GovHydroPelton
Detailed hydro unit - Pelton model. This model can be used to represent the dynamic related to water tunnel and surge chamber. The DetailedHydroModelHydraulicSystem diagram, located under the GovHydroFrancis class, provides a schematic of the hydraulic system of detailed hydro unit models, such as Francis and Pelton.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Dataset containing the data objects. |
||
0..1 |
Area of the surge tank (AV0). Unit = m2. Typical value = 30. |
||
0..1 |
Area of the compensation tank (AV1). Unit = m2. Typical value = 700. |
||
0..1 |
Droop (bp). Typical value = 0,05. |
||
0..1 |
Intentional dead-band width (DB1). Unit = Hz. Typical value = 0. |
||
0..1 |
Intentional dead-band width of valve opening error (DB2). Unit = Hz. Typical value = 0,01. |
||
0..1 |
Head of compensation chamber water level with respect to the level of penstock (H1). Unit = km. Typical value = 0,004. |
||
0..1 |
Head of surge tank water level with respect to the level of penstock (H2). Unit = km. Typical value = 0,040. |
||
0..1 |
Rated hydraulic head (Hn). Unit = km. Typical value = 0,250. |
||
0..1 |
Penstock loss coefficient (due to friction) (Kc). Typical value = 0,025. |
||
0..1 |
Water tunnel and surge chamber loss coefficient (due to friction) (Kg). Typical value = 0,025. |
||
0..1 |
No-load turbine flow at nominal head (Qc0). Typical value = 0,05. |
||
0..1 |
Rated flow (Qn). Unit = m3/s. Typical value = 250. |
||
0..1 |
Simplified Pelton model simulation (Sflag). true = enable of simplified Pelton model simulation false = enable of complete Pelton model simulation (non-linear gain). Typical value = true. |
||
0..1 |
Static compensating characteristic (Cflag). It should be true if simplifiedPelton = false. true = enable of static compensating characteristic false = inhibit of static compensating characteristic. Typical value = false. |
||
0..1 |
Derivative gain (accelerometer time constant) (Ta) (>= 0). Typical value = 3. |
||
0..1 |
Gate servo time constant (Ts) (>= 0). Typical value = 0,15. |
||
0..1 |
Servomotor integrator time constant (Tv) (>= 0). Typical value = 0,3. |
||
0..1 |
Water inertia time constant (Twnc) (>= 0). Typical value = 1. |
||
0..1 |
Water tunnel and surge chamber inertia time constant (Twng) (>= 0). Typical value = 3. |
||
0..1 |
Electronic integrator time constant (Tx) (>= 0). Typical value = 0,5. |
||
0..1 |
Maximum gate opening velocity (Va). Unit = PU / s. Typical value = 0,06. |
||
0..1 |
Maximum gate opening (ValvMax) (> GovHydroPelton.valvmin). Typical value = 1,1. |
||
0..1 |
Minimum gate opening (ValvMin) (< GovHydroPelton.valvmax). Typical value = 0. |
||
0..1 |
Maximum servomotor valve opening velocity (Vav). Typical value = 0,1. |
||
0..1 |
Maximum gate closing velocity (Vc). Unit = PU / s. Typical value = -0,06. |
||
0..1 |
Maximum servomotor valve closing velocity (Vcv). Typical value = -0,1. |
||
0..1 |
Water tunnel and surge chamber simulation (Tflag). true = enable of water tunnel and surge chamber simulation false = inhibit of water tunnel and surge chamber simulation. Typical value = false. |
||
0..1 |
Head of upper water level with respect to the level of penstock (Zsfc). Unit = km. Typical value = 0,025. |
||
0..1 |
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
Turbine load controller providing input to this turbine-governor. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
av0
Area of the surge tank (AV0). Unit = m2. Typical value = 30.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
av1
Area of the compensation tank (AV1). Unit = m2. Typical value = 700.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
db1
Intentional dead-band width (DB1). Unit = Hz. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
db2
Intentional dead-band width of valve opening error (DB2). Unit = Hz. Typical value = 0,01.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
h1
Head of compensation chamber water level with respect to the level of penstock (H1). Unit = km. Typical value = 0,004.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
h2
Head of surge tank water level with respect to the level of penstock (H2). Unit = km. Typical value = 0,040.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
hn
Rated hydraulic head (Hn). Unit = km. Typical value = 0,250.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
kc
Penstock loss coefficient (due to friction) (Kc). Typical value = 0,025.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kg
Water tunnel and surge chamber loss coefficient (due to friction) (Kg). Typical value = 0,025.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
qc0
No-load turbine flow at nominal head (Qc0). Typical value = 0,05.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
qn
Rated flow (Qn). Unit = m3/s. Typical value = 250.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
simplifiedPelton
Simplified Pelton model simulation (Sflag). true = enable of simplified Pelton model simulation false = enable of complete Pelton model simulation (non-linear gain). Typical value = true.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
staticCompensating
Static compensating characteristic (Cflag). It should be true if simplifiedPelton = false. true = enable of static compensating characteristic false = inhibit of static compensating characteristic. Typical value = false.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
SynchronousMachineDynamics
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
ta
Derivative gain (accelerometer time constant) (Ta) (>= 0). Typical value = 3.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
ts
Gate servo time constant (Ts) (>= 0). Typical value = 0,15.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TurbineLoadControllerDynamics
Turbine load controller providing input to this turbine-governor.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
tv
Servomotor integrator time constant (Tv) (>= 0). Typical value = 0,3.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
twnc
Water inertia time constant (Twnc) (>= 0). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
twng
Water tunnel and surge chamber inertia time constant (Twng) (>= 0). Typical value = 3.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tx
Electronic integrator time constant (Tx) (>= 0). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
va
Maximum gate opening velocity (Va). Unit = PU / s. Typical value = 0,06.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
valvmax
Maximum gate opening (ValvMax) (> GovHydroPelton.valvmin). Typical value = 1,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
valvmin
Minimum gate opening (ValvMin) (< GovHydroPelton.valvmax). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vav
Maximum servomotor valve opening velocity (Vav). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vc
Maximum gate closing velocity (Vc). Unit = PU / s. Typical value = -0,06.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vcv
Maximum servomotor valve closing velocity (Vcv). Typical value = -0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
waterTunnelSurgeChamberSimulation
Water tunnel and surge chamber simulation (Tflag). true = enable of water tunnel and surge chamber simulation false = inhibit of water tunnel and surge chamber simulation. Typical value = false.
URI |
|
---|---|
Cardinality |
0..1 |
Type |