LinearShuntCompensatorPhase

A per phase linear shunt compensator has banks or sections with equal admittance values.

Type

Class

URI

cim:LinearShuntCompensatorPhase

CIM standard (perspective)

IEC61970 (Grid)

Class hierarchy

Slots

Name Type Description Inherited from

bPerSection

0..1
Susceptance

Susceptance per section of the phase if shunt compensator is wye connected. Susceptance per section phase to phase if...

n/a

gPerSection

0..1
Conductance

Conductance per section for this phase if shunt compensator is wye connected. Conductance per section phase to phase if...

n/a

ShuntCompensator

1
ShuntCompensator

Shunt compensator of this shunt compensator phase.

ShuntCompensatorPhase

maximumSections

0..1
integer

The maximum number of sections that may be switched in for this phase.

ShuntCompensatorPhase

normalSections

0..1
integer

For the capacitor phase, the normal number of sections switched in. The value shall be between zero and...

ShuntCompensatorPhase

phase

0..1
SinglePhaseKind

Phase of this shunt compensator component. If the shunt compensator is wye connected, the connection is from the indicated...

ShuntCompensatorPhase

sections

0..1
float

Shunt compensator sections in use. Starting value for steady state solution. The attribute shall be a positive value or...

ShuntCompensatorPhase

AssetDatasheet

0..1
AssetInfo

Datasheet information for this power system resource.

PowerSystemResource

Assets

0..*
Asset

All assets represented by this power system resource. For example, multiple conductor assets are electrically modelled as a...

PowerSystemResource

Clearances

0..*
ClearanceDocument

All clearances applicable to this power system resource.

PowerSystemResource

ConfigurationEvent

0..*
ConfigurationEvent

All configuration events created for this Power System resource.

PowerSystemResource

Controls

0..*
Control

The controller outputs used to actually govern a regulating device, e.g. the magnetization of a synchronous machine or...

PowerSystemResource

GenericAction

0..*
GenericAction

The generic action that is performed on the power system resource

PowerSystemResource

Location

0..1
Location

Location of this power system resource.

PowerSystemResource

Measurements

0..*
Measurement

The measurements associated with this power system resource.

PowerSystemResource

OperatingShare

0..*
OperatingShare

The operating shares of this power system resource.

PowerSystemResource

OperationalTags

0..*
OperationalTag

All operational tags placed on this power system resource.

PowerSystemResource

PSREvents

0..*
PSREvent

All events associated with this power system resource.

PowerSystemResource

PSRType

0..1
PSRType

Custom classification for this power system resource.

PowerSystemResource

ReportingGroup

0..*
ReportingGroup

Reporting groups to which this power system resource belongs.

PowerSystemResource

VerificationAction

0..*
VerificationAction

The verification action that is performed on the power system resource

PowerSystemResource

DiagramObjects

0..*
DiagramObject

The diagram objects that are associated with the domain object.

IdentifiedObject

InstanceSet

1
InstanceSet

Dataset containing the data objects.

IdentifiedObject

Names

0..*
Name

All names of this identified object.

IdentifiedObject

PropertiesCIMDataObject

0..1
ChangeSetMember

The single CIM data object in the appropriate dataset context.

IdentifiedObject

TargetingCIMDataObject

0..*
ChangeSetMember

Data objects registered.

IdentifiedObject

aliasName

0..1
string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and...

IdentifiedObject

description

0..1
string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to...

IdentifiedObject

mRID

0..1
string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is...

IdentifiedObject

name

0..1
string

The name is any free human readable and possibly non unique text naming the object.

IdentifiedObject


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

AssetDatasheet

Datasheet information for this power system resource.

URI

cim:PowerSystemResource.AssetDatasheet

Cardinality

0..1

Type

AssetInfo

Inherited from

PowerSystemResource

Assets

All assets represented by this power system resource. For example, multiple conductor assets are electrically modelled as a single AC line segment.

URI

cim:PowerSystemResource.Assets

Cardinality

0..*

Type

Asset

Inherited from

PowerSystemResource

bPerSection

Susceptance per section of the phase if shunt compensator is wye connected. Susceptance per section phase to phase if shunt compensator is delta connected.

URI

cim:LinearShuntCompensatorPhase.bPerSection

Cardinality

0..1

Type

Susceptance

Clearances

All clearances applicable to this power system resource.

URI

cim:PowerSystemResource.Clearances

Cardinality

0..*

Type

ClearanceDocument

Inherited from

PowerSystemResource

ConfigurationEvent

All configuration events created for this Power System resource.

URI

cim:PowerSystemResource.ConfigurationEvent

Cardinality

0..*

Type

ConfigurationEvent

Inherited from

PowerSystemResource

Controls

The controller outputs used to actually govern a regulating device, e.g. the magnetization of a synchronous machine or capacitor bank breaker actuator.

URI

cim:PowerSystemResource.Controls

Cardinality

0..*

Type

Control

Inherited from

PowerSystemResource

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

GenericAction

The generic action that is performed on the power system resource

URI

cim:PowerSystemResource.GenericAction

Cardinality

0..*

Type

GenericAction

Inherited from

PowerSystemResource

gPerSection

Conductance per section for this phase if shunt compensator is wye connected. Conductance per section phase to phase if shunt compensator is delta connected.

URI

cim:LinearShuntCompensatorPhase.gPerSection

Cardinality

0..1

Type

Conductance

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

Location

Location of this power system resource.

URI

cim:PowerSystemResource.Location

Cardinality

0..1

Type

Location

Inherited from

PowerSystemResource

maximumSections

The maximum number of sections that may be switched in for this phase.

URI

cim:ShuntCompensatorPhase.maximumSections

Cardinality

0..1

Type

integer

Inherited from

ShuntCompensatorPhase

Measurements

The measurements associated with this power system resource.

URI

cim:PowerSystemResource.Measurements

Cardinality

0..*

Type

Measurement

Inherited from

PowerSystemResource

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

normalSections

For the capacitor phase, the normal number of sections switched in. The value shall be between zero and ShuntCompensatorPhase.maximumSections.

URI

cim:ShuntCompensatorPhase.normalSections

Cardinality

0..1

Type

integer

Inherited from

ShuntCompensatorPhase

OperatingShare

The operating shares of this power system resource.

URI

cim:PowerSystemResource.OperatingShare

Cardinality

0..*

Type

OperatingShare

Inherited from

PowerSystemResource

OperationalTags

All operational tags placed on this power system resource.

URI

cim:PowerSystemResource.OperationalTags

Cardinality

0..*

Type

OperationalTag

Inherited from

PowerSystemResource

phase

Phase of this shunt compensator component. If the shunt compensator is wye connected, the connection is from the indicated phase to the central ground or neutral point. If the shunt compensator is delta connected, the phase indicates a shunt compensator connected from the indicated phase to the next logical non-neutral phase.

URI

cim:ShuntCompensatorPhase.phase

Cardinality

0..1

Type

SinglePhaseKind

Inherited from

ShuntCompensatorPhase

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

PSREvents

All events associated with this power system resource.

URI

cim:PowerSystemResource.PSREvents

Cardinality

0..*

Type

PSREvent

Inherited from

PowerSystemResource

PSRType

Custom classification for this power system resource.

URI

cim:PowerSystemResource.PSRType

Cardinality

0..1

Type

PSRType

Inherited from

PowerSystemResource

ReportingGroup

Reporting groups to which this power system resource belongs.

URI

cim:PowerSystemResource.ReportingGroup

Cardinality

0..*

Type

ReportingGroup

Inherited from

PowerSystemResource

sections

Shunt compensator sections in use. Starting value for steady state solution. The attribute shall be a positive value or zero. Non integer values are allowed to support continuous variables. The reasons for continuous value are to support study cases where no discrete shunt compensators has yet been designed, a solutions where a narrow voltage band force the sections to oscillate or accommodate for a continuous solution as input. For LinearShuntConpensator the value shall be between zero and ShuntCompensatorPhase.maximumSections. At value zero the shunt compensator conductance and admittance is zero. Linear interpolation of conductance and admittance between the previous and next integer section is applied in case of non-integer values. For NonlinearShuntCompensator-s shall only be set to one of the NonlinearShuntCompenstorPhasePoint.sectionNumber. There is no interpolation between NonlinearShuntCompenstorPhasePoint-s.

URI

cim:ShuntCompensatorPhase.sections

Cardinality

0..1

Type

float

Inherited from

ShuntCompensatorPhase

ShuntCompensator

Shunt compensator of this shunt compensator phase.

URI

cim:ShuntCompensatorPhase.ShuntCompensator

Cardinality

1

Type

ShuntCompensator

Inherited from

ShuntCompensatorPhase

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

VerificationAction

The verification action that is performed on the power system resource

URI

cim:PowerSystemResource.VerificationAction

Cardinality

0..*

Type

VerificationAction

Inherited from

PowerSystemResource

Used by

This class is not used by any other classes as the range of a slot.