TapChangerControl
Describes behaviour specific to tap changers, e.g. how the voltage at the end of a line varies with the load level and compensation of the voltage drop by tap adjustment.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1..* |
The tap changers that participates in this regulating tap control scheme. |
||
1 |
Dataset containing the data objects. |
||
0..1 |
Maximum allowed regulated voltage on the PT secondary, regardless of line drop compensation. Sometimes referred to as first-house protection. |
||
0..1 |
If true, the line drop compensation is to be applied. |
||
0..1 |
Line drop compensator resistance setting for normal (forward) power flow. |
||
0..1 |
Line drop compensator reactance setting for normal (forward) power flow. |
||
0..1 |
Line drop compensator resistance setting for reverse power flow. |
||
0..1 |
Line drop compensator reactance setting for reverse power flow. |
||
0..1 |
Datasheet information for this power system resource. |
||
0..1 |
Location of this power system resource. |
||
0..1 |
Custom classification for this power system resource. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
The terminal associated with this regulating control. The terminal is associated instead of a node, since the terminal could connect into either a topological node or a connectivity node. Sometimes it is useful to model regulation at a terminal of a bus bar object. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
The regulation is performed in a discrete mode. This applies to equipment with discrete controls, e.g. tap changers and shunt compensators. |
||
0..1 |
The flag tells if regulation is enabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
Maximum allowed target value (RegulatingControl.targetValue). |
||
0..1 |
Minimum allowed target value (RegulatingControl.targetValue). |
||
0..1 |
The regulating control mode presently available. This specification allows for determining the kind of regulation without need for obtaining the units from a schedule. |
||
0..1 |
Phase voltage controlling this regulator, measured at regulator location. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..1 |
This is a deadband used with discrete control to avoid excessive update of controls like tap changers and shunt compensator banks while regulating. The units of those appropriate for the mode. The attribute shall be a positive value or zero. If RegulatingControl.discrete is set to "false", the RegulatingControl.targetDeadband is to be ignored. Note that for instance, if the targetValue is 100 kV and the targetDeadband is 2 kV the range is from 99 to 101 kV. |
||
0..1 |
The target value specified for case input. This value can be used for the target value without the use of schedules. The value has the units appropriate to the mode attribute. |
||
0..1 |
Specify the multiplier for used for the targetValue. |
||
0..* |
All assets represented by this power system resource. For example, multiple conductor assets are electrically modelled as a single AC line segment. |
||
0..* |
All clearances applicable to this power system resource. |
||
0..* |
All configuration events created for this Power System resource. |
||
0..* |
The controller outputs used to actually govern a regulating device, e.g. the magnetization of a synchronous machine or capacitor bank breaker actuator. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
The generic action that is performed on the power system resource |
||
0..* |
The measurements associated with this power system resource. |
||
0..* |
All names of this identified object. |
||
0..* |
The operating shares of this power system resource. |
||
0..* |
All operational tags placed on this power system resource. |
||
0..* |
All events associated with this power system resource. |
||
0..* |
Enable/disable a regulating control or set new target value. |
||
0..* |
The equipment that participates in this regulating control scheme. |
||
0..* |
Schedule for this regulating control. |
||
0..* |
Reporting groups to which this power system resource belongs. |
||
0..* |
Data objects registered. |
||
0..* |
The verification action that is performed on the power system resource |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
AssetDatasheet
Datasheet information for this power system resource.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Assets
All assets represented by this power system resource. For example, multiple conductor assets are electrically modelled as a single AC line segment.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
Clearances
All clearances applicable to this power system resource.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
ConfigurationEvent
All configuration events created for this Power System resource.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
Controls
The controller outputs used to actually govern a regulating device, e.g. the magnetization of a synchronous machine or capacitor bank breaker actuator.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
discrete
The regulation is performed in a discrete mode. This applies to equipment with discrete controls, e.g. tap changers and shunt compensators.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
enabled
The flag tells if regulation is enabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
GenericAction
The generic action that is performed on the power system resource
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
limitVoltage
Maximum allowed regulated voltage on the PT secondary, regardless of line drop compensation. Sometimes referred to as first-house protection.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
lineDropCompensation
If true, the line drop compensation is to be applied.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
lineDropR
Line drop compensator resistance setting for normal (forward) power flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
lineDropX
Line drop compensator reactance setting for normal (forward) power flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
Location
Location of this power system resource.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
maxAllowedTargetValue
Maximum allowed target value (RegulatingControl.targetValue).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Measurements
The measurements associated with this power system resource.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
minAllowedTargetValue
Minimum allowed target value (RegulatingControl.targetValue).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
mode
The regulating control mode presently available. This specification allows for determining the kind of regulation without need for obtaining the units from a schedule.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
monitoredPhase
Phase voltage controlling this regulator, measured at regulator location.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
OperatingShare
The operating shares of this power system resource.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
OperationalTags
All operational tags placed on this power system resource.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
ProtectiveActionRegulation
Enable/disable a regulating control or set new target value.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
PSREvents
All events associated with this power system resource.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
PSRType
Custom classification for this power system resource.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
RegulatingCondEq
The equipment that participates in this regulating control scheme.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
RegulationSchedule
Schedule for this regulating control.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
ReportingGroup
Reporting groups to which this power system resource belongs.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
reverseLineDropR
Line drop compensator resistance setting for reverse power flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
reverseLineDropX
Line drop compensator reactance setting for reverse power flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TapChanger
The tap changers that participates in this regulating tap control scheme.
URI |
|
---|---|
Cardinality |
1..* |
Type |
targetDeadband
This is a deadband used with discrete control to avoid excessive update of controls like tap changers and shunt compensator banks while regulating. The units of those appropriate for the mode. The attribute shall be a positive value or zero. If RegulatingControl.discrete is set to "false", the RegulatingControl.targetDeadband is to be ignored. Note that for instance, if the targetValue is 100 kV and the targetDeadband is 2 kV the range is from 99 to 101 kV.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
targetValue
The target value specified for case input. This value can be used for the target value without the use of schedules. The value has the units appropriate to the mode attribute.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
targetValueUnitMultiplier
Specify the multiplier for used for the targetValue.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Terminal
The terminal associated with this regulating control. The terminal is associated instead of a node, since the terminal could connect into either a topological node or a connectivity node. Sometimes it is useful to model regulation at a terminal of a bus bar object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |