GovGASTWD
Woodwardâ„¢ gas turbine governor. [Footnote: Woodward gas turbines are an example of suitable products available commercially. This information is given for the convenience of users of this document and does not constitute an endorsement by IEC of these products.]
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Dataset containing the data objects. |
||
0..1 |
Valve positioner (A). |
||
0..1 |
Exhaust temperature parameter (Af1). |
||
0..1 |
Coefficient equal to 0,5(1-speed) (Af2). |
||
0..1 |
Valve positioner (B). |
||
0..1 |
(Bf1). Bf1 = E(1-w) where E (speed sensitivity coefficient) is 0,55 to 0,65 x Tr. |
||
0..1 |
Turbine torque coefficient Khhv (depends on heating value of fuel stream in combustion chamber) (Bf2). |
||
0..1 |
Valve positioner (C). |
||
0..1 |
Coefficient defining fuel flow where power output is 0 % (Cf2). Synchronous but no output. Typically 0,23 x Khhv (23 % fuel flow). |
||
0..1 |
Combustion reaction time delay (Ecr) (>= 0). |
||
0..1 |
Turbine and exhaust delay (Etd) (>= 0). |
||
0..1 |
Ratio of fuel adjustment (K3). |
||
0..1 |
Gain of radiation shield (K4). |
||
0..1 |
Gain of radiation shield (K5). |
||
0..1 |
Minimum fuel flow (K6). |
||
0..1 |
Drop governor gain (Kd). |
||
0..1 |
(Kdroop) (>= 0). |
||
0..1 |
Fuel system feedback (Kf). |
||
0..1 |
Isochronous Governor Gain (Ki). |
||
0..1 |
PID proportional gain (Kp). |
||
0..1 |
Base for power values (MWbase) (> 0). Unit = MW. |
||
0..1 |
Fuel control time constant (T) (>= 0). |
||
0..1 |
Radiation shield time constant (T3) (>= 0). |
||
0..1 |
Thermocouple time constant (T4) (>= 0). |
||
0..1 |
Temperature control time constant (T5) (>= 0). |
||
0..1 |
Temperature control (Tc). |
||
0..1 |
Compressor discharge time constant (Tcd) (>= 0). |
||
0..1 |
Power transducer time constant (Td) (>= 0). |
||
0..1 |
Fuel system time constant (Tf) (>= 0). |
||
0..1 |
Maximum Turbine limit (Tmax) (> GovGASTWD.tmin). |
||
0..1 |
Minimum turbine limit (Tmin) (< GovGASTWD.tmax). |
||
0..1 |
Rated temperature (Tr). |
||
0..1 |
Turbine rating (Trate). Unit = MW. |
||
0..1 |
Temperature controller integration rate (Tt) (>= 0). |
||
0..1 |
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
Turbine load controller providing input to this turbine-governor. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
bf1
(Bf1). Bf1 = E(1-w) where E (speed sensitivity coefficient) is 0,55 to 0,65 x Tr.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
bf2
Turbine torque coefficient Khhv (depends on heating value of fuel stream in combustion chamber) (Bf2).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
cf2
Coefficient defining fuel flow where power output is 0 % (Cf2). Synchronous but no output. Typically 0,23 x Khhv (23 % fuel flow).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
mwbase
Base for power values (MWbase) (> 0). Unit = MW.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
SynchronousMachineDynamics
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |