GovSteamFV3
Simplified GovSteamIEEE1 steam turbine governor with Prmax limit and fast valving.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Dataset containing the data objects. |
||
0..1 |
Nonlinear gain valve position point 1 (GV1). Typical value = 0. |
||
0..1 |
Nonlinear gain valve position point 2 (GV2). Typical value = 0,4. |
||
0..1 |
Nonlinear gain valve position point 3 (GV3). Typical value = 0,5. |
||
0..1 |
Nonlinear gain valve position point 4 (GV4). Typical value = 0,6. |
||
0..1 |
Nonlinear gain valve position point 5 (GV5). Typical value = 1. |
||
0..1 |
Nonlinear gain valve position point 6 (GV6). Typical value = 0. |
||
0..1 |
Governor gain, (reciprocal of droop) (K). Typical value = 20. |
||
0..1 |
Fraction of turbine power developed after first boiler pass (K1). Typical value = 0,2. |
||
0..1 |
Fraction of turbine power developed after second boiler pass (K2). Typical value = 0,2. |
||
0..1 |
Fraction of hp turbine power developed after crossover or third boiler pass (K3). Typical value = 0,6. |
||
0..1 |
Base for power values (MWbase) (> 0). Unit = MW. |
||
0..1 |
Nonlinear gain power value point 1 (Pgv1). Typical value = 0. |
||
0..1 |
Nonlinear gain power value point 2 (Pgv2). Typical value = 0,75. |
||
0..1 |
Nonlinear gain power value point 3 (Pgv3). Typical value = 0,91. |
||
0..1 |
Nonlinear gain power value point 4 (Pgv4). Typical value = 0,98. |
||
0..1 |
Nonlinear gain power value point 5 (Pgv5). Typical value = 1. |
||
0..1 |
Nonlinear gain power value point 6 (Pgv6). Typical value = 0. |
||
0..1 |
Maximum valve opening, PU of MWbase (Pmax) (> GovSteamFV3.pmin). Typical value = 1. |
||
0..1 |
Minimum valve opening, PU of MWbase (Pmin) (< GovSteamFV3.pmax). Typical value = 0. |
||
0..1 |
Max. pressure in reheater (Prmax). Typical value = 1. |
||
0..1 |
Governor lead time constant (T1) (>= 0). Typical value = 0. |
||
0..1 |
Governor lag time constant (T2) (>= 0). Typical value = 0. |
||
0..1 |
Valve positioner time constant (T3) (> 0). Typical value = 0. |
||
0..1 |
Inlet piping/steam bowl time constant (T4) (>= 0). Typical value = 0,2. |
||
0..1 |
Time constant of second boiler pass (i.e. reheater) (T5) (> 0 if fast valving is used, otherwise >= 0). Typical value = 0,5. |
||
0..1 |
Time constant of crossover or third boiler pass (T6) (>= 0). Typical value = 10. |
||
0..1 |
Time to close intercept valve (IV) (Ta) (>= 0). Typical value = 0,97. |
||
0..1 |
Time until IV starts to reopen (Tb) (>= 0). Typical value = 0,98. |
||
0..1 |
Time until IV is fully open (Tc) (>= 0). Typical value = 0,99. |
||
0..1 |
Maximum valve closing velocity (Uc). Unit = PU / s. Typical value = -1. |
||
0..1 |
Maximum valve opening velocity (Uo). Unit = PU / s. Typical value = 0,1. |
||
0..1 |
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
Turbine load controller providing input to this turbine-governor. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
gv1
Nonlinear gain valve position point 1 (GV1). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv2
Nonlinear gain valve position point 2 (GV2). Typical value = 0,4.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv3
Nonlinear gain valve position point 3 (GV3). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv4
Nonlinear gain valve position point 4 (GV4). Typical value = 0,6.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv5
Nonlinear gain valve position point 5 (GV5). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv6
Nonlinear gain valve position point 6 (GV6). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
k
Governor gain, (reciprocal of droop) (K). Typical value = 20.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
k1
Fraction of turbine power developed after first boiler pass (K1). Typical value = 0,2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
k2
Fraction of turbine power developed after second boiler pass (K2). Typical value = 0,2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
k3
Fraction of hp turbine power developed after crossover or third boiler pass (K3). Typical value = 0,6.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
mwbase
Base for power values (MWbase) (> 0). Unit = MW.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
pgv1
Nonlinear gain power value point 1 (Pgv1). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv2
Nonlinear gain power value point 2 (Pgv2). Typical value = 0,75.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv3
Nonlinear gain power value point 3 (Pgv3). Typical value = 0,91.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv4
Nonlinear gain power value point 4 (Pgv4). Typical value = 0,98.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv5
Nonlinear gain power value point 5 (Pgv5). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv6
Nonlinear gain power value point 6 (Pgv6). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmax
Maximum valve opening, PU of MWbase (Pmax) (> GovSteamFV3.pmin). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmin
Minimum valve opening, PU of MWbase (Pmin) (< GovSteamFV3.pmax). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
prmax
Max. pressure in reheater (Prmax). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
SynchronousMachineDynamics
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
t1
Governor lead time constant (T1) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t2
Governor lag time constant (T2) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t3
Valve positioner time constant (T3) (> 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t4
Inlet piping/steam bowl time constant (T4) (>= 0). Typical value = 0,2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t5
Time constant of second boiler pass (i.e. reheater) (T5) (> 0 if fast valving is used, otherwise >= 0). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t6
Time constant of crossover or third boiler pass (T6) (>= 0). Typical value = 10.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
ta
Time to close intercept valve (IV) (Ta) (>= 0). Typical value = 0,97.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
tb
Time until IV starts to reopen (Tb) (>= 0). Typical value = 0,98.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tc
Time until IV is fully open (Tc) (>= 0). Typical value = 0,99.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TurbineLoadControllerDynamics
Turbine load controller providing input to this turbine-governor.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
uc
Maximum valve closing velocity (Uc). Unit = PU / s. Typical value = -1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |