TransformerEnd

A conducting connection point of a power transformer. It corresponds to a physical transformer winding terminal. In earlier CIM versions, the TransformerWinding class served a similar purpose, but this class is more flexible because it associates to terminal but is not a specialization of ConductingEquipment.

Type

Class

URI

cim:TransformerEnd

CIM standard (perspective)

IEC61970 (Grid)

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

InstanceSet

1

InstanceSet

Dataset containing the data objects.

BaseVoltage

0..1

BaseVoltage

Base voltage of the transformer end. This is essential for PU calculation.

CoreAdmittance

0..1

TransformerCoreAdmittance

Core admittance of this transformer end, representing magnetising current and core losses. The full values of the transformer should be supplied for one transformer end only.

PhaseTapChanger

0..1

PhaseTapChanger

Phase tap changer associated with this transformer end.

RatioTapChanger

0..1

RatioTapChanger

Ratio tap changer associated with this transformer end.

StarImpedance

0..1

TransformerStarImpedance

(accurate for 2- or 3-winding transformers only) Pi-model impedances of this transformer end. By convention, for a two winding transformer, the full values of the transformer should be entered on the high voltage end (endNumber=1).

Terminal

0..1

Terminal

Terminal of the power transformer to which this transformer end belongs.

bmagSat

0..1

PerCent

Core shunt magnetizing susceptance in the saturation region.

endNumber

0..1

integer

Number for this transformer end, corresponding to the end's order in the power transformer vector group or phase angle clock number. Highest voltage winding should be 1. Each end within a power transformer should have a unique subsequent end number. Note the transformer end number need not match the terminal sequence number.

grounded

0..1

boolean

(for Yn and Zn connections) True if the neutral is solidly grounded.

magBaseU

0..1

Voltage

The reference voltage at which the magnetizing saturation measurements were made.

magSatFlux

0..1

PerCent

Core magnetizing saturation curve knee flux level.

rground

0..1

Resistance

(for Yn and Zn connections) Resistance part of neutral impedance where 'grounded' is true.

xground

0..1

Reactance

(for Yn and Zn connections) Reactive part of neutral impedance where 'grounded' is true.

FromMeshImpedance

0..*

TransformerMeshImpedance

All mesh impedances between this 'to' and other 'from' transformer ends.

FromWindingInsulations

0..*

WindingInsulation

n/a

ToMeshImpedance

0..*

TransformerMeshImpedance

All mesh impedances between this 'from' and other 'to' transformer ends.

ToWindingInsulations

0..*

WindingInsulation

n/a

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

BaseVoltage

Base voltage of the transformer end. This is essential for PU calculation.

URI

cim:TransformerEnd.BaseVoltage

Cardinality

0..1

Type

BaseVoltage

bmagSat

Core shunt magnetizing susceptance in the saturation region.

URI

cim:TransformerEnd.bmagSat

Cardinality

0..1

Type

PerCent

CoreAdmittance

Core admittance of this transformer end, representing magnetising current and core losses. The full values of the transformer should be supplied for one transformer end only.

URI

cim:TransformerEnd.CoreAdmittance

Cardinality

0..1

Type

TransformerCoreAdmittance

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

endNumber

Number for this transformer end, corresponding to the end's order in the power transformer vector group or phase angle clock number. Highest voltage winding should be 1. Each end within a power transformer should have a unique subsequent end number. Note the transformer end number need not match the terminal sequence number.

URI

cim:TransformerEnd.endNumber

Cardinality

0..1

Type

integer

FromMeshImpedance

All mesh impedances between this 'to' and other 'from' transformer ends.

URI

cim:TransformerEnd.FromMeshImpedance

Cardinality

0..*

Type

TransformerMeshImpedance

FromWindingInsulations

URI

cim:TransformerEnd.FromWindingInsulations

Cardinality

0..*

Type

WindingInsulation

grounded

(for Yn and Zn connections) True if the neutral is solidly grounded.

URI

cim:TransformerEnd.grounded

Cardinality

0..1

Type

boolean

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

magBaseU

The reference voltage at which the magnetizing saturation measurements were made.

URI

cim:TransformerEnd.magBaseU

Cardinality

0..1

Type

Voltage

magSatFlux

Core magnetizing saturation curve knee flux level.

URI

cim:TransformerEnd.magSatFlux

Cardinality

0..1

Type

PerCent

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

PhaseTapChanger

Phase tap changer associated with this transformer end.

URI

cim:TransformerEnd.PhaseTapChanger

Cardinality

0..1

Type

PhaseTapChanger

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

RatioTapChanger

Ratio tap changer associated with this transformer end.

URI

cim:TransformerEnd.RatioTapChanger

Cardinality

0..1

Type

RatioTapChanger

rground

(for Yn and Zn connections) Resistance part of neutral impedance where 'grounded' is true.

URI

cim:TransformerEnd.rground

Cardinality

0..1

Type

Resistance

StarImpedance

(accurate for 2- or 3-winding transformers only) Pi-model impedances of this transformer end. By convention, for a two winding transformer, the full values of the transformer should be entered on the high voltage end (endNumber=1).

URI

cim:TransformerEnd.StarImpedance

Cardinality

0..1

Type

TransformerStarImpedance

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

Terminal

Terminal of the power transformer to which this transformer end belongs.

URI

cim:TransformerEnd.Terminal

Cardinality

0..1

Type

Terminal

ToMeshImpedance

All mesh impedances between this 'from' and other 'to' transformer ends.

URI

cim:TransformerEnd.ToMeshImpedance

Cardinality

0..*

Type

TransformerMeshImpedance

ToWindingInsulations

URI

cim:TransformerEnd.ToWindingInsulations

Cardinality

0..*

Type

WindingInsulation

xground

(for Yn and Zn connections) Reactive part of neutral impedance where 'grounded' is true.

URI

cim:TransformerEnd.xground

Cardinality

0..1

Type

Reactance