ExcIEEEAC5A
IEEE 421.5-2005 type AC5A model. The model represents a simplified model for brushless excitation systems. The regulator is supplied from a source, such as a permanent magnet generator, which is not affected by system disturbances. Unlike other AC models, this model uses loaded rather than open circuit exciter saturation data in the same way as it is used for the DC models. Because the model has been widely implemented by the industry, it is sometimes used to represent other types of systems when either detailed data for them are not available or simplified models are required. Reference: IEEE 421.5-2005, 6.5.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Dataset containing the data objects. |
||
1 |
Synchronous machine model with which this excitation system model is associated. |
||
1 |
Voltage compensator model associated with this excitation system model. |
||
0..1 |
Exciter voltage at which exciter saturation is defined (EFD1) (> 0). Typical value = 5,6. |
||
0..1 |
Exciter voltage at which exciter saturation is defined (EFD2) (> 0). Typical value = 4,2. |
||
0..1 |
Voltage regulator gain (KA) (> 0). Typical value = 400. |
||
0..1 |
Exciter constant related to self-excited field (KE). Typical value = 1. |
||
0..1 |
Excitation control system stabilizer gains (KF) (>= 0). Typical value = 0,03. |
||
0..1 |
Exciter saturation function value at the corresponding exciter voltage, EFD1 (SE[EFD1]) (>= 0). Typical value = 0,86. |
||
0..1 |
Exciter saturation function value at the corresponding exciter voltage, EFD2 (SE[EFD2]) (>= 0). Typical value = 0,5. |
||
0..1 |
Voltage regulator time constant (TA) (> 0). Typical value = 0,02. |
||
0..1 |
Exciter time constant, integration rate associated with exciter control (TE) (> 0). Typical value = 0,8. |
||
0..1 |
Excitation control system stabilizer time constant (TF1) (> 0). Typical value = 1. |
||
0..1 |
Excitation control system stabilizer time constant (TF2) (>= 0). Typical value = 1. |
||
0..1 |
Excitation control system stabilizer time constant (TF3) (>= 0). Typical value = 1. |
||
0..1 |
Maximum voltage regulator output (VRMAX) (> 0). Typical value = 7,3. |
||
0..1 |
Minimum voltage regulator output (VRMIN) (< 0). Typical value = -7,3. |
||
0..1 |
Discontinuous excitation control model associated with this excitation system model. |
||
0..1 |
Overexcitation limiter model associated with this excitation system model. |
||
0..1 |
Power factor or VAr controller type 1 model associated with this excitation system model. |
||
0..1 |
Power factor or VAr controller type 2 model associated with this excitation system model. |
||
0..1 |
Power system stabilizer model associated with this excitation system model. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
Undrexcitation limiter model associated with this excitation system model. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
DiscontinuousExcitationControlDynamics
Discontinuous excitation control model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
efd1
Exciter voltage at which exciter saturation is defined (EFD1) (> 0). Typical value = 5,6.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
efd2
Exciter voltage at which exciter saturation is defined (EFD2) (> 0). Typical value = 4,2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
ka
Voltage regulator gain (KA) (> 0). Typical value = 400.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
ke
Exciter constant related to self-excited field (KE). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kf
Excitation control system stabilizer gains (KF) (>= 0). Typical value = 0,03.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
OverexcitationLimiterDynamics
Overexcitation limiter model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
PFVArControllerType1Dynamics
Power factor or VAr controller type 1 model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
PFVArControllerType2Dynamics
Power factor or VAr controller type 2 model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
PowerSystemStabilizerDynamics
Power system stabilizer model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
seefd1
Exciter saturation function value at the corresponding exciter voltage, EFD1 (SE[EFD1]) (>= 0). Typical value = 0,86.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
seefd2
Exciter saturation function value at the corresponding exciter voltage, EFD2 (SE[EFD2]) (>= 0). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
SynchronousMachineDynamics
Synchronous machine model with which this excitation system model is associated.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
ta
Voltage regulator time constant (TA) (> 0). Typical value = 0,02.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
te
Exciter time constant, integration rate associated with exciter control (TE) (> 0). Typical value = 0,8.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tf1
Excitation control system stabilizer time constant (TF1) (> 0). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tf2
Excitation control system stabilizer time constant (TF2) (>= 0). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tf3
Excitation control system stabilizer time constant (TF3) (>= 0). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
UnderexcitationLimiterDynamics
Undrexcitation limiter model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
VoltageCompensatorDynamics
Voltage compensator model associated with this excitation system model.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
vrmax
Maximum voltage regulator output (VRMAX) (> 0). Typical value = 7,3.
URI |
|
---|---|
Cardinality |
0..1 |
Type |