WindContPType3IEC
P control model type 3.
Reference: IEC 61400-27-1:2015, 5.6.5.4.
URI: cim:WindContPType3IEC
Type: Class
classDiagram
class WindContPType3IEC
click WindContPType3IEC href "../WindContPType3IEC"
IdentifiedObject <|-- WindContPType3IEC
click IdentifiedObject href "../IdentifiedObject"
WindContPType3IEC : IdentifiedObject.description
WindContPType3IEC : WindContPType3IEC.dpmax
WindContPType3IEC --> PU : WindContPType3IEC.dpmax
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.dprefmax
WindContPType3IEC --> PU : WindContPType3IEC.dprefmax
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.dprefmin
WindContPType3IEC --> PU : WindContPType3IEC.dprefmin
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.dthetamax
WindContPType3IEC --> PU : WindContPType3IEC.dthetamax
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.dthetamaxuvrt
WindContPType3IEC --> PU : WindContPType3IEC.dthetamaxuvrt
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.kdtd
WindContPType3IEC --> PU : WindContPType3IEC.kdtd
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.kip
WindContPType3IEC --> PU : WindContPType3IEC.kip
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.kpp
WindContPType3IEC --> PU : WindContPType3IEC.kpp
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.mpuvrt
WindContPType3IEC : IdentifiedObject.mRID
WindContPType3IEC : IdentifiedObject.name
WindContPType3IEC : WindContPType3IEC.omegadtd
WindContPType3IEC --> PU : WindContPType3IEC.omegadtd
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.omegaoffset
WindContPType3IEC --> PU : WindContPType3IEC.omegaoffset
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.pdtdmax
WindContPType3IEC --> PU : WindContPType3IEC.pdtdmax
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.tdvs
WindContPType3IEC --> Seconds : WindContPType3IEC.tdvs
click Seconds href "../Seconds"
WindContPType3IEC : WindContPType3IEC.thetaemin
WindContPType3IEC --> PU : WindContPType3IEC.thetaemin
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.thetauscale
WindContPType3IEC --> PU : WindContPType3IEC.thetauscale
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.tomegafiltp3
WindContPType3IEC --> Seconds : WindContPType3IEC.tomegafiltp3
click Seconds href "../Seconds"
WindContPType3IEC : WindContPType3IEC.tomegaref
WindContPType3IEC --> Seconds : WindContPType3IEC.tomegaref
click Seconds href "../Seconds"
WindContPType3IEC : WindContPType3IEC.tpfiltp3
WindContPType3IEC --> Seconds : WindContPType3IEC.tpfiltp3
click Seconds href "../Seconds"
WindContPType3IEC : WindContPType3IEC.tpord
WindContPType3IEC --> PU : WindContPType3IEC.tpord
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.tufiltp3
WindContPType3IEC --> Seconds : WindContPType3IEC.tufiltp3
click Seconds href "../Seconds"
WindContPType3IEC : WindContPType3IEC.udvs
WindContPType3IEC --> PU : WindContPType3IEC.udvs
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.updip
WindContPType3IEC --> PU : WindContPType3IEC.updip
click PU href "../PU"
WindContPType3IEC : WindContPType3IEC.WindDynamicsLookupTable
WindContPType3IEC --> WindDynamicsLookupTable : WindContPType3IEC.WindDynamicsLookupTable
click WindDynamicsLookupTable href "../WindDynamicsLookupTable"
WindContPType3IEC : WindContPType3IEC.WindTurbineType3IEC
WindContPType3IEC --> WindTurbineType3IEC : WindContPType3IEC.WindTurbineType3IEC
click WindTurbineType3IEC href "../WindTurbineType3IEC"
WindContPType3IEC : WindContPType3IEC.zeta
Inheritance
- IdentifiedObject
- WindContPType3IEC
Attributes
Name | URI | Cardinality and Range | Description | Inheritance |
---|---|---|---|---|
dpmax | cim:WindContPType3IEC.dpmax | 1 PU |
Maximum wind turbine power ramp rate (dpmax) | direct |
dprefmax | cim:WindContPType3IEC.dprefmax | 1 PU |
Maximum ramp rate of wind turbine reference power (dprefmax</s... | direct |
dprefmin | cim:WindContPType3IEC.dprefmin | 1 PU |
Minimum ramp rate of wind turbine reference power (dprefmin</s... | direct |
dthetamax | cim:WindContPType3IEC.dthetamax | 1 PU |
Ramp limitation of torque, required in some grid codes (dtmax<... | direct |
dthetamaxuvrt | cim:WindContPType3IEC.dthetamaxuvrt | 1 PU |
Limitation of torque rise rate during UVRT (dthetamaxUVRT</sub... | direct |
kdtd | cim:WindContPType3IEC.kdtd | 1 PU |
Gain for active drive train damping (KDTD) | direct |
kip | cim:WindContPType3IEC.kip | 1 PU |
PI controller integration parameter (KIp) | direct |
kpp | cim:WindContPType3IEC.kpp | 1 PU |
PI controller proportional gain (KPp) | direct |
mpuvrt | cim:WindContPType3IEC.mpuvrt | 1 boolean |
Enable UVRT power control mode (MpUVRT) | direct |
omegaoffset | cim:WindContPType3IEC.omegaoffset | 1 PU |
Offset to reference value that limits controller action during rotor speed ch... | direct |
pdtdmax | cim:WindContPType3IEC.pdtdmax | 1 PU |
Maximum active drive train damping power (pDTDmax) | direct |
tdvs | cim:WindContPType3IEC.tdvs | 1 Seconds |
Time delay after deep voltage sags (TDVS)... | direct |
thetaemin | cim:WindContPType3IEC.thetaemin | 1 PU |
Minimum electrical generator torque (temin) | direct |
thetauscale | cim:WindContPType3IEC.thetauscale | 1 PU |
Voltage scaling factor of reset-torque (tuscale) | direct |
tomegafiltp3 | cim:WindContPType3IEC.tomegafiltp3 | 1 Seconds |
Filter time constant for generator speed measurement (Tomegafiltp... | direct |
tpfiltp3 | cim:WindContPType3IEC.tpfiltp3 | 1 Seconds |
Filter time constant for power measurement (Tpfiltp3) (>... | direct |
tpord | cim:WindContPType3IEC.tpord | 1 PU |
Time constant in power order lag (Tpord) | direct |
tufiltp3 | cim:WindContPType3IEC.tufiltp3 | 1 Seconds |
Filter time constant for voltage measurement (Tufiltp3) (&g... | direct |
tomegaref | cim:WindContPType3IEC.tomegaref | 1 Seconds |
Time constant in speed reference filter (Tomega,ref) (>=... | direct |
udvs | cim:WindContPType3IEC.udvs | 1 PU |
Voltage limit for hold UVRT status after deep voltage sags (uD... | direct |
updip | cim:WindContPType3IEC.updip | 1 PU |
Voltage dip threshold for P-control (uPdip) | direct |
omegadtd | cim:WindContPType3IEC.omegadtd | 1 PU |
Active drive train damping frequency (omegaDTD) | direct |
zeta | cim:WindContPType3IEC.zeta | 1 float |
Coefficient for active drive train damping (zeta) | direct |
WindTurbineType3IEC | cim:WindContPType3IEC.WindTurbineType3IEC | 1 WindTurbineType3IEC |
Wind turbine type 3 model with which this wind control P type 3 model is asso... | direct |
WindDynamicsLookupTable | cim:WindContPType3IEC.WindDynamicsLookupTable | 1..* WindDynamicsLookupTable |
The wind dynamics lookup table associated with this P control type 3 model | direct |
description | cim:IdentifiedObject.description | 0..1 string |
The description is a free human readable text describing or naming the object | IdentifiedObject |
mRID | cim:IdentifiedObject.mRID | 1 string |
Master resource identifier issued by a model authority | IdentifiedObject |
name | cim:IdentifiedObject.name | 0..1 string |
The name is any free human readable and possibly non unique text naming the o... | IdentifiedObject |
Usages
used by | used in | type | used |
---|---|---|---|
WindDynamicsLookupTable | WindContPType3IEC | range | WindContPType3IEC |
WindTurbineType3IEC | WindContPType3IEC | range | WindContPType3IEC |
Identifier and Mapping Information
Schema Source
- from schema: http://iec.ch/TC57/ns/CIM/Dynamics-EU#Package_DynamicsProfile
Mappings
Mapping Type | Mapped Value |
---|---|
self | cim:WindContPType3IEC |
native | this:WindContPType3IEC |