Skip to content

WindGenType3bIEC

IEC type 3B generator set model.

Reference: IEC 61400-27-1:2015, 5.6.3.3.

URI: cim:WindGenType3bIEC
Type: Class

 classDiagram
    class WindGenType3bIEC
    click WindGenType3bIEC href "../WindGenType3bIEC"
      WindGenType3IEC <|-- WindGenType3bIEC
        click WindGenType3IEC href "../WindGenType3IEC"

      WindGenType3bIEC : IdentifiedObject.description

      WindGenType3bIEC : WindGenType3IEC.dipmax

          WindGenType3bIEC --> PU : WindGenType3IEC.dipmax
          click PU href "../PU"

      WindGenType3bIEC : WindGenType3IEC.diqmax

          WindGenType3bIEC --> PU : WindGenType3IEC.diqmax
          click PU href "../PU"

      WindGenType3bIEC : IdentifiedObject.mRID

      WindGenType3bIEC : WindGenType3bIEC.mwtcwp

      WindGenType3bIEC : IdentifiedObject.name

      WindGenType3bIEC : WindGenType3bIEC.tg

          WindGenType3bIEC --> Seconds : WindGenType3bIEC.tg
          click Seconds href "../Seconds"

      WindGenType3bIEC : WindGenType3bIEC.two

          WindGenType3bIEC --> Seconds : WindGenType3bIEC.two
          click Seconds href "../Seconds"

      WindGenType3bIEC : WindGenType3bIEC.WindDynamicsLookupTable

          WindGenType3bIEC --> WindDynamicsLookupTable : WindGenType3bIEC.WindDynamicsLookupTable
          click WindDynamicsLookupTable href "../WindDynamicsLookupTable"

      WindGenType3bIEC : WindGenType3IEC.WindTurbineType3IEC

          WindGenType3bIEC --> WindTurbineType3IEC : WindGenType3IEC.WindTurbineType3IEC
          click WindTurbineType3IEC href "../WindTurbineType3IEC"

      WindGenType3bIEC : WindGenType3IEC.xs

          WindGenType3bIEC --> PU : WindGenType3IEC.xs
          click PU href "../PU"

Inheritance

Attributes

Name URI Cardinality and Range Description Inheritance
WindDynamicsLookupTable cim:WindGenType3bIEC.WindDynamicsLookupTable 1..*
WindDynamicsLookupTable
The wind dynamics lookup table associated with this generator type 3B model direct
mwtcwp cim:WindGenType3bIEC.mwtcwp 1
boolean
Crowbar control mode (MWTcwp) direct
tg cim:WindGenType3bIEC.tg 1
Seconds
Current generation time constant (Tg) (>= 0) direct
two cim:WindGenType3bIEC.two 1
Seconds
Time constant for crowbar washout filter (Two) (>... direct
dipmax cim:WindGenType3IEC.dipmax 1
PU
Maximum active current ramp rate (dipmax) WindGenType3IEC
diqmax cim:WindGenType3IEC.diqmax 1
PU
Maximum reactive current ramp rate (diqmax) WindGenType3IEC
xs cim:WindGenType3IEC.xs 1
PU
Electromagnetic transient reactance (xS) WindGenType3IEC
WindTurbineType3IEC cim:WindGenType3IEC.WindTurbineType3IEC 0..1
WindTurbineType3IEC
Wind turbine type 3 model with which this wind generator type 3 is associated WindGenType3IEC
description cim:IdentifiedObject.description 0..1
string
The description is a free human readable text describing or naming the object IdentifiedObject
mRID cim:IdentifiedObject.mRID 1
string
Master resource identifier issued by a model authority IdentifiedObject
name cim:IdentifiedObject.name 0..1
string
The name is any free human readable and possibly non unique text naming the o... IdentifiedObject

Usages

used by used in type used
WindDynamicsLookupTable WindGenType3bIEC range WindGenType3bIEC

Identifier and Mapping Information

Schema Source

  • from schema: http://iec.ch/TC57/ns/CIM/Dynamics-EU#Package_DynamicsProfile

Mappings

Mapping Type Mapped Value
self cim:WindGenType3bIEC
native this:WindGenType3bIEC