ExcIEEEDC3A

IEEE 421.5-2005 type DC3A model. This model represents older systems, in particular those DC commutator exciters with non-continuously acting regulators that were commonly used before the development of the continuously acting varieties. These systems respond at basically two different rates, depending upon the magnitude of voltage error. For small errors, adjustment is made periodically with a signal to a motor-operated rheostat. Larger errors cause resistors to be quickly shorted or inserted and a strong forcing signal applied to the exciter. Continuous motion of the motor-operated rheostat occurs for these larger error signals, even though it is bypassed by contactor action. Reference: IEEE 421.5-2005, 5.3.

Type

Class

URI

cim:ExcIEEEDC3A

CIM standard (perspective)

IEC61970 (Grid)

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

InstanceSet

1

InstanceSet

Dataset containing the data objects.

SynchronousMachineDynamics

1

SynchronousMachineDynamics

Synchronous machine model with which this excitation system model is associated.

VoltageCompensatorDynamics

1

VoltageCompensatorDynamics

Voltage compensator model associated with this excitation system model.

efd1

0..1

PU

Exciter voltage at which exciter saturation is defined (EFD1) (> 0). Typical value = 3,375.

efd2

0..1

PU

Exciter voltage at which exciter saturation is defined (EFD2) (> 0). Typical value = 3,15.

exclim

0..1

boolean

(exclim). IEEE standard is ambiguous about lower limit on exciter output. true = a lower limit of zero is applied to integrator output false = a lower limit of zero is not applied to integrator output. Typical value = true.

ke

0..1

PU

Exciter constant related to self-excited field (KE). Typical value = 0,05.

kv

0..1

PU

Fast raise/lower contact setting (KV) (> 0). Typical value = 0,05.

seefd1

0..1

float

Exciter saturation function value at the corresponding exciter voltage, EFD1 (SE[EFD1]) (>= 0). Typical value = 0,267.

seefd2

0..1

float

Exciter saturation function value at the corresponding exciter voltage, EFD2 (SE[EFD2]) (>= 0). Typical value = 0,068.

te

0..1

Seconds

Exciter time constant, integration rate associated with exciter control (TE) (> 0). Typical value = 0,5.

trh

0..1

Seconds

Rheostat travel time (TRH) (> 0). Typical value = 20.

vrmax

0..1

PU

Maximum voltage regulator output (VRMAX) (> 0). Typical value = 1.

vrmin

0..1

PU

Minimum voltage regulator output (VRMIN) (<= 0). Typical value = 0.

DiscontinuousExcitationControlDynamics

0..1

DiscontinuousExcitationControlDynamics

Discontinuous excitation control model associated with this excitation system model.

OverexcitationLimiterDynamics

0..1

OverexcitationLimiterDynamics

Overexcitation limiter model associated with this excitation system model.

PFVArControllerType1Dynamics

0..1

PFVArControllerType1Dynamics

Power factor or VAr controller type 1 model associated with this excitation system model.

PFVArControllerType2Dynamics

0..1

PFVArControllerType2Dynamics

Power factor or VAr controller type 2 model associated with this excitation system model.

PowerSystemStabilizerDynamics

0..1

PowerSystemStabilizerDynamics

Power system stabilizer model associated with this excitation system model.

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

UnderexcitationLimiterDynamics

0..1

UnderexcitationLimiterDynamics

Undrexcitation limiter model associated with this excitation system model.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

enabled

0..1

boolean

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

DiscontinuousExcitationControlDynamics

Discontinuous excitation control model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.DiscontinuousExcitationControlDynamics

Cardinality

0..1

Type

DiscontinuousExcitationControlDynamics

Inherited from

ExcitationSystemDynamics

efd1

Exciter voltage at which exciter saturation is defined (EFD1) (> 0). Typical value = 3,375.

URI

cim:ExcIEEEDC3A.efd1

Cardinality

0..1

Type

PU

efd2

Exciter voltage at which exciter saturation is defined (EFD2) (> 0). Typical value = 3,15.

URI

cim:ExcIEEEDC3A.efd2

Cardinality

0..1

Type

PU

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

URI

cim:DynamicsFunctionBlock.enabled

Cardinality

0..1

Type

boolean

Inherited from

DynamicsFunctionBlock

exclim

(exclim). IEEE standard is ambiguous about lower limit on exciter output. true = a lower limit of zero is applied to integrator output false = a lower limit of zero is not applied to integrator output. Typical value = true.

URI

cim:ExcIEEEDC3A.exclim

Cardinality

0..1

Type

boolean

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

ke

Exciter constant related to self-excited field (KE). Typical value = 0,05.

URI

cim:ExcIEEEDC3A.ke

Cardinality

0..1

Type

PU

kv

Fast raise/lower contact setting (KV) (> 0). Typical value = 0,05.

URI

cim:ExcIEEEDC3A.kv

Cardinality

0..1

Type

PU

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

OverexcitationLimiterDynamics

Overexcitation limiter model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.OverexcitationLimiterDynamics

Cardinality

0..1

Type

OverexcitationLimiterDynamics

Inherited from

ExcitationSystemDynamics

PFVArControllerType1Dynamics

Power factor or VAr controller type 1 model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.PFVArControllerType1Dynamics

Cardinality

0..1

Type

PFVArControllerType1Dynamics

Inherited from

ExcitationSystemDynamics

PFVArControllerType2Dynamics

Power factor or VAr controller type 2 model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.PFVArControllerType2Dynamics

Cardinality

0..1

Type

PFVArControllerType2Dynamics

Inherited from

ExcitationSystemDynamics

PowerSystemStabilizerDynamics

Power system stabilizer model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.PowerSystemStabilizerDynamics

Cardinality

0..1

Type

PowerSystemStabilizerDynamics

Inherited from

ExcitationSystemDynamics

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

seefd1

Exciter saturation function value at the corresponding exciter voltage, EFD1 (SE[EFD1]) (>= 0). Typical value = 0,267.

URI

cim:ExcIEEEDC3A.seefd1

Cardinality

0..1

Type

float

seefd2

Exciter saturation function value at the corresponding exciter voltage, EFD2 (SE[EFD2]) (>= 0). Typical value = 0,068.

URI

cim:ExcIEEEDC3A.seefd2

Cardinality

0..1

Type

float

SynchronousMachineDynamics

Synchronous machine model with which this excitation system model is associated.

URI

cim:ExcitationSystemDynamics.SynchronousMachineDynamics

Cardinality

1

Type

SynchronousMachineDynamics

Inherited from

ExcitationSystemDynamics

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

te

Exciter time constant, integration rate associated with exciter control (TE) (> 0). Typical value = 0,5.

URI

cim:ExcIEEEDC3A.te

Cardinality

0..1

Type

Seconds

trh

Rheostat travel time (TRH) (> 0). Typical value = 20.

URI

cim:ExcIEEEDC3A.trh

Cardinality

0..1

Type

Seconds

UnderexcitationLimiterDynamics

Undrexcitation limiter model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.UnderexcitationLimiterDynamics

Cardinality

0..1

Type

UnderexcitationLimiterDynamics

Inherited from

ExcitationSystemDynamics

VoltageCompensatorDynamics

Voltage compensator model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.VoltageCompensatorDynamics

Cardinality

1

Type

VoltageCompensatorDynamics

Inherited from

ExcitationSystemDynamics

vrmax

Maximum voltage regulator output (VRMAX) (> 0). Typical value = 1.

URI

cim:ExcIEEEDC3A.vrmax

Cardinality

0..1

Type

PU

vrmin

Minimum voltage regulator output (VRMIN) (<= 0). Typical value = 0.

URI

cim:ExcIEEEDC3A.vrmin

Cardinality

0..1

Type

PU