ExcREXS

General purpose rotating excitation system. This model can be used to represent a wide range of excitation systems whose DC power source is an AC or DC generator. It encompasses IEEE type AC1, AC2, DC1, and DC2 excitation system models.

Type

Class

URI

cim:ExcREXS

CIM standard (perspective)

IEC61970 (Grid)

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

InstanceSet

1

InstanceSet

Dataset containing the data objects.

SynchronousMachineDynamics

1

SynchronousMachineDynamics

Synchronous machine model with which this excitation system model is associated.

VoltageCompensatorDynamics

1

VoltageCompensatorDynamics

Voltage compensator model associated with this excitation system model.

e1

0..1

PU

Field voltage value 1 (E1). Typical value = 3.

e2

0..1

PU

Field voltage value 2 (E2). Typical value = 4.

fbf

0..1

ExcREXSFeedbackSignalKind

Rate feedback signal flag (fbf). Typical value = fieldCurrent.

flimf

0..1

PU

Limit type flag (Flimf). Typical value = 0.

kc

0..1

PU

Rectifier regulation factor (Kc). Typical value = 0,05.

kd

0..1

PU

Exciter regulation factor (Kd). Typical value = 2.

ke

0..1

PU

Exciter field proportional constant (Ke). Typical value = 1.

kefd

0..1

PU

Field voltage feedback gain (Kefd). Typical value = 0.

kf

0..1

Seconds

Rate feedback gain (Kf) (>= 0). Typical value = 0,05.

kh

0..1

PU

Field voltage controller feedback gain (Kh). Typical value = 0.

kii

0..1

PU

Field current regulator integral gain (Kii). Typical value = 0.

kip

0..1

PU

Field current regulator proportional gain (Kip). Typical value = 1.

ks

0..1

PU

Coefficient to allow different usage of the model-speed coefficient (Ks). Typical value = 0.

kvi

0..1

PU

Voltage regulator integral gain (Kvi). Typical value = 0.

kvp

0..1

PU

Voltage regulator proportional gain (Kvp). Typical value = 2800.

kvphz

0..1

PU

V/Hz limiter gain (Kvphz). Typical value = 0.

nvphz

0..1

PU

Pickup speed of V/Hz limiter (Nvphz). Typical value = 0.

se1

0..1

PU

Saturation factor at E1 (Se1). Typical value = 0,0001.

se2

0..1

PU

Saturation factor at E2 (Se2). Typical value = 0,001.

ta

0..1

Seconds

Voltage regulator time constant (Ta) (>= 0). If = 0, block is bypassed. Typical value = 0,01.

tb1

0..1

Seconds

Lag time constant (Tb1) (>= 0). If = 0, block is bypassed. Typical value = 0.

tb2

0..1

Seconds

Lag time constant (Tb2) (>= 0). If = 0, block is bypassed. Typical value = 0.

tc1

0..1

Seconds

Lead time constant (Tc1) (>= 0). Typical value = 0.

tc2

0..1

Seconds

Lead time constant (Tc2) (>= 0). Typical value = 0.

te

0..1

Seconds

Exciter field time constant (Te) (> 0). Typical value = 1,2.

tf

0..1

Seconds

Rate feedback time constant (Tf) (>= 0). If = 0, the feedback path is not used. Typical value = 1.

tf1

0..1

Seconds

Feedback lead time constant (Tf1) (>= 0). Typical value = 0.

tf2

0..1

Seconds

Feedback lag time constant (Tf2) (>= 0). If = 0, block is bypassed. Typical value = 0.

tp

0..1

Seconds

Field current bridge time constant (Tp) (>= 0). Typical value = 0.

vcmax

0..1

PU

Maximum compounding voltage (Vcmax). Typical value = 0.

vfmax

0..1

PU

Maximum exciter field current (Vfmax) (> ExcREXS.vfmin). Typical value = 47.

vfmin

0..1

PU

Minimum exciter field current (Vfmin) (< ExcREXS.vfmax). Typical value = -20.

vimax

0..1

PU

Voltage regulator input limit (Vimax). Typical value = 0,1.

vrmax

0..1

PU

Maximum controller output (Vrmax) (> ExcREXS.vrmin). Typical value = 47.

vrmin

0..1

PU

Minimum controller output (Vrmin) (< ExcREXS.vrmax). Typical value = -20.

xc

0..1

PU

Exciter compounding reactance (Xc). Typical value = 0.

DiscontinuousExcitationControlDynamics

0..1

DiscontinuousExcitationControlDynamics

Discontinuous excitation control model associated with this excitation system model.

OverexcitationLimiterDynamics

0..1

OverexcitationLimiterDynamics

Overexcitation limiter model associated with this excitation system model.

PFVArControllerType1Dynamics

0..1

PFVArControllerType1Dynamics

Power factor or VAr controller type 1 model associated with this excitation system model.

PFVArControllerType2Dynamics

0..1

PFVArControllerType2Dynamics

Power factor or VAr controller type 2 model associated with this excitation system model.

PowerSystemStabilizerDynamics

0..1

PowerSystemStabilizerDynamics

Power system stabilizer model associated with this excitation system model.

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

UnderexcitationLimiterDynamics

0..1

UnderexcitationLimiterDynamics

Undrexcitation limiter model associated with this excitation system model.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

enabled

0..1

boolean

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

DiscontinuousExcitationControlDynamics

Discontinuous excitation control model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.DiscontinuousExcitationControlDynamics

Cardinality

0..1

Type

DiscontinuousExcitationControlDynamics

Inherited from

ExcitationSystemDynamics

e1

Field voltage value 1 (E1). Typical value = 3.

URI

cim:ExcREXS.e1

Cardinality

0..1

Type

PU

e2

Field voltage value 2 (E2). Typical value = 4.

URI

cim:ExcREXS.e2

Cardinality

0..1

Type

PU

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

URI

cim:DynamicsFunctionBlock.enabled

Cardinality

0..1

Type

boolean

Inherited from

DynamicsFunctionBlock

fbf

Rate feedback signal flag (fbf). Typical value = fieldCurrent.

URI

cim:ExcREXS.fbf

Cardinality

0..1

Type

ExcREXSFeedbackSignalKind

flimf

Limit type flag (Flimf). Typical value = 0.

URI

cim:ExcREXS.flimf

Cardinality

0..1

Type

PU

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

kc

Rectifier regulation factor (Kc). Typical value = 0,05.

URI

cim:ExcREXS.kc

Cardinality

0..1

Type

PU

kd

Exciter regulation factor (Kd). Typical value = 2.

URI

cim:ExcREXS.kd

Cardinality

0..1

Type

PU

ke

Exciter field proportional constant (Ke). Typical value = 1.

URI

cim:ExcREXS.ke

Cardinality

0..1

Type

PU

kefd

Field voltage feedback gain (Kefd). Typical value = 0.

URI

cim:ExcREXS.kefd

Cardinality

0..1

Type

PU

kf

Rate feedback gain (Kf) (>= 0). Typical value = 0,05.

URI

cim:ExcREXS.kf

Cardinality

0..1

Type

Seconds

kh

Field voltage controller feedback gain (Kh). Typical value = 0.

URI

cim:ExcREXS.kh

Cardinality

0..1

Type

PU

kii

Field current regulator integral gain (Kii). Typical value = 0.

URI

cim:ExcREXS.kii

Cardinality

0..1

Type

PU

kip

Field current regulator proportional gain (Kip). Typical value = 1.

URI

cim:ExcREXS.kip

Cardinality

0..1

Type

PU

ks

Coefficient to allow different usage of the model-speed coefficient (Ks). Typical value = 0.

URI

cim:ExcREXS.ks

Cardinality

0..1

Type

PU

kvi

Voltage regulator integral gain (Kvi). Typical value = 0.

URI

cim:ExcREXS.kvi

Cardinality

0..1

Type

PU

kvp

Voltage regulator proportional gain (Kvp). Typical value = 2800.

URI

cim:ExcREXS.kvp

Cardinality

0..1

Type

PU

kvphz

V/Hz limiter gain (Kvphz). Typical value = 0.

URI

cim:ExcREXS.kvphz

Cardinality

0..1

Type

PU

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

nvphz

Pickup speed of V/Hz limiter (Nvphz). Typical value = 0.

URI

cim:ExcREXS.nvphz

Cardinality

0..1

Type

PU

OverexcitationLimiterDynamics

Overexcitation limiter model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.OverexcitationLimiterDynamics

Cardinality

0..1

Type

OverexcitationLimiterDynamics

Inherited from

ExcitationSystemDynamics

PFVArControllerType1Dynamics

Power factor or VAr controller type 1 model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.PFVArControllerType1Dynamics

Cardinality

0..1

Type

PFVArControllerType1Dynamics

Inherited from

ExcitationSystemDynamics

PFVArControllerType2Dynamics

Power factor or VAr controller type 2 model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.PFVArControllerType2Dynamics

Cardinality

0..1

Type

PFVArControllerType2Dynamics

Inherited from

ExcitationSystemDynamics

PowerSystemStabilizerDynamics

Power system stabilizer model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.PowerSystemStabilizerDynamics

Cardinality

0..1

Type

PowerSystemStabilizerDynamics

Inherited from

ExcitationSystemDynamics

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

se1

Saturation factor at E1 (Se1). Typical value = 0,0001.

URI

cim:ExcREXS.se1

Cardinality

0..1

Type

PU

se2

Saturation factor at E2 (Se2). Typical value = 0,001.

URI

cim:ExcREXS.se2

Cardinality

0..1

Type

PU

SynchronousMachineDynamics

Synchronous machine model with which this excitation system model is associated.

URI

cim:ExcitationSystemDynamics.SynchronousMachineDynamics

Cardinality

1

Type

SynchronousMachineDynamics

Inherited from

ExcitationSystemDynamics

ta

Voltage regulator time constant (Ta) (>= 0). If = 0, block is bypassed. Typical value = 0,01.

URI

cim:ExcREXS.ta

Cardinality

0..1

Type

Seconds

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

tb1

Lag time constant (Tb1) (>= 0). If = 0, block is bypassed. Typical value = 0.

URI

cim:ExcREXS.tb1

Cardinality

0..1

Type

Seconds

tb2

Lag time constant (Tb2) (>= 0). If = 0, block is bypassed. Typical value = 0.

URI

cim:ExcREXS.tb2

Cardinality

0..1

Type

Seconds

tc1

Lead time constant (Tc1) (>= 0). Typical value = 0.

URI

cim:ExcREXS.tc1

Cardinality

0..1

Type

Seconds

tc2

Lead time constant (Tc2) (>= 0). Typical value = 0.

URI

cim:ExcREXS.tc2

Cardinality

0..1

Type

Seconds

te

Exciter field time constant (Te) (> 0). Typical value = 1,2.

URI

cim:ExcREXS.te

Cardinality

0..1

Type

Seconds

tf

Rate feedback time constant (Tf) (>= 0). If = 0, the feedback path is not used. Typical value = 1.

URI

cim:ExcREXS.tf

Cardinality

0..1

Type

Seconds

tf1

Feedback lead time constant (Tf1) (>= 0). Typical value = 0.

URI

cim:ExcREXS.tf1

Cardinality

0..1

Type

Seconds

tf2

Feedback lag time constant (Tf2) (>= 0). If = 0, block is bypassed. Typical value = 0.

URI

cim:ExcREXS.tf2

Cardinality

0..1

Type

Seconds

tp

Field current bridge time constant (Tp) (>= 0). Typical value = 0.

URI

cim:ExcREXS.tp

Cardinality

0..1

Type

Seconds

UnderexcitationLimiterDynamics

Undrexcitation limiter model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.UnderexcitationLimiterDynamics

Cardinality

0..1

Type

UnderexcitationLimiterDynamics

Inherited from

ExcitationSystemDynamics

vcmax

Maximum compounding voltage (Vcmax). Typical value = 0.

URI

cim:ExcREXS.vcmax

Cardinality

0..1

Type

PU

vfmax

Maximum exciter field current (Vfmax) (> ExcREXS.vfmin). Typical value = 47.

URI

cim:ExcREXS.vfmax

Cardinality

0..1

Type

PU

vfmin

Minimum exciter field current (Vfmin) (< ExcREXS.vfmax). Typical value = -20.

URI

cim:ExcREXS.vfmin

Cardinality

0..1

Type

PU

vimax

Voltage regulator input limit (Vimax). Typical value = 0,1.

URI

cim:ExcREXS.vimax

Cardinality

0..1

Type

PU

VoltageCompensatorDynamics

Voltage compensator model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.VoltageCompensatorDynamics

Cardinality

1

Type

VoltageCompensatorDynamics

Inherited from

ExcitationSystemDynamics

vrmax

Maximum controller output (Vrmax) (> ExcREXS.vrmin). Typical value = 47.

URI

cim:ExcREXS.vrmax

Cardinality

0..1

Type

PU

vrmin

Minimum controller output (Vrmin) (< ExcREXS.vrmax). Typical value = -20.

URI

cim:ExcREXS.vrmin

Cardinality

0..1

Type

PU

xc

Exciter compounding reactance (Xc). Typical value = 0.

URI

cim:ExcREXS.xc

Cardinality

0..1

Type

PU