TurbLCFB1

Turbine load controller model developed by WECC. This model represents a supervisory turbine load controller that acts to maintain turbine power at a set value by continuous adjustment of the turbine governor speed-load reference. This model is intended to represent slow reset 'outer loop' controllers managing the action of the turbine governor.

Type

Class

URI

cim:TurbLCFB1

CIM standard (perspective)

IEC61970 (Grid)

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

InstanceSet

1

InstanceSet

Dataset containing the data objects.

TurbineGovernorDynamics

1

TurbineGovernorDynamics

Turbine-governor controlled by this turbine load controller.

db

0..1

PU

Controller deadband (db). Typical value = 0.

emax

0..1

PU

Maximum control error (Emax) (see parameter detail 4). Typical value = 0,02.

fb

0..1

PU

Frequency bias gain (Fb). Typical value = 0.

fbf

0..1

boolean

Frequency bias flag (Fbf). true = enable frequency bias false = disable frequency bias. Typical value = false.

irmax

0..1

PU

Maximum turbine speed/load reference bias (Irmax) (see parameter detail 3). Typical value = 0.

ki

0..1

PU

Integral gain (Ki). Typical value = 0.

kp

0..1

PU

Proportional gain (Kp). Typical value = 0.

mwbase

0..1

ActivePower

Base for power values (MWbase) (> 0). Unit = MW.

pbf

0..1

boolean

Power controller flag (Pbf). true = enable load controller false = disable load controller. Typical value = false.

pmwset

0..1

ActivePower

Power controller setpoint (Pmwset) (see parameter detail 1). Unit = MW. Typical value = 0.

speedReferenceGovernor

0..1

boolean

Type of turbine governor reference (Type). true = speed reference governor false = load reference governor. Typical value = true.

tpelec

0..1

Seconds

Power transducer time constant (Tpelec) (>= 0). Typical value = 0.

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

enabled

0..1

boolean

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

db

Controller deadband (db). Typical value = 0.

URI

cim:TurbLCFB1.db

Cardinality

0..1

Type

PU

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

emax

Maximum control error (Emax) (see parameter detail 4). Typical value = 0,02.

URI

cim:TurbLCFB1.emax

Cardinality

0..1

Type

PU

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

URI

cim:DynamicsFunctionBlock.enabled

Cardinality

0..1

Type

boolean

Inherited from

DynamicsFunctionBlock

fb

Frequency bias gain (Fb). Typical value = 0.

URI

cim:TurbLCFB1.fb

Cardinality

0..1

Type

PU

fbf

Frequency bias flag (Fbf). true = enable frequency bias false = disable frequency bias. Typical value = false.

URI

cim:TurbLCFB1.fbf

Cardinality

0..1

Type

boolean

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

irmax

Maximum turbine speed/load reference bias (Irmax) (see parameter detail 3). Typical value = 0.

URI

cim:TurbLCFB1.irmax

Cardinality

0..1

Type

PU

ki

Integral gain (Ki). Typical value = 0.

URI

cim:TurbLCFB1.ki

Cardinality

0..1

Type

PU

kp

Proportional gain (Kp). Typical value = 0.

URI

cim:TurbLCFB1.kp

Cardinality

0..1

Type

PU

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

mwbase

Base for power values (MWbase) (> 0). Unit = MW.

URI

cim:TurbLCFB1.mwbase

Cardinality

0..1

Type

ActivePower

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

pbf

Power controller flag (Pbf). true = enable load controller false = disable load controller. Typical value = false.

URI

cim:TurbLCFB1.pbf

Cardinality

0..1

Type

boolean

pmwset

Power controller setpoint (Pmwset) (see parameter detail 1). Unit = MW. Typical value = 0.

URI

cim:TurbLCFB1.pmwset

Cardinality

0..1

Type

ActivePower

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

speedReferenceGovernor

Type of turbine governor reference (Type). true = speed reference governor false = load reference governor. Typical value = true.

URI

cim:TurbLCFB1.speedReferenceGovernor

Cardinality

0..1

Type

boolean

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

tpelec

Power transducer time constant (Tpelec) (>= 0). Typical value = 0.

URI

cim:TurbLCFB1.tpelec

Cardinality

0..1

Type

Seconds

TurbineGovernorDynamics

Turbine-governor controlled by this turbine load controller.

URI

cim:TurbineLoadControllerDynamics.TurbineGovernorDynamics

Cardinality

1

Type

TurbineGovernorDynamics

Inherited from

TurbineLoadControllerDynamics