ExcBBC

Transformer fed static excitation system (static with ABB regulator). This model represents a static excitation system in which a gated thyristor bridge fed by a transformer at the main generator terminals feeds the main generator directly.

Type

Class

URI

cim:ExcBBC

CIM standard (perspective)

IEC61970 (Grid)

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

InstanceSet

1

InstanceSet

Dataset containing the data objects.

SynchronousMachineDynamics

1

SynchronousMachineDynamics

Synchronous machine model with which this excitation system model is associated.

VoltageCompensatorDynamics

1

VoltageCompensatorDynamics

Voltage compensator model associated with this excitation system model.

efdmax

0..1

PU

Maximum open circuit exciter voltage (Efdmax) (> ExcBBC.efdmin). Typical value = 5.

efdmin

0..1

PU

Minimum open circuit exciter voltage (Efdmin) (< ExcBBC.efdmax). Typical value = -5.

k

0..1

PU

Steady state gain (K) (not = 0). Typical value = 300.

switch

0..1

boolean

Supplementary signal routing selector (switch). true = Vs connected to 3rd summing point false = Vs connected to 1st summing point (see diagram). Typical value = false.

t1

0..1

Seconds

Controller time constant (T1) (>= 0). Typical value = 6.

t2

0..1

Seconds

Controller time constant (T2) (>= 0). Typical value = 1.

t3

0..1

Seconds

Lead/lag time constant (T3) (>= 0). If = 0, block is bypassed. Typical value = 0,05.

t4

0..1

Seconds

Lead/lag time constant (T4) (>= 0). If = 0, block is bypassed. Typical value = 0,01.

vrmax

0..1

PU

Maximum control element output (Vrmax) (> ExcBBC.vrmin). Typical value = 5.

vrmin

0..1

PU

Minimum control element output (Vrmin) (< ExcBBC.vrmax). Typical value = -5.

xe

0..1

PU

Effective excitation transformer reactance (Xe) (>= 0). Xe models the regulation of the transformer/rectifier unit. Typical value = 0,05.

DiscontinuousExcitationControlDynamics

0..1

DiscontinuousExcitationControlDynamics

Discontinuous excitation control model associated with this excitation system model.

OverexcitationLimiterDynamics

0..1

OverexcitationLimiterDynamics

Overexcitation limiter model associated with this excitation system model.

PFVArControllerType1Dynamics

0..1

PFVArControllerType1Dynamics

Power factor or VAr controller type 1 model associated with this excitation system model.

PFVArControllerType2Dynamics

0..1

PFVArControllerType2Dynamics

Power factor or VAr controller type 2 model associated with this excitation system model.

PowerSystemStabilizerDynamics

0..1

PowerSystemStabilizerDynamics

Power system stabilizer model associated with this excitation system model.

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

UnderexcitationLimiterDynamics

0..1

UnderexcitationLimiterDynamics

Undrexcitation limiter model associated with this excitation system model.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

enabled

0..1

boolean

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

DiscontinuousExcitationControlDynamics

Discontinuous excitation control model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.DiscontinuousExcitationControlDynamics

Cardinality

0..1

Type

DiscontinuousExcitationControlDynamics

Inherited from

ExcitationSystemDynamics

efdmax

Maximum open circuit exciter voltage (Efdmax) (> ExcBBC.efdmin). Typical value = 5.

URI

cim:ExcBBC.efdmax

Cardinality

0..1

Type

PU

efdmin

Minimum open circuit exciter voltage (Efdmin) (< ExcBBC.efdmax). Typical value = -5.

URI

cim:ExcBBC.efdmin

Cardinality

0..1

Type

PU

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

URI

cim:DynamicsFunctionBlock.enabled

Cardinality

0..1

Type

boolean

Inherited from

DynamicsFunctionBlock

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

k

Steady state gain (K) (not = 0). Typical value = 300.

URI

cim:ExcBBC.k

Cardinality

0..1

Type

PU

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

OverexcitationLimiterDynamics

Overexcitation limiter model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.OverexcitationLimiterDynamics

Cardinality

0..1

Type

OverexcitationLimiterDynamics

Inherited from

ExcitationSystemDynamics

PFVArControllerType1Dynamics

Power factor or VAr controller type 1 model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.PFVArControllerType1Dynamics

Cardinality

0..1

Type

PFVArControllerType1Dynamics

Inherited from

ExcitationSystemDynamics

PFVArControllerType2Dynamics

Power factor or VAr controller type 2 model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.PFVArControllerType2Dynamics

Cardinality

0..1

Type

PFVArControllerType2Dynamics

Inherited from

ExcitationSystemDynamics

PowerSystemStabilizerDynamics

Power system stabilizer model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.PowerSystemStabilizerDynamics

Cardinality

0..1

Type

PowerSystemStabilizerDynamics

Inherited from

ExcitationSystemDynamics

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

switch

Supplementary signal routing selector (switch). true = Vs connected to 3rd summing point false = Vs connected to 1st summing point (see diagram). Typical value = false.

URI

cim:ExcBBC.switch

Cardinality

0..1

Type

boolean

SynchronousMachineDynamics

Synchronous machine model with which this excitation system model is associated.

URI

cim:ExcitationSystemDynamics.SynchronousMachineDynamics

Cardinality

1

Type

SynchronousMachineDynamics

Inherited from

ExcitationSystemDynamics

t1

Controller time constant (T1) (>= 0). Typical value = 6.

URI

cim:ExcBBC.t1

Cardinality

0..1

Type

Seconds

t2

Controller time constant (T2) (>= 0). Typical value = 1.

URI

cim:ExcBBC.t2

Cardinality

0..1

Type

Seconds

t3

Lead/lag time constant (T3) (>= 0). If = 0, block is bypassed. Typical value = 0,05.

URI

cim:ExcBBC.t3

Cardinality

0..1

Type

Seconds

t4

Lead/lag time constant (T4) (>= 0). If = 0, block is bypassed. Typical value = 0,01.

URI

cim:ExcBBC.t4

Cardinality

0..1

Type

Seconds

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

UnderexcitationLimiterDynamics

Undrexcitation limiter model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.UnderexcitationLimiterDynamics

Cardinality

0..1

Type

UnderexcitationLimiterDynamics

Inherited from

ExcitationSystemDynamics

VoltageCompensatorDynamics

Voltage compensator model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.VoltageCompensatorDynamics

Cardinality

1

Type

VoltageCompensatorDynamics

Inherited from

ExcitationSystemDynamics

vrmax

Maximum control element output (Vrmax) (> ExcBBC.vrmin). Typical value = 5.

URI

cim:ExcBBC.vrmax

Cardinality

0..1

Type

PU

vrmin

Minimum control element output (Vrmin) (< ExcBBC.vrmax). Typical value = -5.

URI

cim:ExcBBC.vrmin

Cardinality

0..1

Type

PU

xe

Effective excitation transformer reactance (Xe) (>= 0). Xe models the regulation of the transformer/rectifier unit. Typical value = 0,05.

URI

cim:ExcBBC.xe

Cardinality

0..1

Type

PU