GovGAST3

Generic turbogas with acceleration and temperature controller.

Type

Class

URI

cim:GovGAST3

CIM standard (perspective)

IEC61970 (Grid)

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

InstanceSet

1

InstanceSet

Dataset containing the data objects.

bca

0..1

float

Acceleration limit set-point (Bca). Unit = 1/s. Typical value = 0,01.

bp

0..1

PU

Droop (bp). Typical value = 0,05.

dtc

0..1

Temperature

Exhaust temperature variation due to fuel flow increasing from 0 to 1 PU (deltaTc). Typical value = 390.

ka

0..1

PU

Minimum fuel flow (Ka). Typical value = 0,23.

kac

0..1

float

Fuel system feedback (KAC). Typical value = 0.

kca

0..1

float

Acceleration control integral gain (Kca). Unit = 1/s. Typical value = 100.

ksi

0..1

float

Gain of radiation shield (Ksi). Typical value = 0,8.

ky

0..1

float

Coefficient of transfer function of fuel valve positioner (Ky). Typical value = 1.

mnef

0..1

PU

Fuel flow maximum negative error value (MNef). Typical value = -0,05.

mxef

0..1

PU

Fuel flow maximum positive error value (MXef). Typical value = 0,05.

rcmn

0..1

PU

Minimum fuel flow (RCMN). Typical value = -0,1.

rcmx

0..1

PU

Maximum fuel flow (RCMX). Typical value = 1.

tac

0..1

Seconds

Fuel control time constant (Tac) (>= 0). Typical value = 0,1.

tc

0..1

Seconds

Compressor discharge volume time constant (Tc) (>= 0). Typical value = 0,2.

td

0..1

Seconds

Temperature controller derivative gain (Td) (>= 0). Typical value = 3,3.

tfen

0..1

Temperature

Turbine rated exhaust temperature correspondent to Pm=1 PU (Tfen). Typical value = 540.

tg

0..1

Seconds

Time constant of speed governor (Tg) (>= 0). Typical value = 0,05.

tsi

0..1

Seconds

Time constant of radiation shield (Tsi) (>= 0). Typical value = 15.

tt

0..1

Temperature

Temperature controller integration rate (Tt). Typical value = 250.

ttc

0..1

Seconds

Time constant of thermocouple (Ttc) (>= 0). Typical value = 2,5.

ty

0..1

Seconds

Time constant of fuel valve positioner (Ty) (>= 0). Typical value = 0,2.

AsynchronousMachineDynamics

0..1

AsynchronousMachineDynamics

Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

SynchronousMachineDynamics

0..1

SynchronousMachineDynamics

Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

TurbineLoadControllerDynamics

0..1

TurbineLoadControllerDynamics

Turbine load controller providing input to this turbine-governor.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

enabled

0..1

boolean

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

AsynchronousMachineDynamics

Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

URI

cim:TurbineGovernorDynamics.AsynchronousMachineDynamics

Cardinality

0..1

Type

AsynchronousMachineDynamics

Inherited from

TurbineGovernorDynamics

bca

Acceleration limit set-point (Bca). Unit = 1/s. Typical value = 0,01.

URI

cim:GovGAST3.bca

Cardinality

0..1

Type

float

bp

Droop (bp). Typical value = 0,05.

URI

cim:GovGAST3.bp

Cardinality

0..1

Type

PU

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

dtc

Exhaust temperature variation due to fuel flow increasing from 0 to 1 PU (deltaTc). Typical value = 390.

URI

cim:GovGAST3.dtc

Cardinality

0..1

Type

Temperature

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

URI

cim:DynamicsFunctionBlock.enabled

Cardinality

0..1

Type

boolean

Inherited from

DynamicsFunctionBlock

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

ka

Minimum fuel flow (Ka). Typical value = 0,23.

URI

cim:GovGAST3.ka

Cardinality

0..1

Type

PU

kac

Fuel system feedback (KAC). Typical value = 0.

URI

cim:GovGAST3.kac

Cardinality

0..1

Type

float

kca

Acceleration control integral gain (Kca). Unit = 1/s. Typical value = 100.

URI

cim:GovGAST3.kca

Cardinality

0..1

Type

float

ksi

Gain of radiation shield (Ksi). Typical value = 0,8.

URI

cim:GovGAST3.ksi

Cardinality

0..1

Type

float

ky

Coefficient of transfer function of fuel valve positioner (Ky). Typical value = 1.

URI

cim:GovGAST3.ky

Cardinality

0..1

Type

float

mnef

Fuel flow maximum negative error value (MNef). Typical value = -0,05.

URI

cim:GovGAST3.mnef

Cardinality

0..1

Type

PU

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

mxef

Fuel flow maximum positive error value (MXef). Typical value = 0,05.

URI

cim:GovGAST3.mxef

Cardinality

0..1

Type

PU

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

rcmn

Minimum fuel flow (RCMN). Typical value = -0,1.

URI

cim:GovGAST3.rcmn

Cardinality

0..1

Type

PU

rcmx

Maximum fuel flow (RCMX). Typical value = 1.

URI

cim:GovGAST3.rcmx

Cardinality

0..1

Type

PU

SynchronousMachineDynamics

Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.

URI

cim:TurbineGovernorDynamics.SynchronousMachineDynamics

Cardinality

0..1

Type

SynchronousMachineDynamics

Inherited from

TurbineGovernorDynamics

tac

Fuel control time constant (Tac) (>= 0). Typical value = 0,1.

URI

cim:GovGAST3.tac

Cardinality

0..1

Type

Seconds

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

tc

Compressor discharge volume time constant (Tc) (>= 0). Typical value = 0,2.

URI

cim:GovGAST3.tc

Cardinality

0..1

Type

Seconds

td

Temperature controller derivative gain (Td) (>= 0). Typical value = 3,3.

URI

cim:GovGAST3.td

Cardinality

0..1

Type

Seconds

tfen

Turbine rated exhaust temperature correspondent to Pm=1 PU (Tfen). Typical value = 540.

URI

cim:GovGAST3.tfen

Cardinality

0..1

Type

Temperature

tg

Time constant of speed governor (Tg) (>= 0). Typical value = 0,05.

URI

cim:GovGAST3.tg

Cardinality

0..1

Type

Seconds

tsi

Time constant of radiation shield (Tsi) (>= 0). Typical value = 15.

URI

cim:GovGAST3.tsi

Cardinality

0..1

Type

Seconds

tt

Temperature controller integration rate (Tt). Typical value = 250.

URI

cim:GovGAST3.tt

Cardinality

0..1

Type

Temperature

ttc

Time constant of thermocouple (Ttc) (>= 0). Typical value = 2,5.

URI

cim:GovGAST3.ttc

Cardinality

0..1

Type

Seconds

TurbineLoadControllerDynamics

Turbine load controller providing input to this turbine-governor.

URI

cim:TurbineGovernorDynamics.TurbineLoadControllerDynamics

Cardinality

0..1

Type

TurbineLoadControllerDynamics

Inherited from

TurbineGovernorDynamics

ty

Time constant of fuel valve positioner (Ty) (>= 0). Typical value = 0,2.

URI

cim:GovGAST3.ty

Cardinality

0..1

Type

Seconds