ExcIEEEST3A
IEEE 421.5-2005 type ST3A model. Some static systems utilize a field voltage control loop to linearize the exciter control characteristic. This also makes the output independent of supply source variations until supply limitations are reached. These systems utilize a variety of controlled-rectifier designs: full thyristor complements or hybrid bridges in either series or shunt configurations. The power source can consist of only a potential source, either fed from the machine terminals or from internal windings. Some designs can have compound power sources utilizing both machine potential and current. These power sources are represented as phasor combinations of machine terminal current and voltage and are accommodated by suitable parameters in model type ST3A which is represented by ExcIEEEST3A. Reference: IEEE 421.5-2005, 7.3.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Dataset containing the data objects. |
||
1 |
Synchronous machine model with which this excitation system model is associated. |
||
1 |
Voltage compensator model associated with this excitation system model. |
||
0..1 |
Voltage regulator gain (KA) (> 0). This is parameter K in the IEEE standard. Typical value = 200. |
||
0..1 |
Rectifier loading factor proportional to commutating reactance (KC) (>= 0). Typical value = 0,2. |
||
0..1 |
Feedback gain constant of the inner loop field regulator (KG) (>= 0). Typical value = 1. |
||
0..1 |
Potential circuit gain coefficient (KI) (>= 0). Typical value = 0. |
||
0..1 |
Forward gain constant of the inner loop field regulator (KM) (> 0). Typical value = 7,93. |
||
0..1 |
Potential circuit gain coefficient (KP) (> 0). Typical value = 6,15. |
||
0..1 |
Voltage regulator time constant (TA) (>= 0). Typical value = 0. |
||
0..1 |
Voltage regulator time constant (TB) (>= 0). Typical value = 10. |
||
0..1 |
Voltage regulator time constant (TC) (>= 0). Typical value = 1. |
||
0..1 |
Potential circuit phase angle (thetap). Typical value = 0. |
||
0..1 |
Forward time constant of inner loop field regulator (TM) (> 0). Typical value = 0,4. |
||
0..1 |
Maximum excitation voltage (VBMax) (> 0). Typical value = 6,9. |
||
0..1 |
Maximum inner loop feedback voltage (VGMax) (>= 0). Typical value = 5,8. |
||
0..1 |
Maximum voltage regulator input limit (VIMAX) (> 0). Typical value = 0,2. |
||
0..1 |
Minimum voltage regulator input limit (VIMIN) (< 0). Typical value = -0,2. |
||
0..1 |
Maximum inner loop output (VMMax) (> 0). Typical value = 1. |
||
0..1 |
Minimum inner loop output (VMMin) (<= 0). Typical value = 0. |
||
0..1 |
Maximum voltage regulator output (VRMAX) (> 0). Typical value = 10. |
||
0..1 |
Minimum voltage regulator output (VRMIN) (< 0). Typical value = -10. |
||
0..1 |
Reactance associated with potential source (XL) (>= 0). Typical value = 0,081. |
||
0..1 |
Discontinuous excitation control model associated with this excitation system model. |
||
0..1 |
Overexcitation limiter model associated with this excitation system model. |
||
0..1 |
Power factor or VAr controller type 1 model associated with this excitation system model. |
||
0..1 |
Power factor or VAr controller type 2 model associated with this excitation system model. |
||
0..1 |
Power system stabilizer model associated with this excitation system model. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
Undrexcitation limiter model associated with this excitation system model. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
DiscontinuousExcitationControlDynamics
Discontinuous excitation control model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
ka
Voltage regulator gain (KA) (> 0). This is parameter K in the IEEE standard. Typical value = 200.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kc
Rectifier loading factor proportional to commutating reactance (KC) (>= 0). Typical value = 0,2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kg
Feedback gain constant of the inner loop field regulator (KG) (>= 0). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
ki
Potential circuit gain coefficient (KI) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
km
Forward gain constant of the inner loop field regulator (KM) (> 0). Typical value = 7,93.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kp
Potential circuit gain coefficient (KP) (> 0). Typical value = 6,15.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
OverexcitationLimiterDynamics
Overexcitation limiter model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
PFVArControllerType1Dynamics
Power factor or VAr controller type 1 model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
PFVArControllerType2Dynamics
Power factor or VAr controller type 2 model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
PowerSystemStabilizerDynamics
Power system stabilizer model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
SynchronousMachineDynamics
Synchronous machine model with which this excitation system model is associated.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
ta
Voltage regulator time constant (TA) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
tb
Voltage regulator time constant (TB) (>= 0). Typical value = 10.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tc
Voltage regulator time constant (TC) (>= 0). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
thetap
Potential circuit phase angle (thetap). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tm
Forward time constant of inner loop field regulator (TM) (> 0). Typical value = 0,4.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
UnderexcitationLimiterDynamics
Undrexcitation limiter model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
vbmax
Maximum excitation voltage (VBMax) (> 0). Typical value = 6,9.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vgmax
Maximum inner loop feedback voltage (VGMax) (>= 0). Typical value = 5,8.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vimax
Maximum voltage regulator input limit (VIMAX) (> 0). Typical value = 0,2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vimin
Minimum voltage regulator input limit (VIMIN) (< 0). Typical value = -0,2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vmmax
Maximum inner loop output (VMMax) (> 0). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vmmin
Minimum inner loop output (VMMin) (<= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
VoltageCompensatorDynamics
Voltage compensator model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
vrmax
Maximum voltage regulator output (VRMAX) (> 0). Typical value = 10.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vrmin
Minimum voltage regulator output (VRMIN) (< 0). Typical value = -10.
URI |
|
---|---|
Cardinality |
0..1 |
Type |