LoadComposite
Combined static load and induction motor load effects. The dynamics of the motor are simplified by linearizing the induction machine equations.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Dataset containing the data objects. |
||
0..1 |
Active load-frequency dependence index (dynamic) (Epfd). Typical value = 1,5. |
||
0..1 |
Active load-frequency dependence index (static) (Epfs). Typical value = 1,5. |
||
0..1 |
Active load-voltage dependence index (dynamic) (Epvd). Typical value = 0,7. |
||
0..1 |
Active load-voltage dependence index (static) (Epvs). Typical value = 0,7. |
||
0..1 |
Reactive load-frequency dependence index (dynamic) (Eqfd). Typical value = 0. |
||
0..1 |
Reactive load-frequency dependence index (static) (Eqfs). Typical value = 0. |
||
0..1 |
Reactive load-voltage dependence index (dynamic) (Eqvd). Typical value = 2. |
||
0..1 |
Reactive load-voltage dependence index (static) (Eqvs). Typical value = 2. |
||
0..1 |
Inertia constant (H) (>= 0). Typical value = 2,5. |
||
0..1 |
Loading factor (Lfac). The ratio of initial P to motor MVA base. Typical value = 0,8. |
||
0..1 |
Fraction of constant-power load to be represented by this motor model (PFRAC) (>= 0,0 and <= 1,0). Typical value = 0,5. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
Energy consumer to which this dynamics load model applies. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
EnergyConsumer
Energy consumer to which this dynamics load model applies.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
epfd
Active load-frequency dependence index (dynamic) (Epfd). Typical value = 1,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
epfs
Active load-frequency dependence index (static) (Epfs). Typical value = 1,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
epvd
Active load-voltage dependence index (dynamic) (Epvd). Typical value = 0,7.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
epvs
Active load-voltage dependence index (static) (Epvs). Typical value = 0,7.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
eqfd
Reactive load-frequency dependence index (dynamic) (Eqfd). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
eqfs
Reactive load-frequency dependence index (static) (Eqfs). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
eqvd
Reactive load-voltage dependence index (dynamic) (Eqvd). Typical value = 2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
eqvs
Reactive load-voltage dependence index (static) (Eqvs). Typical value = 2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
lfac
Loading factor (Lfac). The ratio of initial P to motor MVA base. Typical value = 0,8.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
pfrac
Fraction of constant-power load to be represented by this motor model (PFRAC) (>= 0,0 and <= 1,0). Typical value = 0,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |