TransformerObservation

Common information captured during transformer inspections and/or diagnostics. Note that some properties may be measured through other means and therefore have measurement values in addition to the observed values recorded here.

Type

Class

URI

cim:TransformerObservation

CIM standard (perspective)

IEC61968 (Enterprise)

Class hierarchy

Slots

Name Type Description Inherited from

BushingInsultationPFs

0..*
BushingInsulationPF

n/a

n/a

ProcedureDataSets

0..*
ProcedureDataSet

n/a

n/a

Reconditioning

1
Reconditioning

n/a

n/a

Transformer

0..1
TransformerTank

n/a

n/a

WindingInsulationPFs

0..*
WindingInsulation

n/a

n/a

bushingTemp

0..1
Temperature

Bushing temperature.

n/a

dga

0..1
string

Dissolved Gas Analysis. Typical values are: Acceptable, Overheating, Corona, Sparking, Arcing.

n/a

freqResp

0..1
string

Frequency Response Analysis. Typical values are: acceptable, slight movement, significant movement, failed, near failure. A...

n/a

furfuralDP

0..1
string

Overall measure of furfural in oil and mechanical strength of paper. DP, the degree of polymerization, is the strength of...

n/a

hotSpotTemp

0..1
Temperature

Hotspot oil temperature.

n/a

oilColor

0..1
string

Oil Quality Analysis-Color.

n/a

oilDielectricStrength

0..1
Voltage

Oil Quality Analysis-Dielectric Strength.

n/a

oilIFT

0..1
string

Oil Quality Analysis- inter facial tension (IFT) - number-Dynes/CM.

n/a

oilLevel

0..1
string

The level of oil in the transformer.

n/a

oilNeutralizationNumber

0..1
string

Oil Quality Analysis-Neutralization Number - Number - Mg KOH.

n/a

pumpVibration

0..1
string

Pump vibration, with typical values being: nominal, high.

n/a

status

0..1
Status

n/a

n/a

topOilTemp

0..1
Temperature

Top oil temperature.

n/a

waterContent

0..1
string

Water Content expressed in parts per million.

n/a

DiagramObjects

0..*
DiagramObject

The diagram objects that are associated with the domain object.

IdentifiedObject

InstanceSet

1
InstanceSet

Dataset containing the data objects.

IdentifiedObject

Names

0..*
Name

All names of this identified object.

IdentifiedObject

PropertiesCIMDataObject

0..1
ChangeSetMember

The single CIM data object in the appropriate dataset context.

IdentifiedObject

TargetingCIMDataObject

0..*
ChangeSetMember

Data objects registered.

IdentifiedObject

aliasName

0..1
string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and...

IdentifiedObject

description

0..1
string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to...

IdentifiedObject

mRID

0..1
string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is...

IdentifiedObject

name

0..1
string

The name is any free human readable and possibly non unique text naming the object.

IdentifiedObject


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

BushingInsultationPFs

URI

cim:TransformerObservation.BushingInsultationPFs

Cardinality

0..*

Type

BushingInsulationPF

bushingTemp

Bushing temperature.

URI

cim:TransformerObservation.bushingTemp

Cardinality

0..1

Type

Temperature

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

dga

Dissolved Gas Analysis. Typical values are: Acceptable, Overheating, Corona, Sparking, Arcing.

URI

cim:TransformerObservation.dga

Cardinality

0..1

Type

string

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

freqResp

Frequency Response Analysis. Typical values are: acceptable, slight movement, significant movement, failed, near failure. A graphic of the response diagram, which is a type of document, may be associated with this analysis through the recursive document relationship of the ProcedureDataSet.

URI

cim:TransformerObservation.freqResp

Cardinality

0..1

Type

string

furfuralDP

Overall measure of furfural in oil and mechanical strength of paper. DP, the degree of polymerization, is the strength of the paper. Furfural is a measure of furfural compounds, often expressed in parts per million.

URI

cim:TransformerObservation.furfuralDP

Cardinality

0..1

Type

string

hotSpotTemp

Hotspot oil temperature.

URI

cim:TransformerObservation.hotSpotTemp

Cardinality

0..1

Type

Temperature

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

oilColor

Oil Quality Analysis-Color.

URI

cim:TransformerObservation.oilColor

Cardinality

0..1

Type

string

oilDielectricStrength

Oil Quality Analysis-Dielectric Strength.

URI

cim:TransformerObservation.oilDielectricStrength

Cardinality

0..1

Type

Voltage

oilIFT

Oil Quality Analysis- inter facial tension (IFT) - number-Dynes/CM.

URI

cim:TransformerObservation.oilIFT

Cardinality

0..1

Type

string

oilLevel

The level of oil in the transformer.

URI

cim:TransformerObservation.oilLevel

Cardinality

0..1

Type

string

oilNeutralizationNumber

Oil Quality Analysis-Neutralization Number - Number - Mg KOH.

URI

cim:TransformerObservation.oilNeutralizationNumber

Cardinality

0..1

Type

string

ProcedureDataSets

URI

cim:TransformerObservation.ProcedureDataSets

Cardinality

0..*

Type

ProcedureDataSet

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

pumpVibration

Pump vibration, with typical values being: nominal, high.

URI

cim:TransformerObservation.pumpVibration

Cardinality

0..1

Type

string

Reconditioning

URI

cim:TransformerObservation.Reconditioning

Cardinality

1

Type

Reconditioning

status

URI

cim:TransformerObservation.status

Cardinality

0..1

Type

Status

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

topOilTemp

Top oil temperature.

URI

cim:TransformerObservation.topOilTemp

Cardinality

0..1

Type

Temperature

Transformer

URI

cim:TransformerObservation.Transformer

Cardinality

0..1

Type

TransformerTank

waterContent

Water Content expressed in parts per million.

URI

cim:TransformerObservation.waterContent

Cardinality

0..1

Type

string

WindingInsulationPFs

URI

cim:TransformerObservation.WindingInsulationPFs

Cardinality

0..*

Type

WindingInsulation