SurgeArresterInfo
Properties of surge arrester.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61968 (Enterprise) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Dataset containing the data objects. |
||
0..1 |
Maximum continuous power frequency voltage allowed on the surge arrester. |
||
0..1 |
If true, the arrester has a polymer housing, porcelain otherwise. |
||
0..1 |
Residual voltage during an 8x20 microsecond current impulse at the nominal discharge current level. |
||
0..1 |
Determines the arrester energy discharge capability. Choices are limited to 0 (none) through 5 (highest) by IEC 60099. Classes 1..3 require a 10-kA nominal discharge current. Classes 4..5 require a 20-kA nominal discharge current. Lower nominal discharge currents must use class 0. |
||
0..1 |
The lightning discharge current used to classify the arrester. Choices are limited to 1.5, 2.5, 5, 10, and 20 kA by IEC 60099. |
||
0..1 |
Fault current level at which all parts of the failed arrester lie within a circle prescribed by IEC 60099. |
||
0..1 |
The temporary overvoltage (TOV) level at power frequency that the surge arrester withstands for 10 seconds. |
||
0..1 |
Residual voltage during a current impulse with front time of 1 microsecond, and magnitude equal to the nominal discharge current level. |
||
0..1 |
Residual voltage during a current impulse with front time of at least 30 microseconds, and magnitude specified in IEC 60099 for the line discharge class. Does not apply to line discharge class 0. |
||
0..1 |
Asset information (nameplate) for this catalog asset type. |
||
0..1 |
Product asset model which conforms to this catalog asset type. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
All assets described by this data. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
All power system resources with this datasheet information. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Assets
All assets described by this data.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
CatalogAssetType
Asset information (nameplate) for this catalog asset type.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
continuousOperatingVoltage
Maximum continuous power frequency voltage allowed on the surge arrester.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
isPolymer
If true, the arrester has a polymer housing, porcelain otherwise.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
lightningImpulseDischargeVoltage
Residual voltage during an 8x20 microsecond current impulse at the nominal discharge current level.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
lineDischargeClass
Determines the arrester energy discharge capability. Choices are limited to 0 (none) through 5 (highest) by IEC 60099. Classes 1..3 require a 10-kA nominal discharge current. Classes 4..5 require a 20-kA nominal discharge current. Lower nominal discharge currents must use class 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
nominalDischargeCurrent
The lightning discharge current used to classify the arrester. Choices are limited to 1.5, 2.5, 5, 10, and 20 kA by IEC 60099.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
PowerSystemResources
All power system resources with this datasheet information.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
pressureReliefClass
Fault current level at which all parts of the failed arrester lie within a circle prescribed by IEC 60099.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
ProductAssetModel
Product asset model which conforms to this catalog asset type.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
ratedVoltage
The temporary overvoltage (TOV) level at power frequency that the surge arrester withstands for 10 seconds.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
steepFrontDischargeVoltage
Residual voltage during a current impulse with front time of 1 microsecond, and magnitude equal to the nominal discharge current level.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
switchingImpulseDischargeVoltage
Residual voltage during a current impulse with front time of at least 30 microseconds, and magnitude specified in IEC 60099 for the line discharge class. Does not apply to line discharge class 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |