ExternalNetworkInjection
This class represents the external network and it is used for IEC 60909 calculations.
URI: cim:ExternalNetworkInjection
Type: Class
classDiagram
class ExternalNetworkInjection
click ExternalNetworkInjection href "../ExternalNetworkInjection"
RegulatingCondEq <|-- ExternalNetworkInjection
click RegulatingCondEq href "../RegulatingCondEq"
ExternalNetworkInjection : ExternalNetworkInjection.ikSecond
ExternalNetworkInjection : ExternalNetworkInjection.maxInitialSymShCCurrent
ExternalNetworkInjection --> CurrentFlow : ExternalNetworkInjection.maxInitialSymShCCurrent
click CurrentFlow href "../CurrentFlow"
ExternalNetworkInjection : ExternalNetworkInjection.maxR0ToX0Ratio
ExternalNetworkInjection : ExternalNetworkInjection.maxR1ToX1Ratio
ExternalNetworkInjection : ExternalNetworkInjection.maxZ0ToZ1Ratio
ExternalNetworkInjection : ExternalNetworkInjection.minInitialSymShCCurrent
ExternalNetworkInjection --> CurrentFlow : ExternalNetworkInjection.minInitialSymShCCurrent
click CurrentFlow href "../CurrentFlow"
ExternalNetworkInjection : ExternalNetworkInjection.minR0ToX0Ratio
ExternalNetworkInjection : ExternalNetworkInjection.minR1ToX1Ratio
ExternalNetworkInjection : ExternalNetworkInjection.minZ0ToZ1Ratio
ExternalNetworkInjection : IdentifiedObject.mRID
ExternalNetworkInjection : ExternalNetworkInjection.voltageFactor
ExternalNetworkInjection --> PU : ExternalNetworkInjection.voltageFactor
click PU href "../PU"
Inheritance
- IdentifiedObject
- PowerSystemResource
- Equipment
- ConductingEquipment
- EnergyConnection
- RegulatingCondEq
- ExternalNetworkInjection
- RegulatingCondEq
- EnergyConnection
- ConductingEquipment
- Equipment
- PowerSystemResource
Attributes
Name | URI | Cardinality and Range | Description | Inheritance |
---|---|---|---|---|
ikSecond | cim:ExternalNetworkInjection.ikSecond | 0..1 boolean |
Indicates whether initial symmetrical short-circuit current and power have be... | direct |
maxInitialSymShCCurrent | cim:ExternalNetworkInjection.maxInitialSymShCCurrent | 1 CurrentFlow |
Maximum initial symmetrical short-circuit currents (Ik" max) in A (Ik" = Sk"/... | direct |
maxR0ToX0Ratio | cim:ExternalNetworkInjection.maxR0ToX0Ratio | 1 float |
Maximum ratio of zero sequence resistance of Network Feeder to its zero seque... | direct |
maxR1ToX1Ratio | cim:ExternalNetworkInjection.maxR1ToX1Ratio | 1 float |
Maximum ratio of positive sequence resistance of Network Feeder to its positi... | direct |
maxZ0ToZ1Ratio | cim:ExternalNetworkInjection.maxZ0ToZ1Ratio | 1 float |
Maximum ratio of zero sequence impedance to its positive sequence impedance (... | direct |
minInitialSymShCCurrent | cim:ExternalNetworkInjection.minInitialSymShCCurrent | 1 CurrentFlow |
Minimum initial symmetrical short-circuit currents (Ik" min) in A (Ik" = Sk"/... | direct |
minR0ToX0Ratio | cim:ExternalNetworkInjection.minR0ToX0Ratio | 1 float |
Indicates whether initial symmetrical short-circuit current and power have be... | direct |
minR1ToX1Ratio | cim:ExternalNetworkInjection.minR1ToX1Ratio | 1 float |
Minimum ratio of positive sequence resistance of Network Feeder to its positi... | direct |
minZ0ToZ1Ratio | cim:ExternalNetworkInjection.minZ0ToZ1Ratio | 1 float |
Minimum ratio of zero sequence impedance to its positive sequence impedance (... | direct |
voltageFactor | cim:ExternalNetworkInjection.voltageFactor | 0..1 PU |
Voltage factor in pu, which was used to calculate short-circuit current Ik" a... | direct |
mRID | cim:IdentifiedObject.mRID | 1 string |
Master resource identifier issued by a model authority | IdentifiedObject |
Identifier and Mapping Information
Schema Source
- from schema: http://iec.ch/TC57/ns/CIM/ShortCircuit-EU#Package_ShortCircuitProfile
Mappings
Mapping Type | Mapped Value |
---|---|
self | cim:ExternalNetworkInjection |
native | this:ExternalNetworkInjection |