GovHydroFrancis

Detailed hydro unit - Francis model. This model can be used to represent three types of governors. A schematic of the hydraulic system of detailed hydro unit models, such as Francis and Pelton, is provided in the DetailedHydroModelHydraulicSystem diagram.

Type

Class

URI

cim:GovHydroFrancis

CIM standard (perspective)

IEC61970 (Grid)

Slots

Name Type Description Inherited from

am

0..1
PU

Opening section SEFF at the maximum efficiency (Am). Typical value = 0,7.

n/a

av0

0..1
Area

Area of the surge tank (AV0). Unit = m2. Typical value = 30.

n/a

av1

0..1
Area

Area of the compensation tank (AV1). Unit = m2. Typical value = 700.

n/a

bp

0..1
PU

Droop (Bp). Typical value = 0,05.

n/a

db1

0..1
Frequency

Intentional dead-band width (DB1). Unit = Hz. Typical value = 0.

n/a

etamax

0..1
PU

Maximum efficiency (EtaMax). Typical value = 1,05.

n/a

governorControl

0..1
FrancisGovernorControlKind

Governor control flag (Cflag). Typical value = mechanicHydrolicTachoAccelerator.

n/a

h1

0..1
Length

Head of compensation chamber water level with respect to the level of penstock (H1). Unit = km. ...

n/a

h2

0..1
Length

Head of surge tank water level with respect to the level of penstock (H2). Unit = km. Typical...

n/a

hn

0..1
Length

Rated hydraulic head (Hn). Unit = km. Typical value = 0,250.

n/a

kc

0..1
PU

Penstock loss coefficient (due to friction) (Kc). Typical value = 0,025.

n/a

kg

0..1
PU

Water tunnel and surge chamber loss coefficient (due to friction) (Kg). Typical value = 0,025.

n/a

kt

0..1
PU

Washout gain (Kt). Typical value = 0,25.

n/a

qc0

0..1
PU

No-load turbine flow at nominal head (Qc0). Typical value = 0,1.

n/a

qn

0..1
VolumeFlowRate

Rated flow (Qn). Unit = m3/s. Typical value = 250.

n/a

ta

0..1
Seconds

Derivative gain (Ta) (>= 0). Typical value = 3.

n/a

td

0..1
Seconds

Washout time constant (Td) (>= 0). Typical value = 6.

n/a

ts

0..1
Seconds

Gate servo time constant (Ts) (>= 0). Typical value = 0,5.

n/a

twnc

0..1
Seconds

Water inertia time constant (Twnc) (>= 0). Typical value = 1.

n/a

twng

0..1
Seconds

Water tunnel and surge chamber inertia time constant (Twng) (>= 0). Typical value = 3.

n/a

tx

0..1
Seconds

Derivative feedback gain (Tx) (>= 0). Typical value = 1.

n/a

va

0..1
float

Maximum gate opening velocity (Va). Unit = PU / s. Typical value = 0,06.

n/a

valvmax

0..1
PU

Maximum gate opening (ValvMax) (> GovHydroFrancis.valvmin). Typical value = 1,1.

n/a

valvmin

0..1
PU

Minimum gate opening (ValvMin) (< GovHydroFrancis.valvmax). Typical value = 0.

n/a

vc

0..1
float

Maximum gate closing velocity (Vc). Unit = PU / s. Typical value = -0,06.

n/a

waterTunnelSurgeChamberSimulation

0..1
boolean

Water tunnel and surge chamber simulation (Tflag). true = enable of water tunnel and surge chamber simulation false...

n/a

zsfc

0..1
Length

Head of upper water level with respect to the level of penstock (Zsfc). Unit = km. Typical value = 0,025.

n/a

AsynchronousMachineDynamics

0..1
AsynchronousMachineDynamics

Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either...

TurbineGovernorDynamics

SynchronousMachineDynamics

0..1
SynchronousMachineDynamics

Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an...

TurbineGovernorDynamics

TurbineLoadControllerDynamics

0..1
TurbineLoadControllerDynamics

Turbine load controller providing input to this turbine-governor.

TurbineGovernorDynamics

enabled

0..1
boolean

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

DynamicsFunctionBlock

DiagramObjects

0..*
DiagramObject

The diagram objects that are associated with the domain object.

IdentifiedObject

InstanceSet

1
InstanceSet

Dataset containing the data objects.

IdentifiedObject

Names

0..*
Name

All names of this identified object.

IdentifiedObject

PropertiesCIMDataObject

0..1
ChangeSetMember

The single CIM data object in the appropriate dataset context.

IdentifiedObject

TargetingCIMDataObject

0..*
ChangeSetMember

Data objects registered.

IdentifiedObject

aliasName

0..1
string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and...

IdentifiedObject

description

0..1
string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to...

IdentifiedObject

mRID

0..1
string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is...

IdentifiedObject

name

0..1
string

The name is any free human readable and possibly non unique text naming the object.

IdentifiedObject


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

am

Opening section SEFF at the maximum efficiency (Am). Typical value = 0,7.

URI

cim:GovHydroFrancis.am

Cardinality

0..1

Type

PU

AsynchronousMachineDynamics

Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

URI

cim:TurbineGovernorDynamics.AsynchronousMachineDynamics

Cardinality

0..1

Type

AsynchronousMachineDynamics

Inherited from

TurbineGovernorDynamics

av0

Area of the surge tank (AV0). Unit = m2. Typical value = 30.

URI

cim:GovHydroFrancis.av0

Cardinality

0..1

Type

Area

av1

Area of the compensation tank (AV1). Unit = m2. Typical value = 700.

URI

cim:GovHydroFrancis.av1

Cardinality

0..1

Type

Area

bp

Droop (Bp). Typical value = 0,05.

URI

cim:GovHydroFrancis.bp

Cardinality

0..1

Type

PU

db1

Intentional dead-band width (DB1). Unit = Hz. Typical value = 0.

URI

cim:GovHydroFrancis.db1

Cardinality

0..1

Type

Frequency

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

URI

cim:DynamicsFunctionBlock.enabled

Cardinality

0..1

Type

boolean

Inherited from

DynamicsFunctionBlock

etamax

Maximum efficiency (EtaMax). Typical value = 1,05.

URI

cim:GovHydroFrancis.etamax

Cardinality

0..1

Type

PU

governorControl

Governor control flag (Cflag). Typical value = mechanicHydrolicTachoAccelerator.

URI

cim:GovHydroFrancis.governorControl

Cardinality

0..1

Type

FrancisGovernorControlKind

h1

Head of compensation chamber water level with respect to the level of penstock (H1). Unit = km. Typical value = 0,004.

URI

cim:GovHydroFrancis.h1

Cardinality

0..1

Type

Length

h2

Head of surge tank water level with respect to the level of penstock (H2). Unit = km. Typical value = 0,040.

URI

cim:GovHydroFrancis.h2

Cardinality

0..1

Type

Length

hn

Rated hydraulic head (Hn). Unit = km. Typical value = 0,250.

URI

cim:GovHydroFrancis.hn

Cardinality

0..1

Type

Length

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

kc

Penstock loss coefficient (due to friction) (Kc). Typical value = 0,025.

URI

cim:GovHydroFrancis.kc

Cardinality

0..1

Type

PU

kg

Water tunnel and surge chamber loss coefficient (due to friction) (Kg). Typical value = 0,025.

URI

cim:GovHydroFrancis.kg

Cardinality

0..1

Type

PU

kt

Washout gain (Kt). Typical value = 0,25.

URI

cim:GovHydroFrancis.kt

Cardinality

0..1

Type

PU

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

qc0

No-load turbine flow at nominal head (Qc0). Typical value = 0,1.

URI

cim:GovHydroFrancis.qc0

Cardinality

0..1

Type

PU

qn

Rated flow (Qn). Unit = m3/s. Typical value = 250.

URI

cim:GovHydroFrancis.qn

Cardinality

0..1

Type

VolumeFlowRate

SynchronousMachineDynamics

Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

URI

cim:TurbineGovernorDynamics.SynchronousMachineDynamics

Cardinality

0..1

Type

SynchronousMachineDynamics

Inherited from

TurbineGovernorDynamics

ta

Derivative gain (Ta) (>= 0). Typical value = 3.

URI

cim:GovHydroFrancis.ta

Cardinality

0..1

Type

Seconds

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

td

Washout time constant (Td) (>= 0). Typical value = 6.

URI

cim:GovHydroFrancis.td

Cardinality

0..1

Type

Seconds

ts

Gate servo time constant (Ts) (>= 0). Typical value = 0,5.

URI

cim:GovHydroFrancis.ts

Cardinality

0..1

Type

Seconds

TurbineLoadControllerDynamics

Turbine load controller providing input to this turbine-governor.

URI

cim:TurbineGovernorDynamics.TurbineLoadControllerDynamics

Cardinality

0..1

Type

TurbineLoadControllerDynamics

Inherited from

TurbineGovernorDynamics

twnc

Water inertia time constant (Twnc) (>= 0). Typical value = 1.

URI

cim:GovHydroFrancis.twnc

Cardinality

0..1

Type

Seconds

twng

Water tunnel and surge chamber inertia time constant (Twng) (>= 0). Typical value = 3.

URI

cim:GovHydroFrancis.twng

Cardinality

0..1

Type

Seconds

tx

Derivative feedback gain (Tx) (>= 0). Typical value = 1.

URI

cim:GovHydroFrancis.tx

Cardinality

0..1

Type

Seconds

va

Maximum gate opening velocity (Va). Unit = PU / s. Typical value = 0,06.

URI

cim:GovHydroFrancis.va

Cardinality

0..1

Type

float

valvmax

Maximum gate opening (ValvMax) (> GovHydroFrancis.valvmin). Typical value = 1,1.

URI

cim:GovHydroFrancis.valvmax

Cardinality

0..1

Type

PU

valvmin

Minimum gate opening (ValvMin) (< GovHydroFrancis.valvmax). Typical value = 0.

URI

cim:GovHydroFrancis.valvmin

Cardinality

0..1

Type

PU

vc

Maximum gate closing velocity (Vc). Unit = PU / s. Typical value = -0,06.

URI

cim:GovHydroFrancis.vc

Cardinality

0..1

Type

float

waterTunnelSurgeChamberSimulation

Water tunnel and surge chamber simulation (Tflag). true = enable of water tunnel and surge chamber simulation false = inhibit of water tunnel and surge chamber simulation. Typical value = false.

URI

cim:GovHydroFrancis.waterTunnelSurgeChamberSimulation

Cardinality

0..1

Type

boolean

zsfc

Head of upper water level with respect to the level of penstock (Zsfc). Unit = km. Typical value = 0,025.

URI

cim:GovHydroFrancis.zsfc

Cardinality

0..1

Type

Length

Used by

This class is not used by any other classes as the range of a slot.