Quality61850

Quality flags in this class are as defined in IEC 61850, except for estimatorReplaced, which has been included in this class for convenience.

Type

Class

URI

cim:Quality61850

CIM standard (perspective)

IEC61970 (Grid)

Class hierarchy

Slots

Name Cardinality Type Description

badReference

0..1

boolean

Measurement value may be incorrect due to a reference being out of calibration.

estimatorReplaced

0..1

boolean

Value has been replaced by State Estimator. estimatorReplaced is not an IEC61850 quality bit but has been put in this class for convenience.

failure

0..1

boolean

This identifier indicates that a supervision function has detected an internal or external failure, e.g. communication failure.

oldData

0..1

boolean

Measurement value is old and possibly invalid, as it has not been successfully updated during a specified time interval.

operatorBlocked

0..1

boolean

Measurement value is blocked and hence unavailable for transmission.

oscillatory

0..1

boolean

To prevent some overload of the communication it is sensible to detect and suppress oscillating (fast changing) binary inputs. If a signal changes in a defined time twice in the same direction (from 0 to 1 or from 1 to 0) then oscillation is detected and the detail quality identifier "oscillatory" is set. If it is detected a configured numbers of transient changes could be passed by. In this time the validity status "questionable" is set. If after this defined numbers of changes the signal is still in the oscillating state the value shall be set either to the opposite state of the previous stable value or to a defined default value. In this case the validity status "questionable" is reset and "invalid" is set as long as the signal is oscillating. If it is configured such that no transient changes should be passed by then the validity status "invalid" is set immediately in addition to the detail quality identifier "oscillatory" (used for status information only).

outOfRange

0..1

boolean

Measurement value is beyond a predefined range of value.

overFlow

0..1

boolean

Measurement value is beyond the capability of being represented properly. For example, a counter value overflows from maximum count back to a value of zero.

source

0..1

Source

Source gives information related to the origin of a value. The value may be acquired from the process, defaulted or substituted.

suspect

0..1

boolean

A correlation function has detected that the value is not consistent with other values. Typically set by a network State Estimator.

test

0..1

boolean

Measurement value is transmitted for test purposes.

validity

0..1

Validity

Validity of the measurement value.


badReference

Measurement value may be incorrect due to a reference being out of calibration.

URI

cim:Quality61850.badReference

Cardinality

0..1

Type

boolean

estimatorReplaced

Value has been replaced by State Estimator. estimatorReplaced is not an IEC61850 quality bit but has been put in this class for convenience.

URI

cim:Quality61850.estimatorReplaced

Cardinality

0..1

Type

boolean

failure

This identifier indicates that a supervision function has detected an internal or external failure, e.g. communication failure.

URI

cim:Quality61850.failure

Cardinality

0..1

Type

boolean

oldData

Measurement value is old and possibly invalid, as it has not been successfully updated during a specified time interval.

URI

cim:Quality61850.oldData

Cardinality

0..1

Type

boolean

operatorBlocked

Measurement value is blocked and hence unavailable for transmission.

URI

cim:Quality61850.operatorBlocked

Cardinality

0..1

Type

boolean

oscillatory

To prevent some overload of the communication it is sensible to detect and suppress oscillating (fast changing) binary inputs. If a signal changes in a defined time twice in the same direction (from 0 to 1 or from 1 to 0) then oscillation is detected and the detail quality identifier "oscillatory" is set. If it is detected a configured numbers of transient changes could be passed by. In this time the validity status "questionable" is set. If after this defined numbers of changes the signal is still in the oscillating state the value shall be set either to the opposite state of the previous stable value or to a defined default value. In this case the validity status "questionable" is reset and "invalid" is set as long as the signal is oscillating. If it is configured such that no transient changes should be passed by then the validity status "invalid" is set immediately in addition to the detail quality identifier "oscillatory" (used for status information only).

URI

cim:Quality61850.oscillatory

Cardinality

0..1

Type

boolean

outOfRange

Measurement value is beyond a predefined range of value.

URI

cim:Quality61850.outOfRange

Cardinality

0..1

Type

boolean

overFlow

Measurement value is beyond the capability of being represented properly. For example, a counter value overflows from maximum count back to a value of zero.

URI

cim:Quality61850.overFlow

Cardinality

0..1

Type

boolean

source

Source gives information related to the origin of a value. The value may be acquired from the process, defaulted or substituted.

URI

cim:Quality61850.source

Cardinality

0..1

Type

Source

suspect

A correlation function has detected that the value is not consistent with other values. Typically set by a network State Estimator.

URI

cim:Quality61850.suspect

Cardinality

0..1

Type

boolean

test

Measurement value is transmitted for test purposes.

URI

cim:Quality61850.test

Cardinality

0..1

Type

boolean

validity

Validity of the measurement value.

URI

cim:Quality61850.validity

Cardinality

0..1

Type

Validity