GovHydroIEEE2
IEEE hydro turbine governor model represents plants with straightforward penstock configurations and hydraulic-dashpot governors. Reference: IEEE Transactions on Power Apparatus and Systems, November/December 1973, Volume PAS-92, Number 6, Dynamic Models for Steam and Hydro Turbines in Power System Studies, page 1904.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Dataset containing the data objects. |
||
0..1 |
Turbine numerator multiplier (Aturb). Typical value = -1. |
||
0..1 |
Turbine denominator multiplier (Bturb) (> 0). Typical value = 0,5. |
||
0..1 |
Nonlinear gain point 1, PU gv (Gv1). Typical value = 0. |
||
0..1 |
Nonlinear gain point 2, PU gv (Gv2). Typical value = 0. |
||
0..1 |
Nonlinear gain point 3, PU gv (Gv3). Typical value = 0. |
||
0..1 |
Nonlinear gain point 4, PU gv (Gv4). Typical value = 0. |
||
0..1 |
Nonlinear gain point 5, PU gv (Gv5). Typical value = 0. |
||
0..1 |
Nonlinear gain point 6, PU gv (Gv6). Typical value = 0. |
||
0..1 |
Turbine gain (Kturb). Typical value = 1. |
||
0..1 |
Base for power values (MWbase) (> 0). Unit = MW. |
||
0..1 |
Nonlinear gain point 1, PU power (Pgv1). Typical value = 0. |
||
0..1 |
Nonlinear gain point 2, PU power (Pgv2). Typical value = 0. |
||
0..1 |
Nonlinear gain point 3, PU power (Pgv3). Typical value = 0. |
||
0..1 |
Nonlinear gain point 4, PU power (Pgv4). Typical value = 0. |
||
0..1 |
Nonlinear gain point 5, PU power (Pgv5). Typical value = 0. |
||
0..1 |
Nonlinear gain point 6, PU power (Pgv6). Typical value = 0. |
||
0..1 |
Maximum gate opening (Pmax) (> GovHydroIEEE2.pmin). Typical value = 1. |
||
0..1 |
Minimum gate opening (Pmin) (<GovHydroIEEE2.pmax). Typical value = 0. |
||
0..1 |
Permanent droop (Rperm). Typical value = 0,05. |
||
0..1 |
Temporary droop (Rtemp). Typical value = 0,5. |
||
0..1 |
Gate servo time constant (Tg) (>= 0). Typical value = 0,5. |
||
0..1 |
Pilot servo valve time constant (Tp) (>= 0). Typical value = 0,03. |
||
0..1 |
Dashpot time constant (Tr) (>= 0). Typical value = 12. |
||
0..1 |
Water inertia time constant (Tw) (>= 0). Typical value = 2. |
||
0..1 |
Maximum gate closing velocity (Uc) (<0). Typical value = -0,1. |
||
0..1 |
Maximum gate opening velocity (Uo). Unit = PU / s. Typical value = 0,1. |
||
0..1 |
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
Turbine load controller providing input to this turbine-governor. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
aturb
Turbine numerator multiplier (Aturb). Typical value = -1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
bturb
Turbine denominator multiplier (Bturb) (> 0). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
gv1
Nonlinear gain point 1, PU gv (Gv1). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv2
Nonlinear gain point 2, PU gv (Gv2). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv3
Nonlinear gain point 3, PU gv (Gv3). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv4
Nonlinear gain point 4, PU gv (Gv4). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv5
Nonlinear gain point 5, PU gv (Gv5). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv6
Nonlinear gain point 6, PU gv (Gv6). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
mwbase
Base for power values (MWbase) (> 0). Unit = MW.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
pgv1
Nonlinear gain point 1, PU power (Pgv1). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv2
Nonlinear gain point 2, PU power (Pgv2). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv3
Nonlinear gain point 3, PU power (Pgv3). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv4
Nonlinear gain point 4, PU power (Pgv4). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv5
Nonlinear gain point 5, PU power (Pgv5). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv6
Nonlinear gain point 6, PU power (Pgv6). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmax
Maximum gate opening (Pmax) (> GovHydroIEEE2.pmin). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmin
Minimum gate opening (Pmin) (<GovHydroIEEE2.pmax). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
rperm
Permanent droop (Rperm). Typical value = 0,05.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
rtemp
Temporary droop (Rtemp). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
SynchronousMachineDynamics
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
tg
Gate servo time constant (Tg) (>= 0). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tp
Pilot servo valve time constant (Tp) (>= 0). Typical value = 0,03.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tr
Dashpot time constant (Tr) (>= 0). Typical value = 12.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TurbineLoadControllerDynamics
Turbine load controller providing input to this turbine-governor.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
tw
Water inertia time constant (Tw) (>= 0). Typical value = 2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
uc
Maximum gate closing velocity (Uc) (<0). Typical value = -0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |