GovSteamFV4
Detailed electro-hydraulic governor for steam unit.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Dataset containing the data objects. |
||
0..1 |
Minimum value of pressure regulator output (Cpsmn). Typical value = -1. |
||
0..1 |
Maximum value of pressure regulator output (Cpsmx). Typical value = 1. |
||
0..1 |
Minimum value of regulator set-point (Crmn). Typical value = 0. |
||
0..1 |
Maximum value of regulator set-point (Crmx). Typical value = 1,2. |
||
0..1 |
Derivative gain of pressure regulator (Kdc). Typical value = 1. |
||
0..1 |
Frequency bias (reciprocal of droop) (Kf1). Typical value = 20. |
||
0..1 |
Frequency control (reciprocal of droop) (Kf3). Typical value = 20. |
||
0..1 |
Fraction of total turbine output generated by HP part (Khp). Typical value = 0,35. |
||
0..1 |
Integral gain of pressure regulator (Kic). Typical value = 0,0033. |
||
0..1 |
Integral gain of pressure feedback regulator (Kip). Typical value = 0,5. |
||
0..1 |
Integral gain of electro-hydraulic regulator (Kit). Typical value = 0,04. |
||
0..1 |
First gain coefficient of intercept valves characteristic (Kmp1). Typical value = 0,5. |
||
0..1 |
Second gain coefficient of intercept valves characteristic (Kmp2). Typical value = 3,5. |
||
0..1 |
Proportional gain of pressure regulator (Kpc). Typical value = 0,5. |
||
0..1 |
Proportional gain of pressure feedback regulator (Kpp). Typical value = 1. |
||
0..1 |
Proportional gain of electro-hydraulic regulator (Kpt). Typical value = 0,3. |
||
0..1 |
Maximum variation of fuel flow (Krc). Typical value = 0,05. |
||
0..1 |
Pressure loss due to flow friction in the boiler tubes (Ksh). Typical value = 0,08. |
||
0..1 |
Maximum negative power error (Lpi). Typical value = -0,15. |
||
0..1 |
Maximum positive power error (Lps). Typical value = 0,03. |
||
0..1 |
Lower limit for frequency correction (MNEF). Typical value = -0,05. |
||
0..1 |
Upper limit for frequency correction (MXEF). Typical value = 0,05. |
||
0..1 |
First value of pressure set point static characteristic (Pr1). Typical value = 0,2. |
||
0..1 |
Second value of pressure set point static characteristic, corresponding to Ps0 = 1,0 PU (Pr2). Typical value = 0,75. |
||
0..1 |
Minimum value of pressure set point static characteristic (Psmn). Typical value = 1. |
||
0..1 |
Minimum value of integral regulator (Rsmimn). Typical value = 0. |
||
0..1 |
Maximum value of integral regulator (Rsmimx). Typical value = 1,1. |
||
0..1 |
Minimum value of integral regulator (Rvgmn). Typical value = 0. |
||
0..1 |
Maximum value of integral regulator (Rvgmx). Typical value = 1,2. |
||
0..1 |
Minimum valve opening (Srmn). Typical value = 0. |
||
0..1 |
Maximum valve opening (Srmx). Typical value = 1,1. |
||
0..1 |
Intercept valves characteristic discontinuity point (Srsmp). Typical value = 0,43. |
||
0..1 |
Maximum regulator gate closing velocity (Svmn). Typical value = -0,0333. |
||
0..1 |
Maximum regulator gate opening velocity (Svmx). Typical value = 0,0333. |
||
0..1 |
Control valves rate opening time (Ta) (>= 0). Typical value = 0,8. |
||
0..1 |
Intercept valves rate opening time (Tam) (>= 0). Typical value = 0,8. |
||
0..1 |
Control valves rate closing time (Tc) (>= 0). Typical value = 0,5. |
||
0..1 |
Intercept valves rate closing time (Tcm) (>= 0). Typical value = 0,5. |
||
0..1 |
Derivative time constant of pressure regulator (Tdc) (>= 0). Typical value = 90. |
||
0..1 |
Time constant of fuel regulation (Tf1) (>= 0). Typical value = 10. |
||
0..1 |
Time constant of steam chest (Tf2) (>= 0). Typical value = 10. |
||
0..1 |
High pressure (HP) time constant of the turbine (Thp) (>= 0). Typical value = 0,15. |
||
0..1 |
Low pressure (LP) time constant of the turbine (Tmp) (>= 0). Typical value = 0,4. |
||
0..1 |
Reheater time constant of the turbine (Trh) (>= 0). Typical value = 10. |
||
0..1 |
Boiler time constant (Tv) (>= 0). Typical value = 60. |
||
0..1 |
Control valves servo time constant (Ty) (>= 0). Typical value = 0,1. |
||
0..1 |
Coefficient of linearized equations of turbine (Stodola formulation) (Y). Typical value = 0,13. |
||
0..1 |
Minimum control valve position (Yhpmn). Typical value = 0. |
||
0..1 |
Maximum control valve position (Yhpmx). Typical value = 1,1. |
||
0..1 |
Minimum intercept valve position (Ympmn). Typical value = 0. |
||
0..1 |
Maximum intercept valve position (Ympmx). Typical value = 1,1. |
||
0..1 |
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
Turbine load controller providing input to this turbine-governor. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
cpsmn
Minimum value of pressure regulator output (Cpsmn). Typical value = -1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
cpsmx
Maximum value of pressure regulator output (Cpsmx). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
crmn
Minimum value of regulator set-point (Crmn). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
crmx
Maximum value of regulator set-point (Crmx). Typical value = 1,2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
kdc
Derivative gain of pressure regulator (Kdc). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kf1
Frequency bias (reciprocal of droop) (Kf1). Typical value = 20.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kf3
Frequency control (reciprocal of droop) (Kf3). Typical value = 20.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
khp
Fraction of total turbine output generated by HP part (Khp). Typical value = 0,35.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kic
Integral gain of pressure regulator (Kic). Typical value = 0,0033.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kip
Integral gain of pressure feedback regulator (Kip). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kit
Integral gain of electro-hydraulic regulator (Kit). Typical value = 0,04.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kmp1
First gain coefficient of intercept valves characteristic (Kmp1). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kmp2
Second gain coefficient of intercept valves characteristic (Kmp2). Typical value = 3,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kpc
Proportional gain of pressure regulator (Kpc). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kpp
Proportional gain of pressure feedback regulator (Kpp). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kpt
Proportional gain of electro-hydraulic regulator (Kpt). Typical value = 0,3.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
krc
Maximum variation of fuel flow (Krc). Typical value = 0,05.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
ksh
Pressure loss due to flow friction in the boiler tubes (Ksh). Typical value = 0,08.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
lpi
Maximum negative power error (Lpi). Typical value = -0,15.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
lps
Maximum positive power error (Lps). Typical value = 0,03.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mnef
Lower limit for frequency correction (MNEF). Typical value = -0,05.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
mxef
Upper limit for frequency correction (MXEF). Typical value = 0,05.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
pr1
First value of pressure set point static characteristic (Pr1). Typical value = 0,2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pr2
Second value of pressure set point static characteristic, corresponding to Ps0 = 1,0 PU (Pr2). Typical value = 0,75.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
psmn
Minimum value of pressure set point static characteristic (Psmn). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
rsmimn
Minimum value of integral regulator (Rsmimn). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
rsmimx
Maximum value of integral regulator (Rsmimx). Typical value = 1,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
rvgmn
Minimum value of integral regulator (Rvgmn). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
rvgmx
Maximum value of integral regulator (Rvgmx). Typical value = 1,2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
srmn
Minimum valve opening (Srmn). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
srmx
Maximum valve opening (Srmx). Typical value = 1,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
srsmp
Intercept valves characteristic discontinuity point (Srsmp). Typical value = 0,43.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
svmn
Maximum regulator gate closing velocity (Svmn). Typical value = -0,0333.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
svmx
Maximum regulator gate opening velocity (Svmx). Typical value = 0,0333.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
SynchronousMachineDynamics
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
ta
Control valves rate opening time (Ta) (>= 0). Typical value = 0,8.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tam
Intercept valves rate opening time (Tam) (>= 0). Typical value = 0,8.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
tc
Control valves rate closing time (Tc) (>= 0). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tcm
Intercept valves rate closing time (Tcm) (>= 0). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tdc
Derivative time constant of pressure regulator (Tdc) (>= 0). Typical value = 90.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tf1
Time constant of fuel regulation (Tf1) (>= 0). Typical value = 10.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tf2
Time constant of steam chest (Tf2) (>= 0). Typical value = 10.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
thp
High pressure (HP) time constant of the turbine (Thp) (>= 0). Typical value = 0,15.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tmp
Low pressure (LP) time constant of the turbine (Tmp) (>= 0). Typical value = 0,4.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
trh
Reheater time constant of the turbine (Trh) (>= 0). Typical value = 10.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TurbineLoadControllerDynamics
Turbine load controller providing input to this turbine-governor.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
tv
Boiler time constant (Tv) (>= 0). Typical value = 60.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
ty
Control valves servo time constant (Ty) (>= 0). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
y
Coefficient of linearized equations of turbine (Stodola formulation) (Y). Typical value = 0,13.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
yhpmn
Minimum control valve position (Yhpmn). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
yhpmx
Maximum control valve position (Yhpmx). Typical value = 1,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
ympmn
Minimum intercept valve position (Ympmn). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |