GovCT2
General governor with frequency-dependent fuel flow limit. This model is a modification of the GovCT1 model in order to represent the frequency-dependent fuel flow limit of a specific gas turbine manufacturer.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Dataset containing the data objects. |
||
0..1 |
Acceleration limiter setpoint (Aset). Unit = PU / s. Typical value = 10. |
||
0..1 |
Speed governor deadband in PU speed (db). In the majority of applications, it is recommended that this value be set to zero. Typical value = 0. |
||
0..1 |
Speed sensitivity coefficient (Dm). Dm can represent either the variation of the engine power with the shaft speed or the variation of maximum power capability with shaft speed. If it is positive it describes the falling slope of the engine speed verses power characteristic as speed increases. A slightly falling characteristic is typical for reciprocating engines and some aero-derivative turbines. If it is negative the engine power is assumed to be unaffected by the shaft speed, but the maximum permissible fuel flow is taken to fall with falling shaft speed. This is characteristic of single-shaft industrial turbines due to exhaust temperature limits. Typical value = 0. |
||
0..1 |
Frequency threshold 1 (Flim1). Unit = Hz. Typical value = 59. |
||
0..1 |
Frequency threshold 10 (Flim10). Unit = Hz. Typical value = 0. |
||
0..1 |
Frequency threshold 2 (Flim2). Unit = Hz. Typical value = 0. |
||
0..1 |
Frequency threshold 3 (Flim3). Unit = Hz. Typical value = 0. |
||
0..1 |
Frequency threshold 4 (Flim4). Unit = Hz. Typical value = 0. |
||
0..1 |
Frequency threshold 5 (Flim5). Unit = Hz. Typical value = 0. |
||
0..1 |
Frequency threshold 6 (Flim6). Unit = Hz. Typical value = 0. |
||
0..1 |
Frequency threshold 7 (Flim7). Unit = Hz. Typical value = 0. |
||
0..1 |
Frequency threshold 8 (Flim8). Unit = Hz. Typical value = 0. |
||
0..1 |
Frequency threshold 9 (Flim9). Unit = Hz. Typical value = 0. |
||
0..1 |
Acceleration limiter gain (Ka). Typical value = 10. |
||
0..1 |
Governor derivative gain (Kdgov). Typical value = 0. |
||
0..1 |
Governor integral gain (Kigov). Typical value = 0,45. |
||
0..1 |
Load limiter integral gain for PI controller (Kiload). Typical value = 1. |
||
0..1 |
Power controller (reset) gain (Kimw). The default value of 0,01 corresponds to a reset time of 100 seconds. A value of 0,001 corresponds to a relatively slow-acting load controller. Typical value = 0. |
||
0..1 |
Governor proportional gain (Kpgov). Typical value = 4. |
||
0..1 |
Load limiter proportional gain for PI controller (Kpload). Typical value = 1. |
||
0..1 |
Turbine gain (Kturb). Typical value = 1,9168. |
||
0..1 |
Load limiter reference value (Ldref). Typical value = 1. |
||
0..1 |
Maximum value for speed error signal (Maxerr) (> GovCT2.minerr). Typical value = 1. |
||
0..1 |
Minimum value for speed error signal (Minerr) (< GovCT2.maxerr). Typical value = -1. |
||
0..1 |
Base for power values (MWbase) (> 0). Unit = MW. |
||
0..1 |
Power limit 1 (Plim1). Typical value = 0,8325. |
||
0..1 |
Power limit 10 (Plim10). Typical value = 0. |
||
0..1 |
Power limit 2 (Plim2). Typical value = 0. |
||
0..1 |
Power limit 3 (Plim3). Typical value = 0. |
||
0..1 |
Power limit 4 (Plim4). Typical value = 0. |
||
0..1 |
Power limit 5 (Plim5). Typical value = 0. |
||
0..1 |
Power limit 6 (Plim6). Typical value = 0. |
||
0..1 |
Power limit 7 (Plim7). Typical value = 0. |
||
0..1 |
Power limit 8 (Plim8). Typical value = 0. |
||
0..1 |
Power Limit 9 (Plim9). Typical value = 0. |
||
0..1 |
Ramp rate for frequency-dependent power limit (Prate). Typical value = 0,017. |
||
0..1 |
Permanent droop (R). Typical value = 0,05. |
||
0..1 |
Minimum valve closing rate (Rclose). Unit = PU / s. Typical value = -99. |
||
0..1 |
Maximum rate of load limit decrease (Rdown). Typical value = -99. |
||
0..1 |
Maximum valve opening rate (Ropen). Unit = PU / s. Typical value = 99. |
||
0..1 |
Feedback signal for droop (Rselect). Typical value = electricalPower. |
||
0..1 |
Maximum rate of load limit increase (Rup). Typical value = 99. |
||
0..1 |
Acceleration limiter time constant (Ta) (>= 0). Typical value = 1. |
||
0..1 |
Actuator time constant (Tact) (>= 0). Typical value = 0,4. |
||
0..1 |
Turbine lag time constant (Tb) (>= 0). Typical value = 0,1. |
||
0..1 |
Turbine lead time constant (Tc) (>= 0). Typical value = 0. |
||
0..1 |
Governor derivative controller time constant (Tdgov) (>= 0). Typical value = 1. |
||
0..1 |
Transport time delay for diesel engine used in representing diesel engines where there is a small but measurable transport delay between a change in fuel flow setting and the development of torque (Teng) (>= 0). Teng should be zero in all but special cases where this transport delay is of particular concern. Typical value = 0. |
||
0..1 |
Load limiter time constant (Tfload) (>= 0). Typical value = 3. |
||
0..1 |
Electrical power transducer time constant (Tpelec) (>= 0). Typical value = 2,5. |
||
0..1 |
Temperature detection lead time constant (Tsa) (>= 0). Typical value = 0. |
||
0..1 |
Temperature detection lag time constant (Tsb) (>= 0). Typical value = 50. |
||
0..1 |
Maximum valve position limit (Vmax) (> GovCT2.vmin). Typical value = 1. |
||
0..1 |
Minimum valve position limit (Vmin) (< GovCT2.vmax). Typical value = 0,175. |
||
0..1 |
No load fuel flow (Wfnl). Typical value = 0,187. |
||
0..1 |
Switch for fuel source characteristic to recognize that fuel flow, for a given fuel valve stroke, can be proportional to engine speed (Wfspd). true = fuel flow proportional to speed (for some gas turbines and diesel engines with positive displacement fuel injectors) false = fuel control system keeps fuel flow independent of engine speed. Typical value = false. |
||
0..1 |
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
Turbine load controller providing input to this turbine-governor. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
aset
Acceleration limiter setpoint (Aset). Unit = PU / s. Typical value = 10.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
db
Speed governor deadband in PU speed (db). In the majority of applications, it is recommended that this value be set to zero. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
dm
Speed sensitivity coefficient (Dm). Dm can represent either the variation of the engine power with the shaft speed or the variation of maximum power capability with shaft speed. If it is positive it describes the falling slope of the engine speed verses power characteristic as speed increases. A slightly falling characteristic is typical for reciprocating engines and some aero-derivative turbines. If it is negative the engine power is assumed to be unaffected by the shaft speed, but the maximum permissible fuel flow is taken to fall with falling shaft speed. This is characteristic of single-shaft industrial turbines due to exhaust temperature limits. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
flim1
Frequency threshold 1 (Flim1). Unit = Hz. Typical value = 59.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
flim10
Frequency threshold 10 (Flim10). Unit = Hz. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
flim2
Frequency threshold 2 (Flim2). Unit = Hz. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
flim3
Frequency threshold 3 (Flim3). Unit = Hz. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
flim4
Frequency threshold 4 (Flim4). Unit = Hz. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
flim5
Frequency threshold 5 (Flim5). Unit = Hz. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
flim6
Frequency threshold 6 (Flim6). Unit = Hz. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
flim7
Frequency threshold 7 (Flim7). Unit = Hz. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
flim8
Frequency threshold 8 (Flim8). Unit = Hz. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
flim9
Frequency threshold 9 (Flim9). Unit = Hz. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
kdgov
Governor derivative gain (Kdgov). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kigov
Governor integral gain (Kigov). Typical value = 0,45.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kiload
Load limiter integral gain for PI controller (Kiload). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kimw
Power controller (reset) gain (Kimw). The default value of 0,01 corresponds to a reset time of 100 seconds. A value of 0,001 corresponds to a relatively slow-acting load controller. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kpgov
Governor proportional gain (Kpgov). Typical value = 4.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kpload
Load limiter proportional gain for PI controller (Kpload). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
ldref
Load limiter reference value (Ldref). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
maxerr
Maximum value for speed error signal (Maxerr) (> GovCT2.minerr). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
minerr
Minimum value for speed error signal (Minerr) (< GovCT2.maxerr). Typical value = -1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
prate
Ramp rate for frequency-dependent power limit (Prate). Typical value = 0,017.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
rclose
Minimum valve closing rate (Rclose). Unit = PU / s. Typical value = -99.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
rdown
Maximum rate of load limit decrease (Rdown). Typical value = -99.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
ropen
Maximum valve opening rate (Ropen). Unit = PU / s. Typical value = 99.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
rselect
Feedback signal for droop (Rselect). Typical value = electricalPower.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
rup
Maximum rate of load limit increase (Rup). Typical value = 99.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
SynchronousMachineDynamics
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
ta
Acceleration limiter time constant (Ta) (>= 0). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tact
Actuator time constant (Tact) (>= 0). Typical value = 0,4.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
tb
Turbine lag time constant (Tb) (>= 0). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tc
Turbine lead time constant (Tc) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tdgov
Governor derivative controller time constant (Tdgov) (>= 0). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
teng
Transport time delay for diesel engine used in representing diesel engines where there is a small but measurable transport delay between a change in fuel flow setting and the development of torque (Teng) (>= 0). Teng should be zero in all but special cases where this transport delay is of particular concern. Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tfload
Load limiter time constant (Tfload) (>= 0). Typical value = 3.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tpelec
Electrical power transducer time constant (Tpelec) (>= 0). Typical value = 2,5.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tsa
Temperature detection lead time constant (Tsa) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tsb
Temperature detection lag time constant (Tsb) (>= 0). Typical value = 50.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TurbineLoadControllerDynamics
Turbine load controller providing input to this turbine-governor.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
vmax
Maximum valve position limit (Vmax) (> GovCT2.vmin). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vmin
Minimum valve position limit (Vmin) (< GovCT2.vmax). Typical value = 0,175.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
wfspd
Switch for fuel source characteristic to recognize that fuel flow, for a given fuel valve stroke, can be proportional to engine speed (Wfspd). true = fuel flow proportional to speed (for some gas turbines and diesel engines with positive displacement fuel injectors) false = fuel control system keeps fuel flow independent of engine speed. Typical value = false.
URI |
|
---|---|
Cardinality |
0..1 |
Type |