VsConverter

DC side of the voltage source converter (VSC).

Type

Class

URI

cim:VsConverter

CIM standard (perspective)

IEC61970 (Grid)

Slots

Name Type Description Inherited from

CapabilityCurve

0..1
VsCapabilityCurve

Capability curve of this converter.

n/a

VSCDynamics

0..1
VSCDynamics

Voltage source converter dynamics model used to describe dynamic behaviour of this converter.

n/a

delta

0..1
AngleDegrees

Angle between VsConverter.uv and ACDCConverter.uc. It is converter’s state variable used in power flow. The attribute shall...

n/a

droop

0..1
PU

Droop constant. The pu value is obtained as D [kV/MW] x Sb / Ubdc. The attribute shall be a positive value.

n/a

droopCompensation

0..1
Resistance

Compensation constant. Used to compensate for voltage drop when controlling voltage at a distant bus. The attribute shall be...

n/a

maxModulationIndex

0..1
float

The maximum quotient between the AC converter voltage (Uc) and DC voltage (Ud). A factor typically less than 1. It is...

n/a

maxValveCurrent

0..1
CurrentFlow

The maximum current through a valve. It is converter’s configuration data.

n/a

pPccControl

0..1
VsPpccControlKind

Kind of control of real power and/or DC voltage.

n/a

qPccControl

0..1
VsQpccControlKind

Kind of reactive power control.

n/a

qShare

0..1
PerCent

Reactive power sharing factor among parallel converters on Uac control. The attribute shall be a positive value or zero.

n/a

targetPWMfactor

0..1
float

Magnitude of pulse-modulation factor. The attribute shall be a positive value.

n/a

targetPhasePcc

0..1
AngleDegrees

Phase target at AC side, at point of common coupling. The attribute shall be a positive value.

n/a

targetPowerFactorPcc

0..1
float

Power factor target at the AC side, at point of common coupling. The attribute shall be a positive value.

n/a

targetQpcc

0..1
ReactivePower

Reactive power injection target in AC grid, at point of common coupling. Load sign convention is used, i.e. positive sign...

n/a

targetUpcc

0..1
Voltage

Voltage target in AC grid, at point of common coupling. The attribute shall be a positive value.

n/a

uv

0..1
Voltage

Line-to-line voltage on the valve side of the converter transformer. It is converter’s state variable, result from power...

n/a

DCTerminals

0..*
ACDCConverterDCTerminal

A DC converter have DC converter terminals. A converter has two DC converter terminals.

ACDCConverter

PccTerminal

0..1
Terminal

Point of common coupling terminal for this converter DC side. It is typically the terminal on the power transformer (or...

ACDCConverter

baseS

0..1
ApparentPower

Base apparent power of the converter pole. The attribute shall be a positive value.

ACDCConverter

idc

0..1
CurrentFlow

Converter DC current, also called Id. It is converter’s state variable, result from power flow.

ACDCConverter

idleLoss

0..1
ActivePower

Active power loss in pole at no power transfer. It is converter’s configuration data used in power flow. The attribute shall...

ACDCConverter

maxP

0..1
ActivePower

Maximum active power limit. The value is overwritten by values of VsCapabilityCurve, if present.

ACDCConverter

maxUdc

0..1
Voltage

The maximum voltage on the DC side at which the converter should operate. It is converter’s configuration data used in power...

ACDCConverter

minP

0..1
ActivePower

Minimum active power limit. The value is overwritten by values of VsCapabilityCurve, if present.

ACDCConverter

minUdc

0..1
Voltage

The minimum voltage on the DC side at which the converter should operate. It is converter’s configuration data used in power...

ACDCConverter

numberOfValves

0..1
integer

Number of valves in the converter. Used in loss calculations.

ACDCConverter

p

0..1
ActivePower

Active power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a...

ACDCConverter

poleLossP

0..1
ActivePower

The active power loss at a DC Pole = idleLoss + switchingLoss*|Idc| + resitiveLoss*Idc^2. For lossless operation...

ACDCConverter

q

0..1
ReactivePower

Reactive power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a...

ACDCConverter

ratedUdc

0..1
Voltage

Rated converter DC voltage, also called UdN. The attribute shall be a positive value. It is converter’s configuration data...

ACDCConverter

resistiveLoss

0..1
Resistance

It is converter’s configuration data used in power flow. Refer to poleLossP. The attribute shall be a positive value.

ACDCConverter

switchingLoss

0..1
ActivePowerPerCurrentFlow

Switching losses, relative to the base apparent power 'baseS'. Refer to poleLossP. The attribute shall be a positive value.

ACDCConverter

targetPpcc

0..1
ActivePower

Real power injection target in AC grid, at point of common coupling. Load sign convention is used, i.e. positive sign means...

ACDCConverter

targetUdc

0..1
Voltage

Target value for DC voltage magnitude. The attribute shall be a positive value.

ACDCConverter

uc

0..1
Voltage

Line-to-line converter voltage, the voltage at the AC side of the valve. It is converter’s state variable, result from power...

ACDCConverter

udc

0..1
Voltage

Converter voltage at the DC side, also called Ud. It is converter’s state variable, result from power flow. The attribute...

ACDCConverter

valveU0

0..1
Voltage

Valve threshold voltage, also called Uvalve. Forward voltage drop when the valve is conducting. Used in loss calculations,...

ACDCConverter

BaseVoltage

0..1
BaseVoltage

Base voltage of this conducting equipment. Use only when there is no voltage level container used and only one base voltage...

ConductingEquipment

GroundingAction

0..1
GroundAction

Action involving grounding operation on this conducting equipment.

ConductingEquipment

JumpingAction

0..1
JumperAction

Jumper action involving jumping operation on this conducting equipment.

ConductingEquipment

Outage

0..1
Outage

The outage that is isolated by the outage isolation equipment.

ConductingEquipment

ProtectionEquipments

0..*
ProtectionEquipment

Protection equipment used to protect specific conducting equipment.

ConductingEquipment

ProtectiveActionAdjustment

0..*
ProtectiveActionAdjustment

The operating condition to the Conducting Equipment is changed when protective action adjustment is activated. For...

ConductingEquipment

SvStatus

0..*
SvStatus

The status state variable associated with this conducting equipment.

ConductingEquipment

Terminals

0..*
Terminal

Conducting equipment have terminals that may be connected to other conducting equipment terminals via connectivity nodes or...

ConductingEquipment

AdditionalEquipmentContainer

0..*
EquipmentContainer

Additional equipment container beyond the primary equipment container. The equipment is contained in another equipment...

Equipment

ContingencyEquipment

0..*
ContingencyEquipment

The contingency equipments in which this equipment participates.

Equipment

EqiupmentLimitSeriesComponent

0..*
EquipmentLimitSeriesComponent

Equipment limit series calculation component to which this equipment contributes.

Equipment

EquipmentContainer

0..1
EquipmentContainer

Container of this equipment.

Equipment

EquipmentUnavailabilitySchedule

0..*
EquipmentUnavailabilitySchedule

n/a

Equipment

Faults

0..*
Fault

All faults on this equipment.

Equipment

LimitDependencyModel

0..*
LimitDependency

Limit dependencymodels organized under this equipment as a means for organizing the model in a tree view.

Equipment

OperationalLimitSet

0..*
OperationalLimitSet

The operational limit sets associated with this equipment.

Equipment

OperationalRestrictions

0..*
OperationalRestriction

All operational restrictions for this equipment.

Equipment

Outages

0..*
Outage

All outages in which this equipment is involved.

Equipment

PinEquipment

0..*
PinEquipment

n/a

Equipment

ProtectiveActionEquipment

0..*
ProtectiveActionEquipment

Protective action is controlling equipment. This can be direct signals from the control center, or emulation of action done...

Equipment

UsagePoints

0..*
UsagePoint

All usage points connected to the electrical grid through this equipment.

Equipment

WeatherStation

0..*
WeatherStation

n/a

Equipment

aggregate

0..1
boolean

The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases...

Equipment

inService

0..1
boolean

Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines...

Equipment

networkAnalysisEnabled

0..1
boolean

The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.

Equipment

normallyInService

0..1
boolean

Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for...

Equipment

AssetDatasheet

0..1
AssetInfo

Datasheet information for this power system resource.

PowerSystemResource

Assets

0..*
Asset

All assets represented by this power system resource. For example, multiple conductor assets are electrically modelled as a...

PowerSystemResource

Clearances

0..*
ClearanceDocument

All clearances applicable to this power system resource.

PowerSystemResource

ConfigurationEvent

0..*
ConfigurationEvent

All configuration events created for this Power System resource.

PowerSystemResource

Controls

0..*
Control

The controller outputs used to actually govern a regulating device, e.g. the magnetization of a synchronous machine or...

PowerSystemResource

GenericAction

0..*
GenericAction

The generic action that is performed on the power system resource

PowerSystemResource

Location

0..1
Location

Location of this power system resource.

PowerSystemResource

Measurements

0..*
Measurement

The measurements associated with this power system resource.

PowerSystemResource

OperatingShare

0..*
OperatingShare

The operating shares of this power system resource.

PowerSystemResource

OperationalTags

0..*
OperationalTag

All operational tags placed on this power system resource.

PowerSystemResource

PSREvents

0..*
PSREvent

All events associated with this power system resource.

PowerSystemResource

PSRType

0..1
PSRType

Custom classification for this power system resource.

PowerSystemResource

ReportingGroup

0..*
ReportingGroup

Reporting groups to which this power system resource belongs.

PowerSystemResource

VerificationAction

0..*
VerificationAction

The verification action that is performed on the power system resource

PowerSystemResource

DiagramObjects

0..*
DiagramObject

The diagram objects that are associated with the domain object.

IdentifiedObject

InstanceSet

1
InstanceSet

Dataset containing the data objects.

IdentifiedObject

Names

0..*
Name

All names of this identified object.

IdentifiedObject

PropertiesCIMDataObject

0..1
ChangeSetMember

The single CIM data object in the appropriate dataset context.

IdentifiedObject

TargetingCIMDataObject

0..*
ChangeSetMember

Data objects registered.

IdentifiedObject

aliasName

0..1
string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and...

IdentifiedObject

description

0..1
string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to...

IdentifiedObject

mRID

0..1
string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is...

IdentifiedObject

name

0..1
string

The name is any free human readable and possibly non unique text naming the object.

IdentifiedObject


AdditionalEquipmentContainer

Additional equipment container beyond the primary equipment container. The equipment is contained in another equipment container, but also grouped with this equipment container.

URI

cim:Equipment.AdditionalEquipmentContainer

Cardinality

0..*

Type

EquipmentContainer

Inherited from

Equipment

aggregate

The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine. The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.

URI

cim:Equipment.aggregate

Cardinality

0..1

Type

boolean

Inherited from

Equipment

aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

AssetDatasheet

Datasheet information for this power system resource.

URI

cim:PowerSystemResource.AssetDatasheet

Cardinality

0..1

Type

AssetInfo

Inherited from

PowerSystemResource

Assets

All assets represented by this power system resource. For example, multiple conductor assets are electrically modelled as a single AC line segment.

URI

cim:PowerSystemResource.Assets

Cardinality

0..*

Type

Asset

Inherited from

PowerSystemResource

baseS

Base apparent power of the converter pole. The attribute shall be a positive value.

URI

cim:ACDCConverter.baseS

Cardinality

0..1

Type

ApparentPower

Inherited from

ACDCConverter

BaseVoltage

Base voltage of this conducting equipment. Use only when there is no voltage level container used and only one base voltage applies. For example, not used for transformers.

URI

cim:ConductingEquipment.BaseVoltage

Cardinality

0..1

Type

BaseVoltage

Inherited from

ConductingEquipment

CapabilityCurve

Capability curve of this converter.

URI

cim:VsConverter.CapabilityCurve

Cardinality

0..1

Type

VsCapabilityCurve

Clearances

All clearances applicable to this power system resource.

URI

cim:PowerSystemResource.Clearances

Cardinality

0..*

Type

ClearanceDocument

Inherited from

PowerSystemResource

ConfigurationEvent

All configuration events created for this Power System resource.

URI

cim:PowerSystemResource.ConfigurationEvent

Cardinality

0..*

Type

ConfigurationEvent

Inherited from

PowerSystemResource

ContingencyEquipment

The contingency equipments in which this equipment participates.

URI

cim:Equipment.ContingencyEquipment

Cardinality

0..*

Type

ContingencyEquipment

Inherited from

Equipment

Controls

The controller outputs used to actually govern a regulating device, e.g. the magnetization of a synchronous machine or capacitor bank breaker actuator.

URI

cim:PowerSystemResource.Controls

Cardinality

0..*

Type

Control

Inherited from

PowerSystemResource

DCTerminals

A DC converter have DC converter terminals. A converter has two DC converter terminals.

URI

cim:ACDCConverter.DCTerminals

Cardinality

0..*

Type

ACDCConverterDCTerminal

Inherited from

ACDCConverter

delta

Angle between VsConverter.uv and ACDCConverter.uc. It is converter’s state variable used in power flow. The attribute shall be a positive value or zero.

URI

cim:VsConverter.delta

Cardinality

0..1

Type

AngleDegrees

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

droop

Droop constant. The pu value is obtained as D [kV/MW] x Sb / Ubdc. The attribute shall be a positive value.

URI

cim:VsConverter.droop

Cardinality

0..1

Type

PU

droopCompensation

Compensation constant. Used to compensate for voltage drop when controlling voltage at a distant bus. The attribute shall be a positive value.

URI

cim:VsConverter.droopCompensation

Cardinality

0..1

Type

Resistance

EqiupmentLimitSeriesComponent

Equipment limit series calculation component to which this equipment contributes.

URI

cim:Equipment.EqiupmentLimitSeriesComponent

Cardinality

0..*

Type

EquipmentLimitSeriesComponent

Inherited from

Equipment

EquipmentContainer

Container of this equipment.

URI

cim:Equipment.EquipmentContainer

Cardinality

0..1

Type

EquipmentContainer

Inherited from

Equipment

EquipmentUnavailabilitySchedule

URI

cim:Equipment.EquipmentUnavailabilitySchedule

Cardinality

0..*

Type

EquipmentUnavailabilitySchedule

Inherited from

Equipment

Faults

All faults on this equipment.

URI

cim:Equipment.Faults

Cardinality

0..*

Type

Fault

Inherited from

Equipment

GenericAction

The generic action that is performed on the power system resource

URI

cim:PowerSystemResource.GenericAction

Cardinality

0..*

Type

GenericAction

Inherited from

PowerSystemResource

GroundingAction

Action involving grounding operation on this conducting equipment.

URI

cim:ConductingEquipment.GroundingAction

Cardinality

0..1

Type

GroundAction

Inherited from

ConductingEquipment

idc

Converter DC current, also called Id. It is converter’s state variable, result from power flow.

URI

cim:ACDCConverter.idc

Cardinality

0..1

Type

CurrentFlow

Inherited from

ACDCConverter

idleLoss

Active power loss in pole at no power transfer. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

URI

cim:ACDCConverter.idleLoss

Cardinality

0..1

Type

ActivePower

Inherited from

ACDCConverter

inService

Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

URI

cim:Equipment.inService

Cardinality

0..1

Type

boolean

Inherited from

Equipment

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

JumpingAction

Jumper action involving jumping operation on this conducting equipment.

URI

cim:ConductingEquipment.JumpingAction

Cardinality

0..1

Type

JumperAction

Inherited from

ConductingEquipment

LimitDependencyModel

Limit dependencymodels organized under this equipment as a means for organizing the model in a tree view.

URI

cim:Equipment.LimitDependencyModel

Cardinality

0..*

Type

LimitDependency

Inherited from

Equipment

Location

Location of this power system resource.

URI

cim:PowerSystemResource.Location

Cardinality

0..1

Type

Location

Inherited from

PowerSystemResource

maxModulationIndex

The maximum quotient between the AC converter voltage (Uc) and DC voltage (Ud). A factor typically less than 1. It is converter’s configuration data used in power flow.

URI

cim:VsConverter.maxModulationIndex

Cardinality

0..1

Type

float

maxP

Maximum active power limit. The value is overwritten by values of VsCapabilityCurve, if present.

URI

cim:ACDCConverter.maxP

Cardinality

0..1

Type

ActivePower

Inherited from

ACDCConverter

maxUdc

The maximum voltage on the DC side at which the converter should operate. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

URI

cim:ACDCConverter.maxUdc

Cardinality

0..1

Type

Voltage

Inherited from

ACDCConverter

maxValveCurrent

The maximum current through a valve. It is converter’s configuration data.

URI

cim:VsConverter.maxValveCurrent

Cardinality

0..1

Type

CurrentFlow

Measurements

The measurements associated with this power system resource.

URI

cim:PowerSystemResource.Measurements

Cardinality

0..*

Type

Measurement

Inherited from

PowerSystemResource

minP

Minimum active power limit. The value is overwritten by values of VsCapabilityCurve, if present.

URI

cim:ACDCConverter.minP

Cardinality

0..1

Type

ActivePower

Inherited from

ACDCConverter

minUdc

The minimum voltage on the DC side at which the converter should operate. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

URI

cim:ACDCConverter.minUdc

Cardinality

0..1

Type

Voltage

Inherited from

ACDCConverter

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

networkAnalysisEnabled

The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.

URI

cim:Equipment.networkAnalysisEnabled

Cardinality

0..1

Type

boolean

Inherited from

Equipment

normallyInService

Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

URI

cim:Equipment.normallyInService

Cardinality

0..1

Type

boolean

Inherited from

Equipment

numberOfValves

Number of valves in the converter. Used in loss calculations.

URI

cim:ACDCConverter.numberOfValves

Cardinality

0..1

Type

integer

Inherited from

ACDCConverter

OperatingShare

The operating shares of this power system resource.

URI

cim:PowerSystemResource.OperatingShare

Cardinality

0..*

Type

OperatingShare

Inherited from

PowerSystemResource

OperationalLimitSet

The operational limit sets associated with this equipment.

URI

cim:Equipment.OperationalLimitSet

Cardinality

0..*

Type

OperationalLimitSet

Inherited from

Equipment

OperationalRestrictions

All operational restrictions for this equipment.

URI

cim:Equipment.OperationalRestrictions

Cardinality

0..*

Type

OperationalRestriction

Inherited from

Equipment

OperationalTags

All operational tags placed on this power system resource.

URI

cim:PowerSystemResource.OperationalTags

Cardinality

0..*

Type

OperationalTag

Inherited from

PowerSystemResource

Outage

The outage that is isolated by the outage isolation equipment.

URI

cim:ConductingEquipment.Outage

Cardinality

0..1

Type

Outage

Inherited from

ConductingEquipment

Outages

All outages in which this equipment is involved.

URI

cim:Equipment.Outages

Cardinality

0..*

Type

Outage

Inherited from

Equipment

p

Active power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution in the case a simplified power flow model is used.

URI

cim:ACDCConverter.p

Cardinality

0..1

Type

ActivePower

Inherited from

ACDCConverter

PccTerminal

Point of common coupling terminal for this converter DC side. It is typically the terminal on the power transformer (or switch) closest to the AC network.

URI

cim:ACDCConverter.PccTerminal

Cardinality

0..1

Type

Terminal

Inherited from

ACDCConverter

PinEquipment

URI

cim:Equipment.PinEquipment

Cardinality

0..*

Type

PinEquipment

Inherited from

Equipment

poleLossP

The active power loss at a DC Pole = idleLoss + switchingLoss*|Idc| + resitiveLoss*Idc^2. For lossless operation Pdc=Pac. For rectifier operation with losses Pdc=Pac-lossP. For inverter operation with losses Pdc=Pac+lossP. It is converter’s state variable used in power flow. The attribute shall be a positive value.

URI

cim:ACDCConverter.poleLossP

Cardinality

0..1

Type

ActivePower

Inherited from

ACDCConverter

pPccControl

Kind of control of real power and/or DC voltage.

URI

cim:VsConverter.pPccControl

Cardinality

0..1

Type

VsPpccControlKind

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

ProtectionEquipments

Protection equipment used to protect specific conducting equipment.

URI

cim:ConductingEquipment.ProtectionEquipments

Cardinality

0..*

Type

ProtectionEquipment

Inherited from

ConductingEquipment

ProtectiveActionAdjustment

The operating condition to the Conducting Equipment is changed when protective action adjustment is activated. For ShuntCompensator or other conducting equipment that operates on discrete values (integer), the values given in float will be rounded.

URI

cim:ConductingEquipment.ProtectiveActionAdjustment

Cardinality

0..*

Type

ProtectiveActionAdjustment

Inherited from

ConductingEquipment

ProtectiveActionEquipment

Protective action is controlling equipment. This can be direct signals from the control center, or emulation of action done by protection equipment.

URI

cim:Equipment.ProtectiveActionEquipment

Cardinality

0..*

Type

ProtectiveActionEquipment

Inherited from

Equipment

PSREvents

All events associated with this power system resource.

URI

cim:PowerSystemResource.PSREvents

Cardinality

0..*

Type

PSREvent

Inherited from

PowerSystemResource

PSRType

Custom classification for this power system resource.

URI

cim:PowerSystemResource.PSRType

Cardinality

0..1

Type

PSRType

Inherited from

PowerSystemResource

q

Reactive power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution in the case a simplified power flow model is used.

URI

cim:ACDCConverter.q

Cardinality

0..1

Type

ReactivePower

Inherited from

ACDCConverter

qPccControl

Kind of reactive power control.

URI

cim:VsConverter.qPccControl

Cardinality

0..1

Type

VsQpccControlKind

qShare

Reactive power sharing factor among parallel converters on Uac control. The attribute shall be a positive value or zero.

URI

cim:VsConverter.qShare

Cardinality

0..1

Type

PerCent

ratedUdc

Rated converter DC voltage, also called UdN. The attribute shall be a positive value. It is converter’s configuration data used in power flow. For instance a bipolar HVDC link with value 200 kV has a 400kV difference between the dc lines.

URI

cim:ACDCConverter.ratedUdc

Cardinality

0..1

Type

Voltage

Inherited from

ACDCConverter

ReportingGroup

Reporting groups to which this power system resource belongs.

URI

cim:PowerSystemResource.ReportingGroup

Cardinality

0..*

Type

ReportingGroup

Inherited from

PowerSystemResource

resistiveLoss

It is converter’s configuration data used in power flow. Refer to poleLossP. The attribute shall be a positive value.

URI

cim:ACDCConverter.resistiveLoss

Cardinality

0..1

Type

Resistance

Inherited from

ACDCConverter

SvStatus

The status state variable associated with this conducting equipment.

URI

cim:ConductingEquipment.SvStatus

Cardinality

0..*

Type

SvStatus

Inherited from

ConductingEquipment

switchingLoss

Switching losses, relative to the base apparent power 'baseS'. Refer to poleLossP. The attribute shall be a positive value.

URI

cim:ACDCConverter.switchingLoss

Cardinality

0..1

Type

ActivePowerPerCurrentFlow

Inherited from

ACDCConverter

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

targetPhasePcc

Phase target at AC side, at point of common coupling. The attribute shall be a positive value.

URI

cim:VsConverter.targetPhasePcc

Cardinality

0..1

Type

AngleDegrees

targetPowerFactorPcc

Power factor target at the AC side, at point of common coupling. The attribute shall be a positive value.

URI

cim:VsConverter.targetPowerFactorPcc

Cardinality

0..1

Type

float

targetPpcc

Real power injection target in AC grid, at point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node.

URI

cim:ACDCConverter.targetPpcc

Cardinality

0..1

Type

ActivePower

Inherited from

ACDCConverter

targetPWMfactor

Magnitude of pulse-modulation factor. The attribute shall be a positive value.

URI

cim:VsConverter.targetPWMfactor

Cardinality

0..1

Type

float

targetQpcc

Reactive power injection target in AC grid, at point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node.

URI

cim:VsConverter.targetQpcc

Cardinality

0..1

Type

ReactivePower

targetUdc

Target value for DC voltage magnitude. The attribute shall be a positive value.

URI

cim:ACDCConverter.targetUdc

Cardinality

0..1

Type

Voltage

Inherited from

ACDCConverter

targetUpcc

Voltage target in AC grid, at point of common coupling. The attribute shall be a positive value.

URI

cim:VsConverter.targetUpcc

Cardinality

0..1

Type

Voltage

Terminals

Conducting equipment have terminals that may be connected to other conducting equipment terminals via connectivity nodes or topological nodes.

URI

cim:ConductingEquipment.Terminals

Cardinality

0..*

Type

Terminal

Inherited from

ConductingEquipment

uc

Line-to-line converter voltage, the voltage at the AC side of the valve. It is converter’s state variable, result from power flow. The attribute shall be a positive value.

URI

cim:ACDCConverter.uc

Cardinality

0..1

Type

Voltage

Inherited from

ACDCConverter

udc

Converter voltage at the DC side, also called Ud. It is converter’s state variable, result from power flow. The attribute shall be a positive value.

URI

cim:ACDCConverter.udc

Cardinality

0..1

Type

Voltage

Inherited from

ACDCConverter

UsagePoints

All usage points connected to the electrical grid through this equipment.

URI

cim:Equipment.UsagePoints

Cardinality

0..*

Type

UsagePoint

Inherited from

Equipment

uv

Line-to-line voltage on the valve side of the converter transformer. It is converter’s state variable, result from power flow. The attribute shall be a positive value.

URI

cim:VsConverter.uv

Cardinality

0..1

Type

Voltage

valveU0

Valve threshold voltage, also called Uvalve. Forward voltage drop when the valve is conducting. Used in loss calculations, i.e. the switchLoss depend on numberOfValves * valveU0.

URI

cim:ACDCConverter.valveU0

Cardinality

0..1

Type

Voltage

Inherited from

ACDCConverter

VerificationAction

The verification action that is performed on the power system resource

URI

cim:PowerSystemResource.VerificationAction

Cardinality

0..*

Type

VerificationAction

Inherited from

PowerSystemResource

VSCDynamics

Voltage source converter dynamics model used to describe dynamic behaviour of this converter.

URI

cim:VsConverter.VSCDynamics

Cardinality

0..1

Type

VSCDynamics

WeatherStation

URI

cim:Equipment.WeatherStation

Cardinality

0..*

Type

WeatherStation

Inherited from