PssPTIST3

PTI microprocessor-based stabilizer type 3.

Type

Class

URI

cim:PssPTIST3

CIM standard (perspective)

IEC61970 (Grid)

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

ExcitationSystemDynamics

1

ExcitationSystemDynamics

Excitation system model with which this power system stabilizer model is associated.

InstanceSet

1

InstanceSet

Dataset containing the data objects.

a0

0..1

PU

Filter coefficient (A0).

a1

0..1

PU

Limiter (Al).

a2

0..1

PU

Filter coefficient (A2).

a3

0..1

PU

Filter coefficient (A3).

a4

0..1

PU

Filter coefficient (A4).

a5

0..1

PU

Filter coefficient (A5).

al

0..1

PU

Limiter (Al).

athres

0..1

PU

Threshold value above which output averaging will be bypassed (Athres). Typical value = 0,005.

b0

0..1

PU

Filter coefficient (B0).

b1

0..1

PU

Filter coefficient (B1).

b2

0..1

PU

Filter coefficient (B2).

b3

0..1

PU

Filter coefficient (B3).

b4

0..1

PU

Filter coefficient (B4).

b5

0..1

PU

Filter coefficient (B5).

dl

0..1

PU

Limiter (Dl).

dtc

0..1

Seconds

Time step related to activation of controls (deltatc) (>= 0). Typical value = 0,025 (0,03 for 50 Hz).

dtf

0..1

Seconds

Time step frequency calculation (deltatf) (>= 0). Typical value = 0,025 (0,03 for 50 Hz).

dtp

0..1

Seconds

Time step active power calculation (deltatp) (>= 0). Typical value = 0,0125 (0,015 for 50 Hz).

isw

0..1

boolean

Digital/analogue output switch (Isw). true = produce analogue output false = convert to digital output, using tap selection table.

k

0..1

PU

Gain (K). Typical value = 9.

lthres

0..1

PU

Threshold value (Lthres).

m

0..1

PU

(M). M = 2 x H. Typical value = 5.

nav

0..1

float

Number of control outputs to average (NAV) (1 <= NAV <= 16). Typical value = 4.

ncl

0..1

float

Number of counts at limit to active limit function (NCL) (> 0).

ncr

0..1

float

Number of counts until reset after limit function is triggered (NCR).

pmin

0..1

PU

(Pmin).

t1

0..1

Seconds

Time constant (T1) (>= 0). Typical value = 0,3.

t2

0..1

Seconds

Time constant (T2) (>= 0). Typical value = 1.

t3

0..1

Seconds

Time constant (T3) (>= 0). Typical value = 0,2.

t4

0..1

Seconds

Time constant (T4) (>= 0). Typical value = 0,05.

t5

0..1

Seconds

Time constant (T5) (>= 0).

t6

0..1

Seconds

Time constant (T6) (>= 0).

tf

0..1

Seconds

Time constant (Tf) (>= 0). Typical value = 0,2.

tp

0..1

Seconds

Time constant (Tp) (>= 0). Typical value = 0,2.

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

enabled

0..1

boolean

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

RemoteInputSignal

0..*

RemoteInputSignal

Remote input signal used by this power system stabilizer model.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


a0

Filter coefficient (A0).

URI

cim:PssPTIST3.a0

Cardinality

0..1

Type

PU

a1

Limiter (Al).

URI

cim:PssPTIST3.a1

Cardinality

0..1

Type

PU

a2

Filter coefficient (A2).

URI

cim:PssPTIST3.a2

Cardinality

0..1

Type

PU

a3

Filter coefficient (A3).

URI

cim:PssPTIST3.a3

Cardinality

0..1

Type

PU

a4

Filter coefficient (A4).

URI

cim:PssPTIST3.a4

Cardinality

0..1

Type

PU

a5

Filter coefficient (A5).

URI

cim:PssPTIST3.a5

Cardinality

0..1

Type

PU

al

Limiter (Al).

URI

cim:PssPTIST3.al

Cardinality

0..1

Type

PU

aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

athres

Threshold value above which output averaging will be bypassed (Athres). Typical value = 0,005.

URI

cim:PssPTIST3.athres

Cardinality

0..1

Type

PU

b0

Filter coefficient (B0).

URI

cim:PssPTIST3.b0

Cardinality

0..1

Type

PU

b1

Filter coefficient (B1).

URI

cim:PssPTIST3.b1

Cardinality

0..1

Type

PU

b2

Filter coefficient (B2).

URI

cim:PssPTIST3.b2

Cardinality

0..1

Type

PU

b3

Filter coefficient (B3).

URI

cim:PssPTIST3.b3

Cardinality

0..1

Type

PU

b4

Filter coefficient (B4).

URI

cim:PssPTIST3.b4

Cardinality

0..1

Type

PU

b5

Filter coefficient (B5).

URI

cim:PssPTIST3.b5

Cardinality

0..1

Type

PU

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

dl

Limiter (Dl).

URI

cim:PssPTIST3.dl

Cardinality

0..1

Type

PU

dtc

Time step related to activation of controls (deltatc) (>= 0). Typical value = 0,025 (0,03 for 50 Hz).

URI

cim:PssPTIST3.dtc

Cardinality

0..1

Type

Seconds

dtf

Time step frequency calculation (deltatf) (>= 0). Typical value = 0,025 (0,03 for 50 Hz).

URI

cim:PssPTIST3.dtf

Cardinality

0..1

Type

Seconds

dtp

Time step active power calculation (deltatp) (>= 0). Typical value = 0,0125 (0,015 for 50 Hz).

URI

cim:PssPTIST3.dtp

Cardinality

0..1

Type

Seconds

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

URI

cim:DynamicsFunctionBlock.enabled

Cardinality

0..1

Type

boolean

Inherited from

DynamicsFunctionBlock

ExcitationSystemDynamics

Excitation system model with which this power system stabilizer model is associated.

URI

cim:PowerSystemStabilizerDynamics.ExcitationSystemDynamics

Cardinality

1

Type

ExcitationSystemDynamics

Inherited from

PowerSystemStabilizerDynamics

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

isw

Digital/analogue output switch (Isw). true = produce analogue output false = convert to digital output, using tap selection table.

URI

cim:PssPTIST3.isw

Cardinality

0..1

Type

boolean

k

Gain (K). Typical value = 9.

URI

cim:PssPTIST3.k

Cardinality

0..1

Type

PU

lthres

Threshold value (Lthres).

URI

cim:PssPTIST3.lthres

Cardinality

0..1

Type

PU

m

(M). M = 2 x H. Typical value = 5.

URI

cim:PssPTIST3.m

Cardinality

0..1

Type

PU

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

Number of control outputs to average (NAV) (1 <= NAV <= 16). Typical value = 4.

URI

cim:PssPTIST3.nav

Cardinality

0..1

Type

float

ncl

Number of counts at limit to active limit function (NCL) (> 0).

URI

cim:PssPTIST3.ncl

Cardinality

0..1

Type

float

ncr

Number of counts until reset after limit function is triggered (NCR).

URI

cim:PssPTIST3.ncr

Cardinality

0..1

Type

float

pmin

(Pmin).

URI

cim:PssPTIST3.pmin

Cardinality

0..1

Type

PU

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

RemoteInputSignal

Remote input signal used by this power system stabilizer model.

URI

cim:PowerSystemStabilizerDynamics.RemoteInputSignal

Cardinality

0..*

Type

RemoteInputSignal

Inherited from

PowerSystemStabilizerDynamics

t1

Time constant (T1) (>= 0). Typical value = 0,3.

URI

cim:PssPTIST3.t1

Cardinality

0..1

Type

Seconds

t2

Time constant (T2) (>= 0). Typical value = 1.

URI

cim:PssPTIST3.t2

Cardinality

0..1

Type

Seconds

t3

Time constant (T3) (>= 0). Typical value = 0,2.

URI

cim:PssPTIST3.t3

Cardinality

0..1

Type

Seconds

t4

Time constant (T4) (>= 0). Typical value = 0,05.

URI

cim:PssPTIST3.t4

Cardinality

0..1

Type

Seconds

t5

Time constant (T5) (>= 0).

URI

cim:PssPTIST3.t5

Cardinality

0..1

Type

Seconds

t6

Time constant (T6) (>= 0).

URI

cim:PssPTIST3.t6

Cardinality

0..1

Type

Seconds

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

tf

Time constant (Tf) (>= 0). Typical value = 0,2.

URI

cim:PssPTIST3.tf

Cardinality

0..1

Type

Seconds

tp

Time constant (Tp) (>= 0). Typical value = 0,2.

URI

cim:PssPTIST3.tp

Cardinality

0..1

Type

Seconds