PssIEEE2B
IEEE 421.5-2005 type PSS2B power system stabilizer model. This stabilizer model is designed to represent a variety of dual-input stabilizers, which normally use combinations of power and speed or frequency to derive the stabilizing signal. Reference: IEEE 2B 421.5-2005, 8.2.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Excitation system model with which this power system stabilizer model is associated. |
||
1 |
Dataset containing the data objects. |
||
0..1 |
Type of input signal #1 (rotorAngularFrequencyDeviation, busFrequencyDeviation). Typical value = rotorAngularFrequencyDeviation. |
||
0..1 |
Type of input signal #2 (generatorElectricalPower). Typical value = generatorElectricalPower. |
||
0..1 |
Stabilizer gain (Ks1). Typical value = 12. |
||
0..1 |
Gain on signal #2 (Ks2). Typical value = 0,2. |
||
0..1 |
Gain on signal #2 input before ramp-tracking filter (Ks3). Typical value = 1. |
||
0..1 |
Denominator order of ramp tracking filter (M). Typical value = 5. |
||
0..1 |
Order of ramp tracking filter (N). Typical value = 1. |
||
0..1 |
Lead/lag time constant (T1) (>= 0). Typical value = 0,12. |
||
0..1 |
Lead/lag time constant (T10) (>= 0). Typical value = 0. |
||
0..1 |
Lead/lag time constant (T11) (>= 0). Typical value = 0. |
||
0..1 |
Lead/lag time constant (T2) (>= 0). Typical value = 0,02. |
||
0..1 |
Lead/lag time constant (T3) (>= 0). Typical value = 0,3. |
||
0..1 |
Lead/lag time constant (T4) (>= 0). Typical value = 0,02. |
||
0..1 |
Time constant on signal #1 (T6) (>= 0). Typical value = 0. |
||
0..1 |
Time constant on signal #2 (T7) (>= 0). Typical value = 2. |
||
0..1 |
Lead of ramp tracking filter (T8) (>= 0). Typical value = 0,2. |
||
0..1 |
Lag of ramp tracking filter (T9) (>= 0). Typical value = 0,1. |
||
0..1 |
First washout on signal #1 (Tw1) (>= 0). Typical value = 2. |
||
0..1 |
Second washout on signal #1 (Tw2) (>= 0). Typical value = 2. |
||
0..1 |
First washout on signal #2 (Tw3) (>= 0). Typical value = 2. |
||
0..1 |
Second washout on signal #2 (Tw4) (>= 0). Typical value = 0. |
||
0..1 |
Input signal #1 maximum limit (Vsi1max) (> PssIEEE2B.vsi1min). Typical value = 2. |
||
0..1 |
Input signal #1 minimum limit (Vsi1min) (< PssIEEE2B.vsi1max). Typical value = -2. |
||
0..1 |
Input signal #2 maximum limit (Vsi2max) (> PssIEEE2B.vsi2min). Typical value = 2. |
||
0..1 |
Input signal #2 minimum limit (Vsi2min) (< PssIEEE2B.vsi2max). Typical value = -2. |
||
0..1 |
Stabilizer output maximum limit (Vstmax) (> PssIEEE2B.vstmin). Typical value = 0,1. |
||
0..1 |
Stabilizer output minimum limit (Vstmin) (< PssIEEE2B.vstmax). Typical value = -0,1. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Remote input signal used by this power system stabilizer model. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
ExcitationSystemDynamics
Excitation system model with which this power system stabilizer model is associated.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
inputSignal1Type
Type of input signal #1 (rotorAngularFrequencyDeviation, busFrequencyDeviation). Typical value = rotorAngularFrequencyDeviation.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
inputSignal2Type
Type of input signal #2 (generatorElectricalPower). Typical value = generatorElectricalPower.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
ks3
Gain on signal #2 input before ramp-tracking filter (Ks3). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
m
Denominator order of ramp tracking filter (M). Typical value = 5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
RemoteInputSignal
Remote input signal used by this power system stabilizer model.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
t1
Lead/lag time constant (T1) (>= 0). Typical value = 0,12.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t10
Lead/lag time constant (T10) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t11
Lead/lag time constant (T11) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t2
Lead/lag time constant (T2) (>= 0). Typical value = 0,02.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t3
Lead/lag time constant (T3) (>= 0). Typical value = 0,3.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t4
Lead/lag time constant (T4) (>= 0). Typical value = 0,02.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t6
Time constant on signal #1 (T6) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t7
Time constant on signal #2 (T7) (>= 0). Typical value = 2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t8
Lead of ramp tracking filter (T8) (>= 0). Typical value = 0,2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t9
Lag of ramp tracking filter (T9) (>= 0). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
tw1
First washout on signal #1 (Tw1) (>= 0). Typical value = 2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tw2
Second washout on signal #1 (Tw2) (>= 0). Typical value = 2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tw3
First washout on signal #2 (Tw3) (>= 0). Typical value = 2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tw4
Second washout on signal #2 (Tw4) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vsi1max
Input signal #1 maximum limit (Vsi1max) (> PssIEEE2B.vsi1min). Typical value = 2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vsi1min
Input signal #1 minimum limit (Vsi1min) (< PssIEEE2B.vsi1max). Typical value = -2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vsi2max
Input signal #2 maximum limit (Vsi2max) (> PssIEEE2B.vsi2min). Typical value = 2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vsi2min
Input signal #2 minimum limit (Vsi2min) (< PssIEEE2B.vsi2max). Typical value = -2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vstmax
Stabilizer output maximum limit (Vstmax) (> PssIEEE2B.vstmin). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |