Measurement

A Measurement represents any measured, calculated or non-measured non-calculated quantity. Any piece of equipment may contain Measurements, e.g. a substation may have temperature measurements and door open indications, a transformer may have oil temperature and tank pressure measurements, a bay may contain a number of power flow measurements and a Breaker may contain a switch status measurement. The PSR - Measurement association is intended to capture this use of Measurement and is included in the naming hierarchy based on EquipmentContainer. The naming hierarchy typically has Measurements as leaves, e.g. Substation-VoltageLevel-Bay-Switch-Measurement. Some Measurements represent quantities related to a particular sensor location in the network, e.g. a voltage transformer (VT) or potential transformer (PT) at a busbar or a current transformer (CT) at the bar between a breaker and an isolator. The sensing position is not captured in the PSR - Measurement association. Instead it is captured by the Measurement - Terminal association that is used to define the sensing location in the network topology. The location is defined by the connection of the Terminal to ConductingEquipment. If both a Terminal and PSR are associated, and the PSR is of type ConductingEquipment, the associated Terminal should belong to that ConductingEquipment instance. When the sensor location is needed both Measurement-PSR and Measurement-Terminal are used. The Measurement-Terminal association is never used alone.

Type

Class

URI

cim:Measurement

CIM standard (perspective)

IEC61970 (Grid)

Class hierarchy

Slots

Associated classes
Figure 1. Associated classes
Name Type Description Inherited from

PowerSystemResource

0..1
PowerSystemResource

The power system resource that contains the measurement.

n/a

Terminal

0..1
ACDCTerminal

One or more measurements may be associated with a terminal in the network.

n/a

measurementType

0..1
string

Specifies the type of measurement. For example, this specifies if the measurement represents an indoor temperature, outdoor...

n/a

unitMultiplier

0..1
UnitMultiplier

The unit multiplier of the measured quantity.

n/a

unitSymbol

0..1
UnitSymbol

The unit of measure of the measured quantity.

n/a

description

0..1
string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to...

IdentifiedObject

europeanArticleNumberEAN

0..1
string

The attribute is used for an exchange of the EAN code (European Article Number). The length of the string is 16 characters...

IdentifiedObject

mRID

0..1
string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is...

IdentifiedObject


description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

europeanArticleNumberEAN

The attribute is used for an exchange of the EAN code (European Article Number). The length of the string is 16 characters as defined by the EAN code.

URI

nl:IdentifiedObject.europeanArticleNumberEAN

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

measurementType

Specifies the type of measurement. For example, this specifies if the measurement represents an indoor temperature, outdoor temperature, bus voltage, line flow, etc. When the measurementType is set to "Specialization", the type of Measurement is defined in more detail by the specialized class which inherits from Measurement.

URI

cim:Measurement.measurementType

Cardinality

0..1

Type

string

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

PowerSystemResource

The power system resource that contains the measurement.

URI

cim:Measurement.PowerSystemResource

Cardinality

0..1

Type

PowerSystemResource

Terminal

One or more measurements may be associated with a terminal in the network.

URI

cim:Measurement.Terminal

Cardinality

0..1

Type

ACDCTerminal

unitMultiplier

The unit multiplier of the measured quantity.

URI

cim:Measurement.unitMultiplier

Cardinality

0..1

Type

UnitMultiplier

unitSymbol

The unit of measure of the measured quantity.

URI

cim:Measurement.unitSymbol

Cardinality

0..1

Type

UnitSymbol

Used by