GovGAST1

Modified single shaft gas turbine.

Type

Class

URI

cim:GovGAST1

CIM standard (perspective)

IEC61970 (Grid)

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

InstanceSet

1

InstanceSet

Dataset containing the data objects.

a

0..1

float

Turbine power time constant numerator scale factor (a). Typical value = 0,8.

b

0..1

float

Turbine power time constant denominator scale factor (b) (>0). Typical value = 1.

db1

0..1

Frequency

Intentional dead-band width (db1). Unit = Hz. Typical value = 0.

db2

0..1

ActivePower

Unintentional dead-band (db2). Unit = MW. Typical value = 0.

eps

0..1

Frequency

Intentional db hysteresis (eps). Unit = Hz. Typical value = 0.

fidle

0..1

PU

Fuel flow at zero power output (Fidle). Typical value = 0,18.

gv1

0..1

PU

Nonlinear gain point 1, PU gv (Gv1). Typical value = 0.

gv2

0..1

PU

Nonlinear gain point 2,PU gv (Gv2). Typical value = 0.

gv3

0..1

PU

Nonlinear gain point 3, PU gv (Gv3). Typical value = 0.

gv4

0..1

PU

Nonlinear gain point 4, PU gv (Gv4). Typical value = 0.

gv5

0..1

PU

Nonlinear gain point 5, PU gv (Gv5). Typical value = 0.

gv6

0..1

PU

Nonlinear gain point 6, PU gv (Gv6). Typical value = 0.

ka

0..1

PU

Governor gain (Ka). Typical value = 0.

kt

0..1

PU

Temperature limiter gain (Kt). Typical value = 3.

lmax

0..1

PU

Ambient temperature load limit (Lmax). Lmax is the turbine power output corresponding to the limiting exhaust gas temperature. Typical value = 1.

loadinc

0..1

PU

Valve position change allowed at fast rate (Loadinc). Typical value = 0,05.

ltrate

0..1

float

Maximum long term fuel valve opening rate (Ltrate). Typical value = 0,02.

mwbase

0..1

ActivePower

Base for power values (MWbase) (> 0). Unit = MW.

pgv1

0..1

PU

Nonlinear gain point 1, PU power (Pgv1). Typical value = 0.

pgv2

0..1

PU

Nonlinear gain point 2, PU power (Pgv2). Typical value = 0.

pgv3

0..1

PU

Nonlinear gain point 3, PU power (Pgv3). Typical value = 0.

pgv4

0..1

PU

Nonlinear gain point 4, PU power (Pgv4). Typical value = 0.

pgv5

0..1

PU

Nonlinear gain point 5, PU power (Pgv5). Typical value = 0.

pgv6

0..1

PU

Nonlinear gain point 6, PU power (Pgv6). Typical value = 0.

r

0..1

PU

Permanent droop (R) (>0). Typical value = 0,04.

rmax

0..1

float

Maximum fuel valve opening rate (Rmax). Unit = PU / s. Typical value = 1.

t1

0..1

Seconds

Governor mechanism time constant (T1) (>= 0). T1 represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical value = 0,5.

t2

0..1

Seconds

Turbine power time constant (T2) (>= 0). T2 represents delay due to internal energy storage of the gas turbine engine. T2 can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi-shaft engine, or with the compressibility of gas in the plenum of the free power turbine of an aero-derivative unit, for example. Typical value = 0,5.

t3

0..1

Seconds

Turbine exhaust temperature time constant (T3) (>= 0). T3 represents delay in the exhaust temperature and load limiting system. Typical value = 3.

t4

0..1

Seconds

Governor lead time constant (T4) (>= 0). Typical value = 0.

t5

0..1

Seconds

Governor lag time constant (T5) (>= 0). If = 0, entire gain and lead-lag block is bypassed. Typical value = 0.

tltr

0..1

Seconds

Valve position averaging time constant (Tltr) (>= 0). Typical value = 10.

vmax

0..1

PU

Maximum turbine power, PU of MWbase (Vmax) (> GovGAST1.vmin). Typical value = 1.

vmin

0..1

PU

Minimum turbine power, PU of MWbase (Vmin) (< GovGAST1.vmax). Typical value = 0.

AsynchronousMachineDynamics

0..1

AsynchronousMachineDynamics

Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

SynchronousMachineDynamics

0..1

SynchronousMachineDynamics

Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

TurbineLoadControllerDynamics

0..1

TurbineLoadControllerDynamics

Turbine load controller providing input to this turbine-governor.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

enabled

0..1

boolean

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


a

Turbine power time constant numerator scale factor (a). Typical value = 0,8.

URI

cim:GovGAST1.a

Cardinality

0..1

Type

float

aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

AsynchronousMachineDynamics

Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

URI

cim:TurbineGovernorDynamics.AsynchronousMachineDynamics

Cardinality

0..1

Type

AsynchronousMachineDynamics

Inherited from

TurbineGovernorDynamics

b

Turbine power time constant denominator scale factor (b) (>0). Typical value = 1.

URI

cim:GovGAST1.b

Cardinality

0..1

Type

float

db1

Intentional dead-band width (db1). Unit = Hz. Typical value = 0.

URI

cim:GovGAST1.db1

Cardinality

0..1

Type

Frequency

db2

Unintentional dead-band (db2). Unit = MW. Typical value = 0.

URI

cim:GovGAST1.db2

Cardinality

0..1

Type

ActivePower

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

URI

cim:DynamicsFunctionBlock.enabled

Cardinality

0..1

Type

boolean

Inherited from

DynamicsFunctionBlock

eps

Intentional db hysteresis (eps). Unit = Hz. Typical value = 0.

URI

cim:GovGAST1.eps

Cardinality

0..1

Type

Frequency

fidle

Fuel flow at zero power output (Fidle). Typical value = 0,18.

URI

cim:GovGAST1.fidle

Cardinality

0..1

Type

PU

gv1

Nonlinear gain point 1, PU gv (Gv1). Typical value = 0.

URI

cim:GovGAST1.gv1

Cardinality

0..1

Type

PU

gv2

Nonlinear gain point 2,PU gv (Gv2). Typical value = 0.

URI

cim:GovGAST1.gv2

Cardinality

0..1

Type

PU

gv3

Nonlinear gain point 3, PU gv (Gv3). Typical value = 0.

URI

cim:GovGAST1.gv3

Cardinality

0..1

Type

PU

gv4

Nonlinear gain point 4, PU gv (Gv4). Typical value = 0.

URI

cim:GovGAST1.gv4

Cardinality

0..1

Type

PU

gv5

Nonlinear gain point 5, PU gv (Gv5). Typical value = 0.

URI

cim:GovGAST1.gv5

Cardinality

0..1

Type

PU

gv6

Nonlinear gain point 6, PU gv (Gv6). Typical value = 0.

URI

cim:GovGAST1.gv6

Cardinality

0..1

Type

PU

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

ka

Governor gain (Ka). Typical value = 0.

URI

cim:GovGAST1.ka

Cardinality

0..1

Type

PU

kt

Temperature limiter gain (Kt). Typical value = 3.

URI

cim:GovGAST1.kt

Cardinality

0..1

Type

PU

lmax

Ambient temperature load limit (Lmax). Lmax is the turbine power output corresponding to the limiting exhaust gas temperature. Typical value = 1.

URI

cim:GovGAST1.lmax

Cardinality

0..1

Type

PU

loadinc

Valve position change allowed at fast rate (Loadinc). Typical value = 0,05.

URI

cim:GovGAST1.loadinc

Cardinality

0..1

Type

PU

ltrate

Maximum long term fuel valve opening rate (Ltrate). Typical value = 0,02.

URI

cim:GovGAST1.ltrate

Cardinality

0..1

Type

float

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

mwbase

Base for power values (MWbase) (> 0). Unit = MW.

URI

cim:GovGAST1.mwbase

Cardinality

0..1

Type

ActivePower

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

pgv1

Nonlinear gain point 1, PU power (Pgv1). Typical value = 0.

URI

cim:GovGAST1.pgv1

Cardinality

0..1

Type

PU

pgv2

Nonlinear gain point 2, PU power (Pgv2). Typical value = 0.

URI

cim:GovGAST1.pgv2

Cardinality

0..1

Type

PU

pgv3

Nonlinear gain point 3, PU power (Pgv3). Typical value = 0.

URI

cim:GovGAST1.pgv3

Cardinality

0..1

Type

PU

pgv4

Nonlinear gain point 4, PU power (Pgv4). Typical value = 0.

URI

cim:GovGAST1.pgv4

Cardinality

0..1

Type

PU

pgv5

Nonlinear gain point 5, PU power (Pgv5). Typical value = 0.

URI

cim:GovGAST1.pgv5

Cardinality

0..1

Type

PU

pgv6

Nonlinear gain point 6, PU power (Pgv6). Typical value = 0.

URI

cim:GovGAST1.pgv6

Cardinality

0..1

Type

PU

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

r

Permanent droop (R) (>0). Typical value = 0,04.

URI

cim:GovGAST1.r

Cardinality

0..1

Type

PU

rmax

Maximum fuel valve opening rate (Rmax). Unit = PU / s. Typical value = 1.

URI

cim:GovGAST1.rmax

Cardinality

0..1

Type

float

SynchronousMachineDynamics

Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

URI

cim:TurbineGovernorDynamics.SynchronousMachineDynamics

Cardinality

0..1

Type

SynchronousMachineDynamics

Inherited from

TurbineGovernorDynamics

t1

Governor mechanism time constant (T1) (>= 0). T1 represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical value = 0,5.

URI

cim:GovGAST1.t1

Cardinality

0..1

Type

Seconds

t2

Turbine power time constant (T2) (>= 0). T2 represents delay due to internal energy storage of the gas turbine engine. T2 can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi-shaft engine, or with the compressibility of gas in the plenum of the free power turbine of an aero-derivative unit, for example. Typical value = 0,5.

URI

cim:GovGAST1.t2

Cardinality

0..1

Type

Seconds

t3

Turbine exhaust temperature time constant (T3) (>= 0). T3 represents delay in the exhaust temperature and load limiting system. Typical value = 3.

URI

cim:GovGAST1.t3

Cardinality

0..1

Type

Seconds

t4

Governor lead time constant (T4) (>= 0). Typical value = 0.

URI

cim:GovGAST1.t4

Cardinality

0..1

Type

Seconds

t5

Governor lag time constant (T5) (>= 0). If = 0, entire gain and lead-lag block is bypassed. Typical value = 0.

URI

cim:GovGAST1.t5

Cardinality

0..1

Type

Seconds

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

tltr

Valve position averaging time constant (Tltr) (>= 0). Typical value = 10.

URI

cim:GovGAST1.tltr

Cardinality

0..1

Type

Seconds

TurbineLoadControllerDynamics

Turbine load controller providing input to this turbine-governor.

URI

cim:TurbineGovernorDynamics.TurbineLoadControllerDynamics

Cardinality

0..1

Type

TurbineLoadControllerDynamics

Inherited from

TurbineGovernorDynamics

vmax

Maximum turbine power, PU of MWbase (Vmax) (> GovGAST1.vmin). Typical value = 1.

URI

cim:GovGAST1.vmax

Cardinality

0..1

Type

PU

vmin

Minimum turbine power, PU of MWbase (Vmin) (< GovGAST1.vmax). Typical value = 0.

URI

cim:GovGAST1.vmin

Cardinality

0..1

Type

PU