PssWECC
Dual input power system stabilizer, based on IEEE type 2, with modified output limiter defined by WECC (Western Electricity Coordinating Council, USA).
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Excitation system model with which this power system stabilizer model is associated. |
||
1 |
Dataset containing the data objects. |
||
0..1 |
Type of input signal #1 (rotorAngularFrequencyDeviation, busFrequencyDeviation, generatorElectricalPower, generatorAcceleratingPower, busVoltage, or busVoltageDerivative - shall be different than PssWECC.inputSignal2Type). Typical value = rotorAngularFrequencyDeviation. |
||
0..1 |
Type of input signal #2 (rotorAngularFrequencyDeviation, busFrequencyDeviation, generatorElectricalPower, generatorAcceleratingPower, busVoltage, busVoltageDerivative - shall be different than PssWECC.inputSignal1Type). Typical value = busVoltageDerivative. |
||
0..1 |
Input signal 1 gain (K1). Typical value = 1,13. |
||
0..1 |
Input signal 2 gain (K2). Typical value = 0,0. |
||
0..1 |
Input signal 1 transducer time constant (T1) (>= 0). Typical value = 0,037. |
||
0..1 |
Lag time constant (T10) (>= 0). Typical value = 0. |
||
0..1 |
Input signal 2 transducer time constant (T2) (>= 0). Typical value = 0,0. |
||
0..1 |
Stabilizer washout time constant (T3) (>= 0). Typical value = 9,5. |
||
0..1 |
Stabilizer washout time lag constant (T4) (>= 0). Typical value = 9,5. |
||
0..1 |
Lead time constant (T5) (>= 0). Typical value = 1,7. |
||
0..1 |
Lag time constant (T6) (>= 0). Typical value = 1,5. |
||
0..1 |
Lead time constant (T7) (>= 0). Typical value = 1,7. |
||
0..1 |
Lag time constant (T8) (>= 0). Typical value = 1,5. |
||
0..1 |
Lead time constant (T9) (>= 0). Typical value = 0. |
||
0..1 |
Minimum value for voltage compensator output (VCL). Typical value = 0. |
||
0..1 |
Maximum value for voltage compensator output (VCU). Typical value = 0. |
||
0..1 |
Maximum output signal (Vsmax) (> PssWECC.vsmin). Typical value = 0,05. |
||
0..1 |
Minimum output signal (Vsmin) (< PssWECC.vsmax). Typical value = -0,05. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Remote input signal used by this power system stabilizer model. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
ExcitationSystemDynamics
Excitation system model with which this power system stabilizer model is associated.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
inputSignal1Type
Type of input signal #1 (rotorAngularFrequencyDeviation, busFrequencyDeviation, generatorElectricalPower, generatorAcceleratingPower, busVoltage, or busVoltageDerivative - shall be different than PssWECC.inputSignal2Type). Typical value = rotorAngularFrequencyDeviation.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
inputSignal2Type
Type of input signal #2 (rotorAngularFrequencyDeviation, busFrequencyDeviation, generatorElectricalPower, generatorAcceleratingPower, busVoltage, busVoltageDerivative - shall be different than PssWECC.inputSignal1Type). Typical value = busVoltageDerivative.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
RemoteInputSignal
Remote input signal used by this power system stabilizer model.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
t1
Input signal 1 transducer time constant (T1) (>= 0). Typical value = 0,037.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t2
Input signal 2 transducer time constant (T2) (>= 0). Typical value = 0,0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t3
Stabilizer washout time constant (T3) (>= 0). Typical value = 9,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t4
Stabilizer washout time lag constant (T4) (>= 0). Typical value = 9,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
vcl
Minimum value for voltage compensator output (VCL). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vcu
Maximum value for voltage compensator output (VCU). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vsmax
Maximum output signal (Vsmax) (> PssWECC.vsmin). Typical value = 0,05.
URI |
|
---|---|
Cardinality |
0..1 |
Type |