RatioTapChangerTablePoint
Describes each tap step in the ratio tap changer tabular curve.
| Type | Class | 
|---|---|
| URI | 
 | 
| CIM standard (perspective) | IEC61970 (Grid) | 
Slots
| Name | Cardinality | Type | Description | 
|---|---|---|---|
| 1 | Table of this point. | ||
| 0..1 | The magnetizing branch susceptance deviation as a percentage of nominal value. The actual susceptance is calculated as follows: calculated magnetizing susceptance = b(nominal) * (1 + b(from this class)/100). The b(nominal) is defined as the static magnetizing susceptance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form. | ||
| 0..1 | The magnetizing branch conductance deviation as a percentage of nominal value. The actual conductance is calculated as follows: calculated magnetizing conductance = g(nominal) * (1 + g(from this class)/100). The g(nominal) is defined as the static magnetizing conductance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form. | ||
| 0..1 | The resistance deviation as a percentage of nominal value. The actual reactance is calculated as follows: calculated resistance = r(nominal) * (1 + r(from this class)/100). The r(nominal) is defined as the static resistance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form. | ||
| 0..1 | The voltage at the tap step divided by rated voltage of the transformer end having the tap changer. Hence this is a value close to one. For example, if the ratio at step 1 is 1.01, and the rated voltage of the transformer end is 110kV, then the voltage obtained by setting the tap changer to step 1 to is 111.1kV. | ||
| 0..1 | The tap step. | ||
| 0..1 | The series reactance deviation as a percentage of nominal value. The actual reactance is calculated as follows: calculated reactance = x(nominal) * (1 + x(from this class)/100). The x(nominal) is defined as the static series reactance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form. | 
b
The magnetizing branch susceptance deviation as a percentage of nominal value. The actual susceptance is calculated as follows: calculated magnetizing susceptance = b(nominal) * (1 + b(from this class)/100). The b(nominal) is defined as the static magnetizing susceptance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form.
| URI | 
 | 
|---|---|
| Cardinality | 0..1 | 
| Type | |
| Inherited from | 
g
The magnetizing branch conductance deviation as a percentage of nominal value. The actual conductance is calculated as follows: calculated magnetizing conductance = g(nominal) * (1 + g(from this class)/100). The g(nominal) is defined as the static magnetizing conductance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form.
| URI | 
 | 
|---|---|
| Cardinality | 0..1 | 
| Type | |
| Inherited from | 
r
The resistance deviation as a percentage of nominal value. The actual reactance is calculated as follows: calculated resistance = r(nominal) * (1 + r(from this class)/100). The r(nominal) is defined as the static resistance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form.
| URI | 
 | 
|---|---|
| Cardinality | 0..1 | 
| Type | |
| Inherited from | 
ratio
The voltage at the tap step divided by rated voltage of the transformer end having the tap changer. Hence this is a value close to one. For example, if the ratio at step 1 is 1.01, and the rated voltage of the transformer end is 110kV, then the voltage obtained by setting the tap changer to step 1 to is 111.1kV.
| URI | 
 | 
|---|---|
| Cardinality | 0..1 | 
| Type | |
| Inherited from | 
RatioTapChangerTable
Table of this point.
| URI | 
 | 
|---|---|
| Cardinality | 1 | 
| Type | 
x
The series reactance deviation as a percentage of nominal value. The actual reactance is calculated as follows: calculated reactance = x(nominal) * (1 + x(from this class)/100). The x(nominal) is defined as the static series reactance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form.
| URI | 
 | 
|---|---|
| Cardinality | 0..1 | 
| Type | |
| Inherited from |