WindContPType3IEC

P control model type 3. Reference: IEC 61400-27-1:2015, 5.6.5.4.

Type

Class

URI

cim:WindContPType3IEC

CIM standard (perspective)

IEC61970 (Grid)

Class hierarchy

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

WindTurbineType3IEC

1

WindTurbineType3IEC

Wind turbine type 3 model with which this wind control P type 3 model is associated.

WindDynamicsLookupTable

1..*

WindDynamicsLookupTable

The wind dynamics lookup table associated with this P control type 3 model.

InstanceSet

1

InstanceSet

Dataset containing the data objects.

dpmax

0..1

PU

Maximum wind turbine power ramp rate (dpmax). It is a type-dependent parameter.

dprefmax

0..1

PU

Maximum ramp rate of wind turbine reference power (dprefmax). It is a project-dependent parameter.

dprefmin

0..1

PU

Minimum ramp rate of wind turbine reference power (dprefmin). It is a project-dependent parameter.

dthetamax

0..1

PU

Ramp limitation of torque, required in some grid codes (dtmax). It is a project-dependent parameter.

dthetamaxuvrt

0..1

PU

Limitation of torque rise rate during UVRT (dthetamaxUVRT). It is a project-dependent parameter.

kdtd

0..1

PU

Gain for active drive train damping (KDTD). It is a type-dependent parameter.

kip

0..1

PU

PI controller integration parameter (KIp). It is a type-dependent parameter.

kpp

0..1

PU

PI controller proportional gain (KPp). It is a type-dependent parameter.

mpuvrt

0..1

boolean

Enable UVRT power control mode (MpUVRT). It is a project-dependent parameter. true = voltage control (1 in the IEC model) false = reactive power control (0 in the IEC model).

omegadtd

0..1

PU

Active drive train damping frequency (omegaDTD). It can be calculated from two mass model parameters. It is a type-dependent parameter.

omegaoffset

0..1

PU

Offset to reference value that limits controller action during rotor speed changes (omegaoffset). It is a case-dependent parameter.

pdtdmax

0..1

PU

Maximum active drive train damping power (pDTDmax). It is a type-dependent parameter.

tdvs

0..1

Seconds

Time delay after deep voltage sags (TDVS) (>= 0). It is a project-dependent parameter.

thetaemin

0..1

PU

Minimum electrical generator torque (temin). It is a type-dependent parameter.

thetauscale

0..1

PU

Voltage scaling factor of reset-torque (tuscale). It is a project-dependent parameter.

tomegafiltp3

0..1

Seconds

Filter time constant for generator speed measurement (Tomegafiltp3) (>= 0). It is a type-dependent parameter.

tomegaref

0..1

Seconds

Time constant in speed reference filter (Tomega,ref) (>= 0). It is a type-dependent parameter.

tpfiltp3

0..1

Seconds

Filter time constant for power measurement (Tpfiltp3) (>= 0). It is a type-dependent parameter.

tpord

0..1

PU

Time constant in power order lag (Tpord). It is a type-dependent parameter.

tufiltp3

0..1

Seconds

Filter time constant for voltage measurement (Tufiltp3) (>= 0). It is a type-dependent parameter.

udvs

0..1

PU

Voltage limit for hold UVRT status after deep voltage sags (uDVS). It is a project-dependent parameter.

updip

0..1

PU

Voltage dip threshold for P-control (uPdip). Part of turbine control, often different (e.g 0.8) from converter thresholds. It is a project-dependent parameter.

zeta

0..1

float

Coefficient for active drive train damping (zeta). It is a type-dependent parameter.

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

dpmax

Maximum wind turbine power ramp rate (dpmax). It is a type-dependent parameter.

URI

cim:WindContPType3IEC.dpmax

Cardinality

0..1

Type

PU

dprefmax

Maximum ramp rate of wind turbine reference power (dprefmax). It is a project-dependent parameter.

URI

cim:WindContPType3IEC.dprefmax

Cardinality

0..1

Type

PU

dprefmin

Minimum ramp rate of wind turbine reference power (dprefmin). It is a project-dependent parameter.

URI

cim:WindContPType3IEC.dprefmin

Cardinality

0..1

Type

PU

dthetamax

Ramp limitation of torque, required in some grid codes (dtmax). It is a project-dependent parameter.

URI

cim:WindContPType3IEC.dthetamax

Cardinality

0..1

Type

PU

dthetamaxuvrt

Limitation of torque rise rate during UVRT (dthetamaxUVRT). It is a project-dependent parameter.

URI

cim:WindContPType3IEC.dthetamaxuvrt

Cardinality

0..1

Type

PU

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

kdtd

Gain for active drive train damping (KDTD). It is a type-dependent parameter.

URI

cim:WindContPType3IEC.kdtd

Cardinality

0..1

Type

PU

kip

PI controller integration parameter (KIp). It is a type-dependent parameter.

URI

cim:WindContPType3IEC.kip

Cardinality

0..1

Type

PU

kpp

PI controller proportional gain (KPp). It is a type-dependent parameter.

URI

cim:WindContPType3IEC.kpp

Cardinality

0..1

Type

PU

mpuvrt

Enable UVRT power control mode (MpUVRT). It is a project-dependent parameter. true = voltage control (1 in the IEC model) false = reactive power control (0 in the IEC model).

URI

cim:WindContPType3IEC.mpuvrt

Cardinality

0..1

Type

boolean

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

omegadtd

Active drive train damping frequency (omegaDTD). It can be calculated from two mass model parameters. It is a type-dependent parameter.

URI

cim:WindContPType3IEC.omegadtd

Cardinality

0..1

Type

PU

omegaoffset

Offset to reference value that limits controller action during rotor speed changes (omegaoffset). It is a case-dependent parameter.

URI

cim:WindContPType3IEC.omegaoffset

Cardinality

0..1

Type

PU

pdtdmax

Maximum active drive train damping power (pDTDmax). It is a type-dependent parameter.

URI

cim:WindContPType3IEC.pdtdmax

Cardinality

0..1

Type

PU

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

tdvs

Time delay after deep voltage sags (TDVS) (>= 0). It is a project-dependent parameter.

URI

cim:WindContPType3IEC.tdvs

Cardinality

0..1

Type

Seconds

thetaemin

Minimum electrical generator torque (temin). It is a type-dependent parameter.

URI

cim:WindContPType3IEC.thetaemin

Cardinality

0..1

Type

PU

thetauscale

Voltage scaling factor of reset-torque (tuscale). It is a project-dependent parameter.

URI

cim:WindContPType3IEC.thetauscale

Cardinality

0..1

Type

PU

tomegafiltp3

Filter time constant for generator speed measurement (Tomegafiltp3) (>= 0). It is a type-dependent parameter.

URI

cim:WindContPType3IEC.tomegafiltp3

Cardinality

0..1

Type

Seconds

tomegaref

Time constant in speed reference filter (Tomega,ref) (>= 0). It is a type-dependent parameter.

URI

cim:WindContPType3IEC.tomegaref

Cardinality

0..1

Type

Seconds

tpfiltp3

Filter time constant for power measurement (Tpfiltp3) (>= 0). It is a type-dependent parameter.

URI

cim:WindContPType3IEC.tpfiltp3

Cardinality

0..1

Type

Seconds

tpord

Time constant in power order lag (Tpord). It is a type-dependent parameter.

URI

cim:WindContPType3IEC.tpord

Cardinality

0..1

Type

PU

tufiltp3

Filter time constant for voltage measurement (Tufiltp3) (>= 0). It is a type-dependent parameter.

URI

cim:WindContPType3IEC.tufiltp3

Cardinality

0..1

Type

Seconds

udvs

Voltage limit for hold UVRT status after deep voltage sags (uDVS). It is a project-dependent parameter.

URI

cim:WindContPType3IEC.udvs

Cardinality

0..1

Type

PU

updip

Voltage dip threshold for P-control (uPdip). Part of turbine control, often different (e.g 0.8) from converter thresholds. It is a project-dependent parameter.

URI

cim:WindContPType3IEC.updip

Cardinality

0..1

Type

PU

WindDynamicsLookupTable

The wind dynamics lookup table associated with this P control type 3 model.

URI

cim:WindContPType3IEC.WindDynamicsLookupTable

Cardinality

1..*

Type

WindDynamicsLookupTable

WindTurbineType3IEC

Wind turbine type 3 model with which this wind control P type 3 model is associated.

URI

cim:WindContPType3IEC.WindTurbineType3IEC

Cardinality

1

Type

WindTurbineType3IEC

zeta

Coefficient for active drive train damping (zeta). It is a type-dependent parameter.

URI

cim:WindContPType3IEC.zeta

Cardinality

0..1

Type

float