GovSteamCC
Cross compound turbine governor. Unlike tandem compound units, cross compound units are not on the same shaft.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
High-pressure synchronous machine with which this cross-compound turbine governor is associated. |
||
1 |
Dataset containing the data objects. |
||
1 |
Low-pressure synchronous machine with which this cross-compound turbine governor is associated. |
||
0..1 |
HP damping factor (Dhp). Typical value = 0. |
||
0..1 |
LP damping factor (Dlp). Typical value = 0. |
||
0..1 |
Fraction of HP power ahead of reheater (Fhp). Typical value = 0,3. |
||
0..1 |
Fraction of LP power ahead of reheater (Flp). Typical value = 0,7. |
||
0..1 |
Base for power values (MWbase) (> 0). Unit = MW. |
||
0..1 |
Maximum HP value position (Pmaxhp). Typical value = 1. |
||
0..1 |
Maximum LP value position (Pmaxlp). Typical value = 1. |
||
0..1 |
HP governor droop (Rhp) (> 0). Typical value = 0,05. |
||
0..1 |
LP governor droop (Rlp) (> 0). Typical value = 0,05. |
||
0..1 |
HP governor time constant (T1hp) (>= 0). Typical value = 0,1. |
||
0..1 |
LP governor time constant (T1lp) (>= 0). Typical value = 0,1. |
||
0..1 |
HP turbine time constant (T3hp) (>= 0). Typical value = 0,1. |
||
0..1 |
LP turbine time constant (T3lp) (>= 0). Typical value = 0,1. |
||
0..1 |
HP turbine time constant (T4hp) (>= 0). Typical value = 0,1. |
||
0..1 |
LP turbine time constant (T4lp) (>= 0). Typical value = 0,1. |
||
0..1 |
HP reheater time constant (T5hp) (>= 0). Typical value = 10. |
||
0..1 |
LP reheater time constant (T5lp) (>= 0). Typical value = 10. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
fhp
Fraction of HP power ahead of reheater (Fhp). Typical value = 0,3.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
flp
Fraction of LP power ahead of reheater (Flp). Typical value = 0,7.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
HighPressureSynchronousMachineDynamics
High-pressure synchronous machine with which this cross-compound turbine governor is associated.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
LowPressureSynchronousMachineDynamics
Low-pressure synchronous machine with which this cross-compound turbine governor is associated.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
mwbase
Base for power values (MWbase) (> 0). Unit = MW.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
pmaxhp
Maximum HP value position (Pmaxhp). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
pmaxlp
Maximum LP value position (Pmaxlp). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
rhp
HP governor droop (Rhp) (> 0). Typical value = 0,05.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
rlp
LP governor droop (Rlp) (> 0). Typical value = 0,05.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t1hp
HP governor time constant (T1hp) (>= 0). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t1lp
LP governor time constant (T1lp) (>= 0). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t3hp
HP turbine time constant (T3hp) (>= 0). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t3lp
LP turbine time constant (T3lp) (>= 0). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t4hp
HP turbine time constant (T4hp) (>= 0). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t4lp
LP turbine time constant (T4lp) (>= 0). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t5hp
HP reheater time constant (T5hp) (>= 0). Typical value = 10.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
t5lp
LP reheater time constant (T5lp) (>= 0). Typical value = 10.
URI |
|
---|---|
Cardinality |
0..1 |
Type |