RemoteConnectDisconnectInfo

Details of remote connect and disconnect function.

Type

Class

URI

cim:RemoteConnectDisconnectInfo

CIM standard (perspective)

IEC61968 (Enterprise)

Class hierarchy

  • RemoteConnectDisconnectInfo

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

armedTimeout

0..1

Seconds

Setting of the timeout elapsed time.

customerVoltageLimit

0..1

Voltage

Voltage limit on customer side of RCD switch above which the connect should not be made.

energyLimit

0..1

RealEnergy

Limit of energy before disconnect.

energyUsageStartDateTime

0..1

date

Start date and time to accumulate energy for energy usage limiting.

energyUsageWarning

0..1

RealEnergy

Warning energy limit, used to trigger event code that energy usage is nearing limit.

isArmConnect

0..1

boolean

True if the RCD switch has to be armed before a connect action can be initiated.

isArmDisconnect

0..1

boolean

True if the RCD switch has to be armed before a disconnect action can be initiated.

isEnergyLimiting

0..1

boolean

True if the energy usage is limited and the customer will be disconnected if they go over the limit.

needsPowerLimitCheck

0..1

boolean

True if load limit has to be checked to issue an immediate disconnect (after a connect) if load is over the limit.

needsVoltageLimitCheck

0..1

boolean

True if voltage limit has to be checked to prevent connect if voltage is over the limit.

powerLimit

0..1

ActivePower

Load limit above which the connect should either not take place or should cause an immediate disconnect.

usePushbutton

0..1

boolean

True if pushbutton has to be used for connect.


armedTimeout

Setting of the timeout elapsed time.

URI

cim:RemoteConnectDisconnectInfo.armedTimeout

Cardinality

0..1

Type

Seconds

customerVoltageLimit

Voltage limit on customer side of RCD switch above which the connect should not be made.

URI

cim:RemoteConnectDisconnectInfo.customerVoltageLimit

Cardinality

0..1

Type

Voltage

energyLimit

Limit of energy before disconnect.

URI

cim:RemoteConnectDisconnectInfo.energyLimit

Cardinality

0..1

Type

RealEnergy

energyUsageStartDateTime

Start date and time to accumulate energy for energy usage limiting.

URI

cim:RemoteConnectDisconnectInfo.energyUsageStartDateTime

Cardinality

0..1

Type

date

energyUsageWarning

Warning energy limit, used to trigger event code that energy usage is nearing limit.

URI

cim:RemoteConnectDisconnectInfo.energyUsageWarning

Cardinality

0..1

Type

RealEnergy

isArmConnect

True if the RCD switch has to be armed before a connect action can be initiated.

URI

cim:RemoteConnectDisconnectInfo.isArmConnect

Cardinality

0..1

Type

boolean

isArmDisconnect

True if the RCD switch has to be armed before a disconnect action can be initiated.

URI

cim:RemoteConnectDisconnectInfo.isArmDisconnect

Cardinality

0..1

Type

boolean

isEnergyLimiting

True if the energy usage is limited and the customer will be disconnected if they go over the limit.

URI

cim:RemoteConnectDisconnectInfo.isEnergyLimiting

Cardinality

0..1

Type

boolean

needsPowerLimitCheck

True if load limit has to be checked to issue an immediate disconnect (after a connect) if load is over the limit.

URI

cim:RemoteConnectDisconnectInfo.needsPowerLimitCheck

Cardinality

0..1

Type

boolean

needsVoltageLimitCheck

True if voltage limit has to be checked to prevent connect if voltage is over the limit.

URI

cim:RemoteConnectDisconnectInfo.needsVoltageLimitCheck

Cardinality

0..1

Type

boolean

powerLimit

Load limit above which the connect should either not take place or should cause an immediate disconnect.

URI

cim:RemoteConnectDisconnectInfo.powerLimit

Cardinality

0..1

Type

ActivePower

usePushbutton

True if pushbutton has to be used for connect.

URI

cim:RemoteConnectDisconnectInfo.usePushbutton

Cardinality

0..1

Type

boolean