PssIEEE3B

IEEE 421.5-2005 type PSS3B power system stabilizer model. The PSS model PSS3B has dual inputs of electrical power and rotor angular frequency deviation. The signals are used to derive an equivalent mechanical power signal. This model has 2 input signals. They have the following fixed types (expressed in terms of InputSignalKind values): the first one is of rotorAngleFrequencyDeviation type and the second one is of generatorElectricalPower type. Reference: IEEE 3B 421.5-2005, 8.3.

Type

Class

URI

cim:PssIEEE3B

CIM standard (perspective)

IEC61970 (Grid)

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

ExcitationSystemDynamics

1

ExcitationSystemDynamics

Excitation system model with which this power system stabilizer model is associated.

InstanceSet

1

InstanceSet

Dataset containing the data objects.

a1

0..1

PU

Notch filter parameter (A1). Typical value = 0,359.

a2

0..1

PU

Notch filter parameter (A2). Typical value = 0,586.

a3

0..1

PU

Notch filter parameter (A3). Typical value = 0,429.

a4

0..1

PU

Notch filter parameter (A4). Typical value = 0,564.

a5

0..1

PU

Notch filter parameter (A5). Typical value = 0,001.

a6

0..1

PU

Notch filter parameter (A6). Typical value = 0.

a7

0..1

PU

Notch filter parameter (A7). Typical value = 0,031.

a8

0..1

PU

Notch filter parameter (A8). Typical value = 0.

ks1

0..1

PU

Gain on signal # 1 (Ks1). Typical value = -0,602.

ks2

0..1

PU

Gain on signal # 2 (Ks2). Typical value = 30,12.

t1

0..1

Seconds

Transducer time constant (T1) (>= 0). Typical value = 0,012.

t2

0..1

Seconds

Transducer time constant (T2) (>= 0). Typical value = 0,012.

tw1

0..1

Seconds

Washout time constant (Tw1) (>= 0). Typical value = 0,3.

tw2

0..1

Seconds

Washout time constant (Tw2) (>= 0). Typical value = 0,3.

tw3

0..1

Seconds

Washout time constant (Tw3) (>= 0). Typical value = 0,6.

vstmax

0..1

PU

Stabilizer output maximum limit (Vstmax) (> PssIEEE3B.vstmin). Typical value = 0,1.

vstmin

0..1

PU

Stabilizer output minimum limit (Vstmin) (< PssIEEE3B.vstmax). Typical value = -0,1.

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

enabled

0..1

boolean

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

RemoteInputSignal

0..*

RemoteInputSignal

Remote input signal used by this power system stabilizer model.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


a1

Notch filter parameter (A1). Typical value = 0,359.

URI

cim:PssIEEE3B.a1

Cardinality

0..1

Type

PU

a2

Notch filter parameter (A2). Typical value = 0,586.

URI

cim:PssIEEE3B.a2

Cardinality

0..1

Type

PU

a3

Notch filter parameter (A3). Typical value = 0,429.

URI

cim:PssIEEE3B.a3

Cardinality

0..1

Type

PU

a4

Notch filter parameter (A4). Typical value = 0,564.

URI

cim:PssIEEE3B.a4

Cardinality

0..1

Type

PU

a5

Notch filter parameter (A5). Typical value = 0,001.

URI

cim:PssIEEE3B.a5

Cardinality

0..1

Type

PU

a6

Notch filter parameter (A6). Typical value = 0.

URI

cim:PssIEEE3B.a6

Cardinality

0..1

Type

PU

a7

Notch filter parameter (A7). Typical value = 0,031.

URI

cim:PssIEEE3B.a7

Cardinality

0..1

Type

PU

a8

Notch filter parameter (A8). Typical value = 0.

URI

cim:PssIEEE3B.a8

Cardinality

0..1

Type

PU

aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

URI

cim:DynamicsFunctionBlock.enabled

Cardinality

0..1

Type

boolean

Inherited from

DynamicsFunctionBlock

ExcitationSystemDynamics

Excitation system model with which this power system stabilizer model is associated.

URI

cim:PowerSystemStabilizerDynamics.ExcitationSystemDynamics

Cardinality

1

Type

ExcitationSystemDynamics

Inherited from

PowerSystemStabilizerDynamics

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

ks1

Gain on signal # 1 (Ks1). Typical value = -0,602.

URI

cim:PssIEEE3B.ks1

Cardinality

0..1

Type

PU

ks2

Gain on signal # 2 (Ks2). Typical value = 30,12.

URI

cim:PssIEEE3B.ks2

Cardinality

0..1

Type

PU

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

RemoteInputSignal

Remote input signal used by this power system stabilizer model.

URI

cim:PowerSystemStabilizerDynamics.RemoteInputSignal

Cardinality

0..*

Type

RemoteInputSignal

Inherited from

PowerSystemStabilizerDynamics

t1

Transducer time constant (T1) (>= 0). Typical value = 0,012.

URI

cim:PssIEEE3B.t1

Cardinality

0..1

Type

Seconds

t2

Transducer time constant (T2) (>= 0). Typical value = 0,012.

URI

cim:PssIEEE3B.t2

Cardinality

0..1

Type

Seconds

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

tw1

Washout time constant (Tw1) (>= 0). Typical value = 0,3.

URI

cim:PssIEEE3B.tw1

Cardinality

0..1

Type

Seconds

tw2

Washout time constant (Tw2) (>= 0). Typical value = 0,3.

URI

cim:PssIEEE3B.tw2

Cardinality

0..1

Type

Seconds

tw3

Washout time constant (Tw3) (>= 0). Typical value = 0,6.

URI

cim:PssIEEE3B.tw3

Cardinality

0..1

Type

Seconds

vstmax

Stabilizer output maximum limit (Vstmax) (> PssIEEE3B.vstmin). Typical value = 0,1.

URI

cim:PssIEEE3B.vstmax

Cardinality

0..1

Type

PU

vstmin

Stabilizer output minimum limit (Vstmin) (< PssIEEE3B.vstmax). Typical value = -0,1.

URI

cim:PssIEEE3B.vstmin

Cardinality

0..1

Type