GovHydroWEH

WoodwardTM electric hydro governor. [Footnote: Woodward electric hydro governors are an example of suitable products available commercially. This information is given for the convenience of users of this document and does not constitute an endorsement by IEC of these products.]

Type

Class

URI

cim:GovHydroWEH

CIM standard (perspective)

IEC61970 (Grid)

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

InstanceSet

1

InstanceSet

Dataset containing the data objects.

db

0..1

PU

Speed deadband (db).

dicn

0..1

PU

Value to allow the integral controller to advance beyond the gate limits (Dicn).

dpv

0..1

PU

Value to allow the pilot valve controller to advance beyond the gate limits (Dpv).

dturb

0..1

PU

Turbine damping factor (Dturb). Unit = delta P (PU of MWbase) / delta speed (PU).

feedbackSignal

0..1

boolean

Feedback signal selection (Sw). true = PID output (if R-Perm-Gate = droop and R-Perm-Pe = 0) false = electrical power (if R-Perm-Gate = 0 and R-Perm-Pe = droop) or false = gate position (if R-Perm-Gate = droop and R-Perm-Pe = 0). Typical value = false.

fl1

0..1

PU

Flowgate 1 (Fl1). Flow value for gate position point 1 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

fl2

0..1

PU

Flowgate 2 (Fl2). Flow value for gate position point 2 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

fl3

0..1

PU

Flowgate 3 (Fl3). Flow value for gate position point 3 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

fl4

0..1

PU

Flowgate 4 (Fl4). Flow value for gate position point 4 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

fl5

0..1

PU

Flowgate 5 (Fl5). Flow value for gate position point 5 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

fp1

0..1

PU

Flow P1 (Fp1). Turbine flow value for point 1 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

fp10

0..1

PU

Flow P10 (Fp10). Turbine flow value for point 10 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

fp2

0..1

PU

Flow P2 (Fp2). Turbine flow value for point 2 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

fp3

0..1

PU

Flow P3 (Fp3). Turbine flow value for point 3 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

fp4

0..1

PU

Flow P4 (Fp4). Turbine flow value for point 4 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

fp5

0..1

PU

Flow P5 (Fp5). Turbine flow value for point 5 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

fp6

0..1

PU

Flow P6 (Fp6). Turbine flow value for point 6 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

fp7

0..1

PU

Flow P7 (Fp7). Turbine flow value for point 7 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

fp8

0..1

PU

Flow P8 (Fp8). Turbine flow value for point 8 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

fp9

0..1

PU

Flow P9 (Fp9). Turbine flow value for point 9 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

gmax

0..1

PU

Maximum gate position (Gmax) (> GovHydroWEH.gmin).

gmin

0..1

PU

Minimum gate position (Gmin) (< GovHydroWEH.gmax).

gtmxcl

0..1

PU

Maximum gate closing rate (Gtmxcl).

gtmxop

0..1

PU

Maximum gate opening rate (Gtmxop).

gv1

0..1

PU

Gate 1 (Gv1). Gate Position value for point 1 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

gv2

0..1

PU

Gate 2 (Gv2). Gate Position value for point 2 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

gv3

0..1

PU

Gate 3 (Gv3). Gate Position value for point 3 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

gv4

0..1

PU

Gate 4 (Gv4). Gate Position value for point 4 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

gv5

0..1

PU

Gate 5 (Gv5). Gate Position value for point 5 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

kd

0..1

PU

Derivative controller derivative gain (Kd).

ki

0..1

PU

Derivative controller Integral gain (Ki).

kp

0..1

PU

Derivative control gain (Kp).

mwbase

0..1

ActivePower

Base for power values (MWbase) (> 0). Unit = MW.

pmss1

0..1

PU

Pmss flow P1 (Pmss1). Mechanical power output for turbine flow point 1 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

pmss10

0..1

PU

Pmss flow P10 (Pmss10). Mechanical power output for turbine flow point 10 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

pmss2

0..1

PU

Pmss flow P2 (Pmss2). Mechanical power output for turbine flow point 2 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

pmss3

0..1

PU

Pmss flow P3 (Pmss3). Mechanical power output for turbine flow point 3 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

pmss4

0..1

PU

Pmss flow P4 (Pmss4). Mechanical power output for turbine flow point 4 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

pmss5

0..1

PU

Pmss flow P5 (Pmss5). Mechanical power output for turbine flow point 5 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

pmss6

0..1

PU

Pmss flow P6 (Pmss6). Mechanical power output for turbine flow point 6 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

pmss7

0..1

PU

Pmss flow P7 (Pmss7). Mechanical power output for turbine flow point 7 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

pmss8

0..1

PU

Pmss flow P8 (Pmss8). Mechanical power output for turbine flow point 8 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

pmss9

0..1

PU

Pmss flow P9 (Pmss9). Mechanical power output for turbine flow point 9 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

rpg

0..1

float

Permanent droop for governor output feedback (R-Perm-Gate).

rpp

0..1

float

Permanent droop for electrical power feedback (R-Perm-Pe).

td

0..1

Seconds

Derivative controller time constant (Td) (>= 0). Limits the derivative characteristic beyond a breakdown frequency to avoid amplification of high-frequency noise.

tdv

0..1

Seconds

Distributive valve time lag time constant (Tdv) (>= 0).

tg

0..1

Seconds

Value to allow the distribution valve controller to advance beyond the gate movement rate limit (Tg) (>= 0).

tp

0..1

Seconds

Pilot valve time lag time constant (Tp) (>= 0).

tpe

0..1

Seconds

Electrical power droop time constant (Tpe) (>= 0).

tw

0..1

Seconds

Water inertia time constant (Tw) (> 0).

AsynchronousMachineDynamics

0..1

AsynchronousMachineDynamics

Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

SynchronousMachineDynamics

0..1

SynchronousMachineDynamics

Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

TurbineLoadControllerDynamics

0..1

TurbineLoadControllerDynamics

Turbine load controller providing input to this turbine-governor.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

enabled

0..1

boolean

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

AsynchronousMachineDynamics

Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

URI

cim:TurbineGovernorDynamics.AsynchronousMachineDynamics

Cardinality

0..1

Type

AsynchronousMachineDynamics

Inherited from

TurbineGovernorDynamics

db

Speed deadband (db).

URI

cim:GovHydroWEH.db

Cardinality

0..1

Type

PU

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

dicn

Value to allow the integral controller to advance beyond the gate limits (Dicn).

URI

cim:GovHydroWEH.dicn

Cardinality

0..1

Type

PU

dpv

Value to allow the pilot valve controller to advance beyond the gate limits (Dpv).

URI

cim:GovHydroWEH.dpv

Cardinality

0..1

Type

PU

dturb

Turbine damping factor (Dturb). Unit = delta P (PU of MWbase) / delta speed (PU).

URI

cim:GovHydroWEH.dturb

Cardinality

0..1

Type

PU

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

URI

cim:DynamicsFunctionBlock.enabled

Cardinality

0..1

Type

boolean

Inherited from

DynamicsFunctionBlock

feedbackSignal

Feedback signal selection (Sw). true = PID output (if R-Perm-Gate = droop and R-Perm-Pe = 0) false = electrical power (if R-Perm-Gate = 0 and R-Perm-Pe = droop) or false = gate position (if R-Perm-Gate = droop and R-Perm-Pe = 0). Typical value = false.

URI

cim:GovHydroWEH.feedbackSignal

Cardinality

0..1

Type

boolean

fl1

Flowgate 1 (Fl1). Flow value for gate position point 1 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

URI

cim:GovHydroWEH.fl1

Cardinality

0..1

Type

PU

fl2

Flowgate 2 (Fl2). Flow value for gate position point 2 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

URI

cim:GovHydroWEH.fl2

Cardinality

0..1

Type

PU

fl3

Flowgate 3 (Fl3). Flow value for gate position point 3 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

URI

cim:GovHydroWEH.fl3

Cardinality

0..1

Type

PU

fl4

Flowgate 4 (Fl4). Flow value for gate position point 4 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

URI

cim:GovHydroWEH.fl4

Cardinality

0..1

Type

PU

fl5

Flowgate 5 (Fl5). Flow value for gate position point 5 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

URI

cim:GovHydroWEH.fl5

Cardinality

0..1

Type

PU

fp1

Flow P1 (Fp1). Turbine flow value for point 1 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.fp1

Cardinality

0..1

Type

PU

fp10

Flow P10 (Fp10). Turbine flow value for point 10 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.fp10

Cardinality

0..1

Type

PU

fp2

Flow P2 (Fp2). Turbine flow value for point 2 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.fp2

Cardinality

0..1

Type

PU

fp3

Flow P3 (Fp3). Turbine flow value for point 3 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.fp3

Cardinality

0..1

Type

PU

fp4

Flow P4 (Fp4). Turbine flow value for point 4 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.fp4

Cardinality

0..1

Type

PU

fp5

Flow P5 (Fp5). Turbine flow value for point 5 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.fp5

Cardinality

0..1

Type

PU

fp6

Flow P6 (Fp6). Turbine flow value for point 6 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.fp6

Cardinality

0..1

Type

PU

fp7

Flow P7 (Fp7). Turbine flow value for point 7 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.fp7

Cardinality

0..1

Type

PU

fp8

Flow P8 (Fp8). Turbine flow value for point 8 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.fp8

Cardinality

0..1

Type

PU

fp9

Flow P9 (Fp9). Turbine flow value for point 9 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.fp9

Cardinality

0..1

Type

PU

gmax

Maximum gate position (Gmax) (> GovHydroWEH.gmin).

URI

cim:GovHydroWEH.gmax

Cardinality

0..1

Type

PU

gmin

Minimum gate position (Gmin) (< GovHydroWEH.gmax).

URI

cim:GovHydroWEH.gmin

Cardinality

0..1

Type

PU

gtmxcl

Maximum gate closing rate (Gtmxcl).

URI

cim:GovHydroWEH.gtmxcl

Cardinality

0..1

Type

PU

gtmxop

Maximum gate opening rate (Gtmxop).

URI

cim:GovHydroWEH.gtmxop

Cardinality

0..1

Type

PU

gv1

Gate 1 (Gv1). Gate Position value for point 1 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

URI

cim:GovHydroWEH.gv1

Cardinality

0..1

Type

PU

gv2

Gate 2 (Gv2). Gate Position value for point 2 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

URI

cim:GovHydroWEH.gv2

Cardinality

0..1

Type

PU

gv3

Gate 3 (Gv3). Gate Position value for point 3 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

URI

cim:GovHydroWEH.gv3

Cardinality

0..1

Type

PU

gv4

Gate 4 (Gv4). Gate Position value for point 4 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

URI

cim:GovHydroWEH.gv4

Cardinality

0..1

Type

PU

gv5

Gate 5 (Gv5). Gate Position value for point 5 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.

URI

cim:GovHydroWEH.gv5

Cardinality

0..1

Type

PU

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

kd

Derivative controller derivative gain (Kd).

URI

cim:GovHydroWEH.kd

Cardinality

0..1

Type

PU

ki

Derivative controller Integral gain (Ki).

URI

cim:GovHydroWEH.ki

Cardinality

0..1

Type

PU

kp

Derivative control gain (Kp).

URI

cim:GovHydroWEH.kp

Cardinality

0..1

Type

PU

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

mwbase

Base for power values (MWbase) (> 0). Unit = MW.

URI

cim:GovHydroWEH.mwbase

Cardinality

0..1

Type

ActivePower

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

pmss1

Pmss flow P1 (Pmss1). Mechanical power output for turbine flow point 1 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.pmss1

Cardinality

0..1

Type

PU

pmss10

Pmss flow P10 (Pmss10). Mechanical power output for turbine flow point 10 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.pmss10

Cardinality

0..1

Type

PU

pmss2

Pmss flow P2 (Pmss2). Mechanical power output for turbine flow point 2 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.pmss2

Cardinality

0..1

Type

PU

pmss3

Pmss flow P3 (Pmss3). Mechanical power output for turbine flow point 3 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.pmss3

Cardinality

0..1

Type

PU

pmss4

Pmss flow P4 (Pmss4). Mechanical power output for turbine flow point 4 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.pmss4

Cardinality

0..1

Type

PU

pmss5

Pmss flow P5 (Pmss5). Mechanical power output for turbine flow point 5 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.pmss5

Cardinality

0..1

Type

PU

pmss6

Pmss flow P6 (Pmss6). Mechanical power output for turbine flow point 6 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.pmss6

Cardinality

0..1

Type

PU

pmss7

Pmss flow P7 (Pmss7). Mechanical power output for turbine flow point 7 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.pmss7

Cardinality

0..1

Type

PU

pmss8

Pmss flow P8 (Pmss8). Mechanical power output for turbine flow point 8 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.pmss8

Cardinality

0..1

Type

PU

pmss9

Pmss flow P9 (Pmss9). Mechanical power output for turbine flow point 9 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.

URI

cim:GovHydroWEH.pmss9

Cardinality

0..1

Type

PU

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

rpg

Permanent droop for governor output feedback (R-Perm-Gate).

URI

cim:GovHydroWEH.rpg

Cardinality

0..1

Type

float

rpp

Permanent droop for electrical power feedback (R-Perm-Pe).

URI

cim:GovHydroWEH.rpp

Cardinality

0..1

Type

float

SynchronousMachineDynamics

Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

URI

cim:TurbineGovernorDynamics.SynchronousMachineDynamics

Cardinality

0..1

Type

SynchronousMachineDynamics

Inherited from

TurbineGovernorDynamics

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

td

Derivative controller time constant (Td) (>= 0). Limits the derivative characteristic beyond a breakdown frequency to avoid amplification of high-frequency noise.

URI

cim:GovHydroWEH.td

Cardinality

0..1

Type

Seconds

tdv

Distributive valve time lag time constant (Tdv) (>= 0).

URI

cim:GovHydroWEH.tdv

Cardinality

0..1

Type

Seconds

tg

Value to allow the distribution valve controller to advance beyond the gate movement rate limit (Tg) (>= 0).

URI

cim:GovHydroWEH.tg

Cardinality

0..1

Type

Seconds

tp

Pilot valve time lag time constant (Tp) (>= 0).

URI

cim:GovHydroWEH.tp

Cardinality

0..1

Type

Seconds

tpe

Electrical power droop time constant (Tpe) (>= 0).

URI

cim:GovHydroWEH.tpe

Cardinality

0..1

Type

Seconds

TurbineLoadControllerDynamics

Turbine load controller providing input to this turbine-governor.

URI

cim:TurbineGovernorDynamics.TurbineLoadControllerDynamics

Cardinality

0..1

Type

TurbineLoadControllerDynamics

Inherited from

TurbineGovernorDynamics

tw

Water inertia time constant (Tw) (> 0).

URI

cim:GovHydroWEH.tw

Cardinality

0..1

Type

Seconds