PFVArType2IEEEPFController
IEEE PF controller type 2 which is a summing point type controller making up the outside loop of a two-loop system. This controller is implemented as a slow PI type controller. The voltage regulator forms the inner loop and is implemented as a fast controller. Reference: IEEE 421.5-2005, 11.4.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Excitation system model with which this power factor or VAr controller type 2 is associated. |
||
1 |
Dataset containing the data objects. |
||
0..1 |
Overexcitation or under excitation flag (EXLON) true = 1 (not in the overexcitation or underexcitation state, integral action is active) false = 0 (in the overexcitation or underexcitation state, so integral action is disabled to allow the limiter to play its role). |
||
0..1 |
Integral gain of the pf controller (KI). Typical value = 1. |
||
0..1 |
Proportional gain of the pf controller (KP). Typical value = 1. |
||
0..1 |
Power factor reference (PFREF). |
||
0..1 |
Maximum output of the pf controller (VCLMT). Typical value = 0,1. |
||
0..1 |
Voltage regulator reference (VREF). |
||
0..1 |
Generator sensing voltage (VS). |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
ExcitationSystemDynamics
Excitation system model with which this power factor or VAr controller type 2 is associated.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
exlon
Overexcitation or under excitation flag (EXLON) true = 1 (not in the overexcitation or underexcitation state, integral action is active) false = 0 (in the overexcitation or underexcitation state, so integral action is disabled to allow the limiter to play its role).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
ki
Integral gain of the pf controller (KI). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kp
Proportional gain of the pf controller (KP). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
pfref
Power factor reference (PFREF).
URI |
|
---|---|
Cardinality |
0..1 |
Type |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
vclmt
Maximum output of the pf controller (VCLMT). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
vref
Voltage regulator reference (VREF).
URI |
|
---|---|
Cardinality |
0..1 |
Type |