GovGAST1
Modified single shaft gas turbine.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Dataset containing the data objects. |
||
0..1 |
Turbine power time constant numerator scale factor (a). Typical value = 0,8. |
||
0..1 |
Turbine power time constant denominator scale factor (b) (>0). Typical value = 1. |
||
0..1 |
Intentional dead-band width (db1). Unit = Hz. Typical value = 0. |
||
0..1 |
Unintentional dead-band (db2). Unit = MW. Typical value = 0. |
||
0..1 |
Intentional db hysteresis (eps). Unit = Hz. Typical value = 0. |
||
0..1 |
Fuel flow at zero power output (Fidle). Typical value = 0,18. |
||
0..1 |
Nonlinear gain point 1, PU gv (Gv1). Typical value = 0. |
||
0..1 |
Nonlinear gain point 2,PU gv (Gv2). Typical value = 0. |
||
0..1 |
Nonlinear gain point 3, PU gv (Gv3). Typical value = 0. |
||
0..1 |
Nonlinear gain point 4, PU gv (Gv4). Typical value = 0. |
||
0..1 |
Nonlinear gain point 5, PU gv (Gv5). Typical value = 0. |
||
0..1 |
Nonlinear gain point 6, PU gv (Gv6). Typical value = 0. |
||
0..1 |
Governor gain (Ka). Typical value = 0. |
||
0..1 |
Temperature limiter gain (Kt). Typical value = 3. |
||
0..1 |
Ambient temperature load limit (Lmax). Lmax is the turbine power output corresponding to the limiting exhaust gas temperature. Typical value = 1. |
||
0..1 |
Valve position change allowed at fast rate (Loadinc). Typical value = 0,05. |
||
0..1 |
Maximum long term fuel valve opening rate (Ltrate). Typical value = 0,02. |
||
0..1 |
Base for power values (MWbase) (> 0). Unit = MW. |
||
0..1 |
Nonlinear gain point 1, PU power (Pgv1). Typical value = 0. |
||
0..1 |
Nonlinear gain point 2, PU power (Pgv2). Typical value = 0. |
||
0..1 |
Nonlinear gain point 3, PU power (Pgv3). Typical value = 0. |
||
0..1 |
Nonlinear gain point 4, PU power (Pgv4). Typical value = 0. |
||
0..1 |
Nonlinear gain point 5, PU power (Pgv5). Typical value = 0. |
||
0..1 |
Nonlinear gain point 6, PU power (Pgv6). Typical value = 0. |
||
0..1 |
Permanent droop (R) (>0). Typical value = 0,04. |
||
0..1 |
Maximum fuel valve opening rate (Rmax). Unit = PU / s. Typical value = 1. |
||
0..1 |
Governor mechanism time constant (T1) (>= 0). T1 represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical value = 0,5. |
||
0..1 |
Turbine power time constant (T2) (>= 0). T2 represents delay due to internal energy storage of the gas turbine engine. T2 can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi-shaft engine, or with the compressibility of gas in the plenum of the free power turbine of an aero-derivative unit, for example. Typical value = 0,5. |
||
0..1 |
Turbine exhaust temperature time constant (T3) (>= 0). T3 represents delay in the exhaust temperature and load limiting system. Typical value = 3. |
||
0..1 |
Governor lead time constant (T4) (>= 0). Typical value = 0. |
||
0..1 |
Governor lag time constant (T5) (>= 0). If = 0, entire gain and lead-lag block is bypassed. Typical value = 0. |
||
0..1 |
Valve position averaging time constant (Tltr) (>= 0). Typical value = 10. |
||
0..1 |
Maximum turbine power, PU of MWbase (Vmax) (> GovGAST1.vmin). Typical value = 1. |
||
0..1 |
Minimum turbine power, PU of MWbase (Vmin) (< GovGAST1.vmax). Typical value = 0. |
||
0..1 |
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
Turbine load controller providing input to this turbine-governor. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
a
Turbine power time constant numerator scale factor (a). Typical value = 0,8.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
b
Turbine power time constant denominator scale factor (b) (>0). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
db1
Intentional dead-band width (db1). Unit = Hz. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
db2
Unintentional dead-band (db2). Unit = MW. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
eps
Intentional db hysteresis (eps). Unit = Hz. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
fidle
Fuel flow at zero power output (Fidle). Typical value = 0,18.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv1
Nonlinear gain point 1, PU gv (Gv1). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv2
Nonlinear gain point 2,PU gv (Gv2). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv3
Nonlinear gain point 3, PU gv (Gv3). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv4
Nonlinear gain point 4, PU gv (Gv4). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv5
Nonlinear gain point 5, PU gv (Gv5). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
gv6
Nonlinear gain point 6, PU gv (Gv6). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
lmax
Ambient temperature load limit (Lmax). Lmax is the turbine power output corresponding to the limiting exhaust gas temperature. Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
loadinc
Valve position change allowed at fast rate (Loadinc). Typical value = 0,05.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
ltrate
Maximum long term fuel valve opening rate (Ltrate). Typical value = 0,02.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
mwbase
Base for power values (MWbase) (> 0). Unit = MW.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
pgv1
Nonlinear gain point 1, PU power (Pgv1). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv2
Nonlinear gain point 2, PU power (Pgv2). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv3
Nonlinear gain point 3, PU power (Pgv3). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv4
Nonlinear gain point 4, PU power (Pgv4). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv5
Nonlinear gain point 5, PU power (Pgv5). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pgv6
Nonlinear gain point 6, PU power (Pgv6). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
rmax
Maximum fuel valve opening rate (Rmax). Unit = PU / s. Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
SynchronousMachineDynamics
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
t1
Governor mechanism time constant (T1) (>= 0). T1 represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t2
Turbine power time constant (T2) (>= 0). T2 represents delay due to internal energy storage of the gas turbine engine. T2 can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi-shaft engine, or with the compressibility of gas in the plenum of the free power turbine of an aero-derivative unit, for example. Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t3
Turbine exhaust temperature time constant (T3) (>= 0). T3 represents delay in the exhaust temperature and load limiting system. Typical value = 3.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t4
Governor lead time constant (T4) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t5
Governor lag time constant (T5) (>= 0). If = 0, entire gain and lead-lag block is bypassed. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
tltr
Valve position averaging time constant (Tltr) (>= 0). Typical value = 10.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TurbineLoadControllerDynamics
Turbine load controller providing input to this turbine-governor.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
vmax
Maximum turbine power, PU of MWbase (Vmax) (> GovGAST1.vmin). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |