Measurement quality flags. Bits 0-10 are defined for substation automation in IEC 61850-7-3. Bits 11-15 are reserved for future expansion by that document. Bits 16-31 are reserved for EMS applications.

URI: cim:MeasurementValueQuality
Type: Class

 classDiagram
    class MeasurementValueQuality
    click MeasurementValueQuality href "../MeasurementValueQuality"
      Quality61850 <|-- MeasurementValueQuality
        click Quality61850 href "../Quality61850"

      MeasurementValueQuality : Quality61850.badReference

      MeasurementValueQuality : Quality61850.estimatorReplaced

      MeasurementValueQuality : Quality61850.failure

      MeasurementValueQuality : MeasurementValueQuality.MeasurementValue

          MeasurementValueQuality --> MeasurementValue : MeasurementValueQuality.MeasurementValue
          click MeasurementValue href "../MeasurementValue"

      MeasurementValueQuality : Quality61850.oldData

      MeasurementValueQuality : Quality61850.operatorBlocked

      MeasurementValueQuality : Quality61850.oscillatory

      MeasurementValueQuality : Quality61850.outOfRange

      MeasurementValueQuality : Quality61850.overFlow

      MeasurementValueQuality : Quality61850.source

          MeasurementValueQuality --> Source : Quality61850.source
          click Source href "../Source"

      MeasurementValueQuality : Quality61850.suspect

      MeasurementValueQuality : Quality61850.test

      MeasurementValueQuality : Quality61850.validity

          MeasurementValueQuality --> Validity : Quality61850.validity
          click Validity href "../Validity"

Inheritance

Attributes

Name URI Cardinality and Range Description Inheritance
MeasurementValue cim:MeasurementValueQuality.MeasurementValue 1
MeasurementValue
A MeasurementValue has a MeasurementValueQuality associated with it direct
badReference cim:Quality61850.badReference 0..1
boolean
Measurement value may be incorrect due to a reference being out of calibratio... Quality61850
estimatorReplaced cim:Quality61850.estimatorReplaced 0..1
boolean
Value has been replaced by State Estimator Quality61850
failure cim:Quality61850.failure 0..1
boolean
This identifier indicates that a supervision function has detected an interna... Quality61850
oldData cim:Quality61850.oldData 0..1
boolean
Measurement value is old and possibly invalid, as it has not been successfull... Quality61850
operatorBlocked cim:Quality61850.operatorBlocked 0..1
boolean
Measurement value is blocked and hence unavailable for transmission Quality61850
oscillatory cim:Quality61850.oscillatory 0..1
boolean
To prevent some overload of the communication it is sensible to detect and su... Quality61850
outOfRange cim:Quality61850.outOfRange 0..1
boolean
Measurement value is beyond a predefined range of value Quality61850
overFlow cim:Quality61850.overFlow 0..1
boolean
Measurement value is beyond the capability of being represented properly Quality61850
source cim:Quality61850.source 0..1
Source
Source gives information related to the origin of a value Quality61850
suspect cim:Quality61850.suspect 0..1
boolean
A correlation function has detected that the value is not consistent with oth... Quality61850
test cim:Quality61850.test 0..1
boolean
Measurement value is transmitted for test purposes Quality61850
validity cim:Quality61850.validity 0..1
Validity
Validity of the measurement value Quality61850

Usages

used by used in type used
AccumulatorValue MeasurementValueQuality range MeasurementValueQuality
AnalogValue MeasurementValueQuality range MeasurementValueQuality
DiscreteValue MeasurementValueQuality range MeasurementValueQuality
MeasurementValue MeasurementValueQuality range MeasurementValueQuality
StringMeasurementValue MeasurementValueQuality range MeasurementValueQuality

Identifier and Mapping Information

Schema Source

  • from schema: http://iec.ch/TC57/ns/CIM/Operation-EU#Package_OperationProfile

Mappings

Mapping Type Mapped Value
self cim:MeasurementValueQuality
native this:MeasurementValueQuality