GovHydroWEH
WoodwardTM electric hydro governor. [Footnote: Woodward electric hydro governors are an example of suitable products available commercially. This information is given for the convenience of users of this document and does not constitute an endorsement by IEC of these products.]
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Type | Description | Inherited from |
---|---|---|---|
0..1 |
Speed deadband (db). |
n/a |
|
0..1 |
Value to allow the integral controller to advance beyond the gate limits (Dicn). |
n/a |
|
0..1 |
Value to allow the pilot valve controller to advance beyond the gate limits (Dpv). |
n/a |
|
0..1 |
Turbine damping factor (Dturb). Unit = delta P (PU of MWbase) / delta speed (PU). |
n/a |
|
0..1 |
Feedback signal selection (Sw). true = PID output (if R-Perm-Gate = droop and R-Perm-Pe = 0) false =... |
n/a |
|
0..1 |
Flowgate 1 (Fl1). Flow value for gate position point 1 for lookup table representing water flow through the turbine... |
n/a |
|
0..1 |
Flowgate 2 (Fl2). Flow value for gate position point 2 for lookup table representing water flow through the turbine... |
n/a |
|
0..1 |
Flowgate 3 (Fl3). Flow value for gate position point 3 for lookup table representing water flow through the turbine... |
n/a |
|
0..1 |
Flowgate 4 (Fl4). Flow value for gate position point 4 for lookup table representing water flow through the turbine... |
n/a |
|
0..1 |
Flowgate 5 (Fl5). Flow value for gate position point 5 for lookup table representing water flow through the turbine... |
n/a |
|
0..1 |
Flow P1 (Fp1). Turbine flow value for point 1 for lookup table representing PU mechanical power on machine MVA... |
n/a |
|
0..1 |
Flow P10 (Fp10). Turbine flow value for point 10 for lookup table representing PU mechanical power on machine MVA... |
n/a |
|
0..1 |
Flow P2 (Fp2). Turbine flow value for point 2 for lookup table representing PU mechanical power on machine MVA... |
n/a |
|
0..1 |
Flow P3 (Fp3). Turbine flow value for point 3 for lookup table representing PU mechanical power on machine MVA... |
n/a |
|
0..1 |
Flow P4 (Fp4). Turbine flow value for point 4 for lookup table representing PU mechanical power on machine MVA... |
n/a |
|
0..1 |
Flow P5 (Fp5). Turbine flow value for point 5 for lookup table representing PU mechanical power on machine MVA... |
n/a |
|
0..1 |
Flow P6 (Fp6). Turbine flow value for point 6 for lookup table representing PU mechanical power on machine MVA... |
n/a |
|
0..1 |
Flow P7 (Fp7). Turbine flow value for point 7 for lookup table representing PU mechanical power on machine MVA... |
n/a |
|
0..1 |
Flow P8 (Fp8). Turbine flow value for point 8 for lookup table representing PU mechanical power on machine MVA... |
n/a |
|
0..1 |
Flow P9 (Fp9). Turbine flow value for point 9 for lookup table representing PU mechanical power on machine MVA... |
n/a |
|
0..1 |
Maximum gate position (Gmax) (> GovHydroWEH.gmin). |
n/a |
|
0..1 |
Minimum gate position (Gmin) (< GovHydroWEH.gmax). |
n/a |
|
0..1 |
Maximum gate closing rate (Gtmxcl). |
n/a |
|
0..1 |
Maximum gate opening rate (Gtmxop). |
n/a |
|
0..1 |
Gate 1 (Gv1). Gate Position value for point 1 for lookup table representing water flow through the turbine as a... |
n/a |
|
0..1 |
Gate 2 (Gv2). Gate Position value for point 2 for lookup table representing water flow through the turbine as a... |
n/a |
|
0..1 |
Gate 3 (Gv3). Gate Position value for point 3 for lookup table representing water flow through the turbine as a... |
n/a |
|
0..1 |
Gate 4 (Gv4). Gate Position value for point 4 for lookup table representing water flow through the turbine as a... |
n/a |
|
0..1 |
Gate 5 (Gv5). Gate Position value for point 5 for lookup table representing water flow through the turbine as a... |
n/a |
|
0..1 |
Derivative controller derivative gain (Kd). |
n/a |
|
0..1 |
Derivative controller Integral gain (Ki). |
n/a |
|
0..1 |
Derivative control gain (Kp). |
n/a |
|
0..1 |
Base for power values (MWbase) (> 0). Unit = MW. |
n/a |
|
0..1 |
Pmss flow P1 (Pmss1). Mechanical power output for turbine flow point 1 for lookup table representing PU mechanical... |
n/a |
|
0..1 |
Pmss flow P10 (Pmss10). Mechanical power output for turbine flow point 10 for lookup table representing PU... |
n/a |
|
0..1 |
Pmss flow P2 (Pmss2). Mechanical power output for turbine flow point 2 for lookup table representing PU mechanical... |
n/a |
|
0..1 |
Pmss flow P3 (Pmss3). Mechanical power output for turbine flow point 3 for lookup table representing PU mechanical... |
n/a |
|
0..1 |
Pmss flow P4 (Pmss4). Mechanical power output for turbine flow point 4 for lookup table representing PU mechanical... |
n/a |
|
0..1 |
Pmss flow P5 (Pmss5). Mechanical power output for turbine flow point 5 for lookup table representing PU mechanical... |
n/a |
|
0..1 |
Pmss flow P6 (Pmss6). Mechanical power output for turbine flow point 6 for lookup table representing PU mechanical... |
n/a |
|
0..1 |
Pmss flow P7 (Pmss7). Mechanical power output for turbine flow point 7 for lookup table representing PU mechanical... |
n/a |
|
0..1 |
Pmss flow P8 (Pmss8). Mechanical power output for turbine flow point 8 for lookup table representing PU mechanical... |
n/a |
|
0..1 |
Pmss flow P9 (Pmss9). Mechanical power output for turbine flow point 9 for lookup table representing PU mechanical... |
n/a |
|
0..1 |
Permanent droop for governor output feedback (R-Perm-Gate). |
n/a |
|
0..1 |
Permanent droop for electrical power feedback (R-Perm-Pe). |
n/a |
|
0..1 |
Derivative controller time constant (Td) (>= 0). Limits the derivative characteristic beyond a breakdown... |
n/a |
|
0..1 |
Distributive valve time lag time constant (Tdv) (>= 0). |
n/a |
|
0..1 |
Value to allow the distribution valve controller to advance beyond the gate movement rate limit (Tg) (>= 0). |
n/a |
|
0..1 |
Pilot valve time lag time constant (Tp) (>= 0). |
n/a |
|
0..1 |
Electrical power droop time constant (Tpe) (>= 0). |
n/a |
|
0..1 |
Water inertia time constant (Tw) (> 0). |
n/a |
|
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either... |
|||
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an... |
|||
Turbine load controller providing input to this turbine-governor. |
|||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
Dataset containing the data objects. |
|||
0..* |
All names of this identified object. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..* |
Data objects registered. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and... |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to... |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is... |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
dicn
Value to allow the integral controller to advance beyond the gate limits (Dicn).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
dpv
Value to allow the pilot valve controller to advance beyond the gate limits (Dpv).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
dturb
Turbine damping factor (Dturb). Unit = delta P (PU of MWbase) / delta speed (PU).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
feedbackSignal
Feedback signal selection (Sw). true = PID output (if R-Perm-Gate = droop and R-Perm-Pe = 0) false = electrical power (if R-Perm-Gate = 0 and R-Perm-Pe = droop) or false = gate position (if R-Perm-Gate = droop and R-Perm-Pe = 0). Typical value = false.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fl1
Flowgate 1 (Fl1). Flow value for gate position point 1 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fl2
Flowgate 2 (Fl2). Flow value for gate position point 2 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fl3
Flowgate 3 (Fl3). Flow value for gate position point 3 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fl4
Flowgate 4 (Fl4). Flow value for gate position point 4 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fl5
Flowgate 5 (Fl5). Flow value for gate position point 5 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fp1
Flow P1 (Fp1). Turbine flow value for point 1 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fp10
Flow P10 (Fp10). Turbine flow value for point 10 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fp2
Flow P2 (Fp2). Turbine flow value for point 2 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fp3
Flow P3 (Fp3). Turbine flow value for point 3 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fp4
Flow P4 (Fp4). Turbine flow value for point 4 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fp5
Flow P5 (Fp5). Turbine flow value for point 5 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fp6
Flow P6 (Fp6). Turbine flow value for point 6 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fp7
Flow P7 (Fp7). Turbine flow value for point 7 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fp8
Flow P8 (Fp8). Turbine flow value for point 8 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fp9
Flow P9 (Fp9). Turbine flow value for point 9 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gmax
Maximum gate position (Gmax) (> GovHydroWEH.gmin).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gmin
Minimum gate position (Gmin) (< GovHydroWEH.gmax).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv1
Gate 1 (Gv1). Gate Position value for point 1 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv2
Gate 2 (Gv2). Gate Position value for point 2 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv3
Gate 3 (Gv3). Gate Position value for point 3 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv4
Gate 4 (Gv4). Gate Position value for point 4 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv5
Gate 5 (Gv5). Gate Position value for point 5 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
mwbase
Base for power values (MWbase) (> 0). Unit = MW.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
pmss1
Pmss flow P1 (Pmss1). Mechanical power output for turbine flow point 1 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmss10
Pmss flow P10 (Pmss10). Mechanical power output for turbine flow point 10 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmss2
Pmss flow P2 (Pmss2). Mechanical power output for turbine flow point 2 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmss3
Pmss flow P3 (Pmss3). Mechanical power output for turbine flow point 3 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmss4
Pmss flow P4 (Pmss4). Mechanical power output for turbine flow point 4 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmss5
Pmss flow P5 (Pmss5). Mechanical power output for turbine flow point 5 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmss6
Pmss flow P6 (Pmss6). Mechanical power output for turbine flow point 6 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmss7
Pmss flow P7 (Pmss7). Mechanical power output for turbine flow point 7 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmss8
Pmss flow P8 (Pmss8). Mechanical power output for turbine flow point 8 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmss9
Pmss flow P9 (Pmss9). Mechanical power output for turbine flow point 9 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
rpg
Permanent droop for governor output feedback (R-Perm-Gate).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
rpp
Permanent droop for electrical power feedback (R-Perm-Pe).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
SynchronousMachineDynamics
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
td
Derivative controller time constant (Td) (>= 0). Limits the derivative characteristic beyond a breakdown frequency to avoid amplification of high-frequency noise.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tdv
Distributive valve time lag time constant (Tdv) (>= 0).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tg
Value to allow the distribution valve controller to advance beyond the gate movement rate limit (Tg) (>= 0).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tpe
Electrical power droop time constant (Tpe) (>= 0).
URI |
|
---|---|
Cardinality |
0..1 |
Type |