Skip to content

WindContQIEC

Q control model.

Reference: IEC 61400-27-1:2015, 5.6.5.7.

URI: cim:WindContQIEC
Type: Class

 classDiagram
    class WindContQIEC
    click WindContQIEC href "../WindContQIEC"
      IdentifiedObject <|-- WindContQIEC
        click IdentifiedObject href "../IdentifiedObject"

      WindContQIEC : IdentifiedObject.description

      WindContQIEC : WindContQIEC.iqh1

          WindContQIEC --> PU : WindContQIEC.iqh1
          click PU href "../PU"

      WindContQIEC : WindContQIEC.iqmax

          WindContQIEC --> PU : WindContQIEC.iqmax
          click PU href "../PU"

      WindContQIEC : WindContQIEC.iqmin

          WindContQIEC --> PU : WindContQIEC.iqmin
          click PU href "../PU"

      WindContQIEC : WindContQIEC.iqpost

          WindContQIEC --> PU : WindContQIEC.iqpost
          click PU href "../PU"

      WindContQIEC : WindContQIEC.kiq

          WindContQIEC --> PU : WindContQIEC.kiq
          click PU href "../PU"

      WindContQIEC : WindContQIEC.kiu

          WindContQIEC --> PU : WindContQIEC.kiu
          click PU href "../PU"

      WindContQIEC : WindContQIEC.kpq

          WindContQIEC --> PU : WindContQIEC.kpq
          click PU href "../PU"

      WindContQIEC : WindContQIEC.kpu

          WindContQIEC --> PU : WindContQIEC.kpu
          click PU href "../PU"

      WindContQIEC : WindContQIEC.kqv

          WindContQIEC --> PU : WindContQIEC.kqv
          click PU href "../PU"

      WindContQIEC : IdentifiedObject.mRID

      WindContQIEC : IdentifiedObject.name

      WindContQIEC : WindContQIEC.rdroop

          WindContQIEC --> PU : WindContQIEC.rdroop
          click PU href "../PU"

      WindContQIEC : WindContQIEC.tpfiltq

          WindContQIEC --> Seconds : WindContQIEC.tpfiltq
          click Seconds href "../Seconds"

      WindContQIEC : WindContQIEC.tpost

          WindContQIEC --> Seconds : WindContQIEC.tpost
          click Seconds href "../Seconds"

      WindContQIEC : WindContQIEC.tqord

          WindContQIEC --> Seconds : WindContQIEC.tqord
          click Seconds href "../Seconds"

      WindContQIEC : WindContQIEC.tufiltq

          WindContQIEC --> Seconds : WindContQIEC.tufiltq
          click Seconds href "../Seconds"

      WindContQIEC : WindContQIEC.udb1

          WindContQIEC --> PU : WindContQIEC.udb1
          click PU href "../PU"

      WindContQIEC : WindContQIEC.udb2

          WindContQIEC --> PU : WindContQIEC.udb2
          click PU href "../PU"

      WindContQIEC : WindContQIEC.umax

          WindContQIEC --> PU : WindContQIEC.umax
          click PU href "../PU"

      WindContQIEC : WindContQIEC.umin

          WindContQIEC --> PU : WindContQIEC.umin
          click PU href "../PU"

      WindContQIEC : WindContQIEC.uqdip

          WindContQIEC --> PU : WindContQIEC.uqdip
          click PU href "../PU"

      WindContQIEC : WindContQIEC.uref0

          WindContQIEC --> PU : WindContQIEC.uref0
          click PU href "../PU"

      WindContQIEC : WindContQIEC.windQcontrolModesType

          WindContQIEC --> WindQcontrolModeKind : WindContQIEC.windQcontrolModesType
          click WindQcontrolModeKind href "../WindQcontrolModeKind"

      WindContQIEC : WindContQIEC.WindTurbineType3or4IEC

          WindContQIEC --> WindTurbineType3or4IEC : WindContQIEC.WindTurbineType3or4IEC
          click WindTurbineType3or4IEC href "../WindTurbineType3or4IEC"

      WindContQIEC : WindContQIEC.windUVRTQcontrolModesType

          WindContQIEC --> WindUVRTQcontrolModeKind : WindContQIEC.windUVRTQcontrolModesType
          click WindUVRTQcontrolModeKind href "../WindUVRTQcontrolModeKind"

      WindContQIEC : WindContQIEC.xdroop

          WindContQIEC --> PU : WindContQIEC.xdroop
          click PU href "../PU"

Inheritance

Attributes

Name URI Cardinality and Range Description Inheritance
iqh1 cim:WindContQIEC.iqh1 1
PU
Maximum reactive current injection during dip (iqh1) direct
iqmax cim:WindContQIEC.iqmax 1
PU
Maximum reactive current injection (iqmax) (> Win... direct
iqmin cim:WindContQIEC.iqmin 1
PU
Minimum reactive current injection (iqmin) (< Win... direct
iqpost cim:WindContQIEC.iqpost 1
PU
Post fault reactive current injection (iqpost) direct
kiq cim:WindContQIEC.kiq 1
PU
Reactive power PI controller integration gain (KI,q) direct
kiu cim:WindContQIEC.kiu 1
PU
Voltage PI controller integration gain (KI,u) direct
kpq cim:WindContQIEC.kpq 1
PU
Reactive power PI controller proportional gain (KP,q... direct
kpu cim:WindContQIEC.kpu 1
PU
Voltage PI controller proportional gain (KP,u) direct
kqv cim:WindContQIEC.kqv 1
PU
Voltage scaling factor for UVRT current (Kqv) direct
tpfiltq cim:WindContQIEC.tpfiltq 1
Seconds
Power measurement filter time constant (Tpfiltq) (&g... direct
rdroop cim:WindContQIEC.rdroop 1
PU
Resistive component of voltage drop impedance (rdroop</i... direct
tufiltq cim:WindContQIEC.tufiltq 1
Seconds
Voltage measurement filter time constant (Tufiltq) (... direct
tpost cim:WindContQIEC.tpost 1
Seconds
Length of time period where post fault reactive power is injected (T<i... direct
tqord cim:WindContQIEC.tqord 1
Seconds
Time constant in reactive power order lag (Tqord) (&... direct
udb1 cim:WindContQIEC.udb1 1
PU
Voltage deadband lower limit (udb1) direct
udb2 cim:WindContQIEC.udb2 1
PU
Voltage deadband upper limit (udb2) direct
umax cim:WindContQIEC.umax 1
PU
Maximum voltage in voltage PI controller integral term (umax</... direct
umin cim:WindContQIEC.umin 1
PU
Minimum voltage in voltage PI controller integral term (umin</... direct
uqdip cim:WindContQIEC.uqdip 1
PU
Voltage threshold for UVRT detection in Q control (uqdip... direct
uref0 cim:WindContQIEC.uref0 1
PU
User-defined bias in voltage reference (uref0) direct
windQcontrolModesType cim:WindContQIEC.windQcontrolModesType 1
WindQcontrolModeKind
Types of general wind turbine Q control modes (MqG) direct
windUVRTQcontrolModesType cim:WindContQIEC.windUVRTQcontrolModesType 1
WindUVRTQcontrolModeKind
Types of UVRT Q control modes (MqUVRT) direct
xdroop cim:WindContQIEC.xdroop 1
PU
Inductive component of voltage drop impedance (xdroop</i... direct
WindTurbineType3or4IEC cim:WindContQIEC.WindTurbineType3or4IEC 1
WindTurbineType3or4IEC
Wind turbine type 3 or type 4 model with which this reactive control model is... direct
description cim:IdentifiedObject.description 0..1
string
The description is a free human readable text describing or naming the object IdentifiedObject
mRID cim:IdentifiedObject.mRID 1
string
Master resource identifier issued by a model authority IdentifiedObject
name cim:IdentifiedObject.name 0..1
string
The name is any free human readable and possibly non unique text naming the o... IdentifiedObject

Usages

used by used in type used
WindTurbineType3IEC WIndContQIEC range WindContQIEC
WindTurbineType3or4IEC WIndContQIEC range WindContQIEC
WindTurbineType4aIEC WIndContQIEC range WindContQIEC
WindTurbineType4bIEC WIndContQIEC range WindContQIEC
WindTurbineType4IEC WIndContQIEC range WindContQIEC

Identifier and Mapping Information

Schema Source

  • from schema: http://iec.ch/TC57/ns/CIM/Dynamics-EU#Package_DynamicsProfile

Mappings

Mapping Type Mapped Value
self cim:WindContQIEC
native this:WindContQIEC