB1 --> PU : TurbLCFB1.db
click PU href "../PU"
TurbLCFB1 : IdentifiedObject.description
TurbLCFB1 : TurbLCFB1.emax
TurbLCFB1 --> PU : TurbLCFB1.emax
click PU href "../PU"
TurbLCFB1 : DynamicsFunctionBlock.enabled
TurbLCFB1 : TurbLCFB1.fb
TurbLCFB1 --> PU : TurbLCFB1.fb
click PU href "../PU"
TurbLCFB1 : TurbLCFB1.fbf
TurbLCFB1 : TurbLCFB1.irmax
TurbLCFB1 --> PU : TurbLCFB1.irmax
click PU href "../PU"
TurbLCFB1 : TurbLCFB1.ki
TurbLCFB1 --> PU : TurbLCFB1.ki
click PU href "../PU"
TurbLCFB1 : TurbLCFB1.kp
TurbLCFB1 --> PU : TurbLCFB1.kp
click PU href "../PU"
TurbLCFB1 : IdentifiedObject.mRID
TurbLCFB1 : TurbLCFB1.mwbase
TurbLCFB1 --> ActivePower : TurbLCFB1.mwbase
click ActivePower href "../ActivePower"
TurbLCFB1 : IdentifiedObject.name
TurbLCFB1 : TurbLCFB1.pbf
TurbLCFB1 : TurbLCFB1.pmwset
TurbLCFB1 --> ActivePower : TurbLCFB1.pmwset
click ActivePower href "../ActivePower"
TurbLCFB1 : TurbLCFB1.speedReferenceGovernor
TurbLCFB1 : TurbLCFB1.tpelec
TurbLCFB1 --> Seconds : TurbLCFB1.tpelec
click Seconds href "../Seconds"
TurbLCFB1 : TurbineLoadControllerDynamics.TurbineGovernorDynamics
TurbLCFB1 --> TurbineGovernorDynamics : TurbineLoadControllerDynamics.TurbineGovernorDynamics
click TurbineGovernorDynamics href "../TurbineGovernorDynamics"
Inheritance
Attributes
Name | URI | Cardinality and Range | Description | Inheritance |
---|---|---|---|---|
mwbase | cim:TurbLCFB1.mwbase | 1 ActivePower |
Base for power values (MWbase) (> 0) | direct |
speedReferenceGovernor | cim:TurbLCFB1.speedReferenceGovernor | 1 boolean |
Type of turbine governor reference (Type) | direct |
db | cim:TurbLCFB1.db | 1 PU |
Controller deadband (db) | direct |
emax | cim:TurbLCFB1.emax | 1 PU |
Maximum control error (Emax) (see parameter detail 4) | direct |
fb | cim:TurbLCFB1.fb | 1 PU |
Frequency bias gain (Fb) | direct |
kp | cim:TurbLCFB1.kp | 1 PU |
Proportional gain (Kp) | direct |
ki | cim:TurbLCFB1.ki | 1 PU |
Integral gain (Ki) | direct |
fbf | cim:TurbLCFB1.fbf | 1 boolean |
Frequency bias flag (Fbf) | direct |
pbf | cim:TurbLCFB1.pbf | 1 boolean |
Power controller flag (Pbf) | direct |
tpelec | cim:TurbLCFB1.tpelec | 1 Seconds |
Power transducer time constant (Tpelec) (>= 0) | direct |
irmax | cim:TurbLCFB1.irmax | 1 PU |
Maximum turbine speed/load reference bias (Irmax) (see parameter detai... | direct |
pmwset | cim:TurbLCFB1.pmwset | 1 ActivePower |
Power controller setpoint (Pmwset) (see parameter detail 1) | direct |
TurbineGovernorDynamics | cim:TurbineLoadControllerDynamics.TurbineGovernorDynamics | 1 TurbineGovernorDynamics |
Turbine-governor controlled by this turbine load controller | TurbineLoadControllerDynamics |
enabled | cim:DynamicsFunctionBlock.enabled | 1 boolean |
Function block used indicator | DynamicsFunctionBlock |
description | cim:IdentifiedObject.description | 0..1 string |
The description is a free human readable text describing or naming the object | IdentifiedObject |
mRID | cim:IdentifiedObject.mRID | 1 string |
Master resource identifier issued by a model authority | IdentifiedObject |
name | cim:IdentifiedObject.name | 0..1 string |
The name is any free human readable and possibly non unique text naming the o... | IdentifiedObject |
Identifier and Mapping Information
Schema Source
- from schema: http://iec.ch/TC57/ns/CIM/Dynamics-EU#Package_DynamicsProfile
Mappings
Mapping Type | Mapped Value |
---|---|
self | cim:TurbLCFB1 |
native | this:TurbLCFB1 |