GovSteamEU
Simplified boiler and steam turbine with PID governor.
Type |
Class |
---|---|
URI |
|
CIM standard (perspective) |
IEC61970 (Grid) |
Slots
Name | Cardinality | Type | Description |
---|---|---|---|
1 |
Dataset containing the data objects. |
||
0..1 |
Control valves rate closing limit (Chc). Unit = PU / s. Typical value = -3,3. |
||
0..1 |
Control valves rate opening limit (Cho). Unit = PU / s. Typical value = 0,17. |
||
0..1 |
Intercept valves rate closing limit (Cic). Typical value = -2,2. |
||
0..1 |
Intercept valves rate opening limit (Cio). Typical value = 0,123. |
||
0..1 |
Deadband of the frequency corrector (db1). Typical value = 0. |
||
0..1 |
Deadband of the speed governor (db2). Typical value = 0,0004. |
||
0..1 |
Maximum control valve position (Hhpmax). Typical value = 1. |
||
0..1 |
Gain of the power controller (Ke). Typical value = 0,65. |
||
0..1 |
Gain of the frequency corrector (Kfcor). Typical value = 20. |
||
0..1 |
Fraction of total turbine output generated by HP part (Khp). Typical value = 0,277. |
||
0..1 |
Fraction of total turbine output generated by HP part (Klp). Typical value = 0,723. |
||
0..1 |
Gain of the speed governor (Kwcor). Typical value = 20. |
||
0..1 |
Base for power values (MWbase) (> 0). Unit = MW. |
||
0..1 |
Maximal active power of the turbine (Pmax). Typical value = 1. |
||
0..1 |
Maximum low pressure limit (Prhmax). Typical value = 1,4. |
||
0..1 |
Intercept valves transfer limit (Simx). Typical value = 0,425. |
||
0..1 |
Boiler time constant (Tb) (>= 0). Typical value = 100. |
||
0..1 |
Derivative time constant of the power controller (Tdp) (>= 0). Typical value = 0. |
||
0..1 |
Electro hydraulic transducer (Ten) (>= 0). Typical value = 0,1. |
||
0..1 |
Frequency transducer time constant (Tf) (>= 0). Typical value = 0. |
||
0..1 |
Time constant of the power controller (Tfp) (>= 0). Typical value = 0. |
||
0..1 |
High pressure (HP) time constant of the turbine (Thp) (>= 0). Typical value = 0,31. |
||
0..1 |
Integral time constant of the power controller (Tip) (>= 0). Typical value = 2. |
||
0..1 |
Low pressure (LP) time constant of the turbine (Tlp) (>= 0). Typical value = 0,45. |
||
0..1 |
Power transducer time constant (Tp) (>= 0). Typical value = 0,07. |
||
0..1 |
Reheater time constant of the turbine (Trh) (>= 0). Typical value = 8. |
||
0..1 |
Control valves servo time constant (Tvhp) (>= 0). Typical value = 0,1. |
||
0..1 |
Intercept valves servo time constant (Tvip) (>= 0). Typical value = 0,15. |
||
0..1 |
Speed transducer time constant (Tw) (>= 0). Typical value = 0,02. |
||
0..1 |
Upper limit for frequency correction (Wfmax) (> GovSteamEU.wfmin). Typical value = 0,05. |
||
0..1 |
Lower limit for frequency correction (Wfmin) (< GovSteamEU.wfmax). Typical value = -0,05. |
||
0..1 |
Emergency speed control lower limit (wmax1). Typical value = 1,025. |
||
0..1 |
Emergency speed control upper limit (wmax2). Typical value = 1,05. |
||
0..1 |
Upper limit for the speed governor (Wwmax) (> GovSteamEU.wwmin). Typical value = 0,1. |
||
0..1 |
Lower limit for the speed governor frequency correction (Wwmin) (< GovSteamEU.wwmax). Typical value = -1. |
||
0..1 |
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
The single CIM data object in the appropriate dataset context. |
||
0..1 |
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics. |
||
0..1 |
Turbine load controller providing input to this turbine-governor. |
||
0..1 |
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time. |
||
0..1 |
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy. |
||
0..1 |
Function block used indicator. true = use of function block is enabled false = use of function block is disabled. |
||
0..1 |
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements. |
||
0..1 |
The name is any free human readable and possibly non unique text naming the object. |
||
0..* |
The diagram objects that are associated with the domain object. |
||
0..* |
All names of this identified object. |
||
0..* |
Data objects registered. |
aliasName
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
AsynchronousMachineDynamics
Asynchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
chc
Control valves rate closing limit (Chc). Unit = PU / s. Typical value = -3,3.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
cho
Control valves rate opening limit (Cho). Unit = PU / s. Typical value = 0,17.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
cic
Intercept valves rate closing limit (Cic). Typical value = -2,2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
cio
Intercept valves rate opening limit (Cio). Typical value = 0,123.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
db1
Deadband of the frequency corrector (db1). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
db2
Deadband of the speed governor (db2). Typical value = 0,0004.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
description
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
DiagramObjects
The diagram objects that are associated with the domain object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
enabled
Function block used indicator. true = use of function block is enabled false = use of function block is disabled.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
hhpmax
Maximum control valve position (Hhpmax). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
InstanceSet
Dataset containing the data objects.
URI |
|
---|---|
Cardinality |
1 |
Type |
|
Inherited from |
ke
Gain of the power controller (Ke). Typical value = 0,65.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
kfcor
Gain of the frequency corrector (Kfcor). Typical value = 20.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
khp
Fraction of total turbine output generated by HP part (Khp). Typical value = 0,277.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
klp
Fraction of total turbine output generated by HP part (Klp). Typical value = 0,723.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
komegacor
Gain of the speed governor (Kwcor). Typical value = 20.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
mRID
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
mwbase
Base for power values (MWbase) (> 0). Unit = MW.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
name
The name is any free human readable and possibly non unique text naming the object.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
Names
All names of this identified object.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
pmax
Maximal active power of the turbine (Pmax). Typical value = 1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
prhmax
Maximum low pressure limit (Prhmax). Typical value = 1,4.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
PropertiesCIMDataObject
The single CIM data object in the appropriate dataset context.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
simx
Intercept valves transfer limit (Simx). Typical value = 0,425.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
SynchronousMachineDynamics
Synchronous machine model with which this turbine-governor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
TargetingCIMDataObject
Data objects registered.
URI |
|
---|---|
Cardinality |
0..* |
Type |
|
Inherited from |
tb
Boiler time constant (Tb) (>= 0). Typical value = 100.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tdp
Derivative time constant of the power controller (Tdp) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
ten
Electro hydraulic transducer (Ten) (>= 0). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tf
Frequency transducer time constant (Tf) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tfp
Time constant of the power controller (Tfp) (>= 0). Typical value = 0.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
thp
High pressure (HP) time constant of the turbine (Thp) (>= 0). Typical value = 0,31.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tip
Integral time constant of the power controller (Tip) (>= 0). Typical value = 2.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tlp
Low pressure (LP) time constant of the turbine (Tlp) (>= 0). Typical value = 0,45.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tp
Power transducer time constant (Tp) (>= 0). Typical value = 0,07.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
trh
Reheater time constant of the turbine (Trh) (>= 0). Typical value = 8.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
TurbineLoadControllerDynamics
Turbine load controller providing input to this turbine-governor.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
|
Inherited from |
tvhp
Control valves servo time constant (Tvhp) (>= 0). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tvip
Intercept valves servo time constant (Tvip) (>= 0). Typical value = 0,15.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
tw
Speed transducer time constant (Tw) (>= 0). Typical value = 0,02.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
wfmax
Upper limit for frequency correction (Wfmax) (> GovSteamEU.wfmin). Typical value = 0,05.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
wfmin
Lower limit for frequency correction (Wfmin) (< GovSteamEU.wfmax). Typical value = -0,05.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
wmax1
Emergency speed control lower limit (wmax1). Typical value = 1,025.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
wmax2
Emergency speed control upper limit (wmax2). Typical value = 1,05.
URI |
|
---|---|
Cardinality |
0..1 |
Type |
wwmax
Upper limit for the speed governor (Wwmax) (> GovSteamEU.wwmin). Typical value = 0,1.
URI |
|
---|---|
Cardinality |
0..1 |
Type |