WindPlantFreqPcontrolIEC

Frequency and active power controller model. Reference: IEC 61400-27-1:2015, Annex D.

Type

Class

URI

cim:WindPlantFreqPcontrolIEC

CIM standard (perspective)

IEC61970 (Grid)

Class hierarchy

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

WindPlantIEC

1

WindPlantIEC

Wind plant model with which this wind plant frequency and active power control is associated.

WindDynamicsLookupTable

1..*

WindDynamicsLookupTable

The wind dynamics lookup table associated with this frequency and active power wind plant model.

InstanceSet

1

InstanceSet

Dataset containing the data objects.

dprefmax

0..1

PU

Maximum ramp rate of pWTref request from the plant controller to the wind turbines (dprefmax) (> WindPlantFreqPcontrolIEC.dprefmin). It is a case-dependent parameter.

dprefmin

0..1

PU

Minimum (negative) ramp rate of pWTref request from the plant controller to the wind turbines (dprefmin) (< WindPlantFreqPcontrolIEC.dprefmax). It is a project-dependent parameter.

dpwprefmax

0..1

PU

Maximum positive ramp rate for wind plant power reference (dpWPrefmax) (> WindPlantFreqPcontrolIEC.dpwprefmin). It is a project-dependent parameter.

dpwprefmin

0..1

PU

Maximum negative ramp rate for wind plant power reference (dpWPrefmin) (< WindPlantFreqPcontrolIEC.dpwprefmax). It is a project-dependent parameter.

kiwpp

0..1

float

Plant P controller integral gain (KIWPp). It is a project-dependent parameter.

kiwppmax

0..1

PU

Maximum PI integrator term (KIWPpmax) (> WindPlantFreqPcontrolIEC.kiwppmin). It is a project-dependent parameter.

kiwppmin

0..1

PU

Minimum PI integrator term (KIWPpmin) (< WindPlantFreqPcontrolIEC.kiwppmax). It is a project-dependent parameter.

kpwpp

0..1

float

Plant P controller proportional gain (KPWPp). It is a project-dependent parameter.

kwppref

0..1

PU

Power reference gain (KWPpref). It is a project-dependent parameter.

prefmax

0..1

PU

Maximum pWTref request from the plant controller to the wind turbines (prefmax) (> WindPlantFreqPcontrolIEC.prefmin). It is a project-dependent parameter.

prefmin

0..1

PU

Minimum pWTref request from the plant controller to the wind turbines (prefmin) (< WindPlantFreqPcontrolIEC.prefmax). It is a project-dependent parameter.

tpft

0..1

Seconds

Lead time constant in reference value transfer function (Tpft) (>= 0). It is a project-dependent parameter.

tpfv

0..1

Seconds

Lag time constant in reference value transfer function (Tpfv) (>= 0). It is a project-dependent parameter.

twpffiltp

0..1

Seconds

Filter time constant for frequency measurement (TWPffiltp) (>= 0). It is a project-dependent parameter.

twppfiltp

0..1

Seconds

Filter time constant for active power measurement (TWPpfiltp) (>= 0). It is a project-dependent parameter.

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

dprefmax

Maximum ramp rate of pWTref request from the plant controller to the wind turbines (dprefmax) (> WindPlantFreqPcontrolIEC.dprefmin). It is a case-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.dprefmax

Cardinality

0..1

Type

PU

dprefmin

Minimum (negative) ramp rate of pWTref request from the plant controller to the wind turbines (dprefmin) (< WindPlantFreqPcontrolIEC.dprefmax). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.dprefmin

Cardinality

0..1

Type

PU

dpwprefmax

Maximum positive ramp rate for wind plant power reference (dpWPrefmax) (> WindPlantFreqPcontrolIEC.dpwprefmin). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.dpwprefmax

Cardinality

0..1

Type

PU

dpwprefmin

Maximum negative ramp rate for wind plant power reference (dpWPrefmin) (< WindPlantFreqPcontrolIEC.dpwprefmax). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.dpwprefmin

Cardinality

0..1

Type

PU

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

kiwpp

Plant P controller integral gain (KIWPp). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.kiwpp

Cardinality

0..1

Type

float

kiwppmax

Maximum PI integrator term (KIWPpmax) (> WindPlantFreqPcontrolIEC.kiwppmin). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.kiwppmax

Cardinality

0..1

Type

PU

kiwppmin

Minimum PI integrator term (KIWPpmin) (< WindPlantFreqPcontrolIEC.kiwppmax). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.kiwppmin

Cardinality

0..1

Type

PU

kpwpp

Plant P controller proportional gain (KPWPp). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.kpwpp

Cardinality

0..1

Type

float

kwppref

Power reference gain (KWPpref). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.kwppref

Cardinality

0..1

Type

PU

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

prefmax

Maximum pWTref request from the plant controller to the wind turbines (prefmax) (> WindPlantFreqPcontrolIEC.prefmin). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.prefmax

Cardinality

0..1

Type

PU

prefmin

Minimum pWTref request from the plant controller to the wind turbines (prefmin) (< WindPlantFreqPcontrolIEC.prefmax). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.prefmin

Cardinality

0..1

Type

PU

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

tpft

Lead time constant in reference value transfer function (Tpft) (>= 0). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.tpft

Cardinality

0..1

Type

Seconds

tpfv

Lag time constant in reference value transfer function (Tpfv) (>= 0). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.tpfv

Cardinality

0..1

Type

Seconds

twpffiltp

Filter time constant for frequency measurement (TWPffiltp) (>= 0). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.twpffiltp

Cardinality

0..1

Type

Seconds

twppfiltp

Filter time constant for active power measurement (TWPpfiltp) (>= 0). It is a project-dependent parameter.

URI

cim:WindPlantFreqPcontrolIEC.twppfiltp

Cardinality

0..1

Type

Seconds

WindDynamicsLookupTable

The wind dynamics lookup table associated with this frequency and active power wind plant model.

URI

cim:WindPlantFreqPcontrolIEC.WindDynamicsLookupTable

Cardinality

1..*

Type

WindDynamicsLookupTable

WindPlantIEC

Wind plant model with which this wind plant frequency and active power control is associated.

URI

cim:WindPlantFreqPcontrolIEC.WindPlantIEC

Cardinality

1

Type