ExcELIN2

Detailed excitation system ELIN (VATECH). This model represents an all-static excitation system. A PI voltage controller establishes a desired field current set point for a proportional current controller. The integrator of the PI controller has a follow-up input to match its signal to the present field current. Power system stabilizer models used in conjunction with this excitation system model: PssELIN2, PssIEEE2B, Pss2B.

Type

Class

URI

cim:ExcELIN2

CIM standard (perspective)

IEC61970 (Grid)

Slots

Associated classes
Figure 1. Associated classes
Name Cardinality Type Description

InstanceSet

1

InstanceSet

Dataset containing the data objects.

SynchronousMachineDynamics

1

SynchronousMachineDynamics

Synchronous machine model with which this excitation system model is associated.

VoltageCompensatorDynamics

1

VoltageCompensatorDynamics

Voltage compensator model associated with this excitation system model.

efdbas

0..1

PU

Gain (Efdbas). Typical value = 0,1.

iefmax

0..1

PU

Limiter (Iefmax) (> ExcELIN2.iefmin). Typical value = 1.

iefmax2

0..1

PU

Minimum open circuit excitation voltage (Iefmax2). Typical value = -5.

iefmin

0..1

PU

Limiter (Iefmin) (< ExcELIN2.iefmax). Typical value = 1.

k1

0..1

PU

Voltage regulator input gain (K1). Typical value = 0.

k1ec

0..1

PU

Voltage regulator input limit (K1ec). Typical value = 2.

k2

0..1

PU

Gain (K2). Typical value = 5.

k3

0..1

PU

Gain (K3). Typical value = 0,1.

k4

0..1

PU

Gain (K4). Typical value = 0.

kd1

0..1

PU

Voltage controller derivative gain (Kd1). Typical value = 34,5.

ke2

0..1

PU

Gain (Ke2). Typical value = 0,1.

ketb

0..1

PU

Gain (Ketb). Typical value = 0,06.

pid1max

0..1

PU

Controller follow up gain (PID1max). Typical value = 2.

seve1

0..1

PU

Exciter saturation function value at the corresponding exciter voltage, Ve1, back of commutating reactance (Se[Ve1]) (>= 0). Typical value = 0.

seve2

0..1

PU

Exciter saturation function value at the corresponding exciter voltage, Ve2, back of commutating reactance (Se[Ve2]) (>= 0). Typical value = 1.

tb1

0..1

Seconds

Voltage controller derivative washout time constant (Tb1) (>= 0). Typical value = 12,45.

te

0..1

Seconds

Time constant (Te) (>= 0). Typical value = 0.

te2

0..1

Seconds

Time Constant (Te2) (>= 0). Typical value = 1.

ti1

0..1

PU

Controller follow up deadband (Ti1). Typical value = 0.

ti3

0..1

Seconds

Time constant (Ti3) (>= 0). Typical value = 3.

ti4

0..1

Seconds

Time constant (Ti4) (>= 0). Typical value = 0.

tr4

0..1

Seconds

Time constant (Tr4) (>= 0). Typical value = 1.

upmax

0..1

PU

Limiter (Upmax) (> ExcELIN2.upmin). Typical value = 3.

upmin

0..1

PU

Limiter (Upmin) (< ExcELIN2.upmax). Typical value = 0.

ve1

0..1

PU

Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve1) (> 0). Typical value = 3.

ve2

0..1

PU

Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve2) (> 0). Typical value = 0.

xp

0..1

PU

Excitation transformer effective reactance (Xp). Typical value = 1.

DiscontinuousExcitationControlDynamics

0..1

DiscontinuousExcitationControlDynamics

Discontinuous excitation control model associated with this excitation system model.

OverexcitationLimiterDynamics

0..1

OverexcitationLimiterDynamics

Overexcitation limiter model associated with this excitation system model.

PFVArControllerType1Dynamics

0..1

PFVArControllerType1Dynamics

Power factor or VAr controller type 1 model associated with this excitation system model.

PFVArControllerType2Dynamics

0..1

PFVArControllerType2Dynamics

Power factor or VAr controller type 2 model associated with this excitation system model.

PowerSystemStabilizerDynamics

0..1

PowerSystemStabilizerDynamics

Power system stabilizer model associated with this excitation system model.

PropertiesCIMDataObject

0..1

ChangeSetMember

The single CIM data object in the appropriate dataset context.

UnderexcitationLimiterDynamics

0..1

UnderexcitationLimiterDynamics

Undrexcitation limiter model associated with this excitation system model.

aliasName

0..1

string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

description

0..1

string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

enabled

0..1

boolean

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

mRID

0..1

string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

0..1

string

The name is any free human readable and possibly non unique text naming the object.

DiagramObjects

0..*

DiagramObject

The diagram objects that are associated with the domain object.

Names

0..*

Name

All names of this identified object.

TargetingCIMDataObject

0..*

ChangeSetMember

Data objects registered.


aliasName

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy. The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

URI

cim:IdentifiedObject.aliasName

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

description

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

URI

cim:IdentifiedObject.description

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

DiagramObjects

The diagram objects that are associated with the domain object.

URI

cim:IdentifiedObject.DiagramObjects

Cardinality

0..*

Type

DiagramObject

Inherited from

IdentifiedObject

DiscontinuousExcitationControlDynamics

Discontinuous excitation control model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.DiscontinuousExcitationControlDynamics

Cardinality

0..1

Type

DiscontinuousExcitationControlDynamics

Inherited from

ExcitationSystemDynamics

efdbas

Gain (Efdbas). Typical value = 0,1.

URI

cim:ExcELIN2.efdbas

Cardinality

0..1

Type

PU

enabled

Function block used indicator. true = use of function block is enabled false = use of function block is disabled.

URI

cim:DynamicsFunctionBlock.enabled

Cardinality

0..1

Type

boolean

Inherited from

DynamicsFunctionBlock

iefmax

Limiter (Iefmax) (> ExcELIN2.iefmin). Typical value = 1.

URI

cim:ExcELIN2.iefmax

Cardinality

0..1

Type

PU

iefmax2

Minimum open circuit excitation voltage (Iefmax2). Typical value = -5.

URI

cim:ExcELIN2.iefmax2

Cardinality

0..1

Type

PU

iefmin

Limiter (Iefmin) (< ExcELIN2.iefmax). Typical value = 1.

URI

cim:ExcELIN2.iefmin

Cardinality

0..1

Type

PU

InstanceSet

Dataset containing the data objects.

URI

cim:IdentifiedObject.InstanceSet

Cardinality

1

Type

InstanceSet

Inherited from

IdentifiedObject

k1

Voltage regulator input gain (K1). Typical value = 0.

URI

cim:ExcELIN2.k1

Cardinality

0..1

Type

PU

k1ec

Voltage regulator input limit (K1ec). Typical value = 2.

URI

cim:ExcELIN2.k1ec

Cardinality

0..1

Type

PU

k2

Gain (K2). Typical value = 5.

URI

cim:ExcELIN2.k2

Cardinality

0..1

Type

PU

k3

Gain (K3). Typical value = 0,1.

URI

cim:ExcELIN2.k3

Cardinality

0..1

Type

PU

k4

Gain (K4). Typical value = 0.

URI

cim:ExcELIN2.k4

Cardinality

0..1

Type

PU

kd1

Voltage controller derivative gain (Kd1). Typical value = 34,5.

URI

cim:ExcELIN2.kd1

Cardinality

0..1

Type

PU

ke2

Gain (Ke2). Typical value = 0,1.

URI

cim:ExcELIN2.ke2

Cardinality

0..1

Type

PU

ketb

Gain (Ketb). Typical value = 0,06.

URI

cim:ExcELIN2.ketb

Cardinality

0..1

Type

PU

mRID

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended. For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

URI

cim:IdentifiedObject.mRID

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

name

The name is any free human readable and possibly non unique text naming the object.

URI

cim:IdentifiedObject.name

Cardinality

0..1

Type

string

Inherited from

IdentifiedObject

Names

All names of this identified object.

URI

cim:IdentifiedObject.Names

Cardinality

0..*

Type

Name

Inherited from

IdentifiedObject

OverexcitationLimiterDynamics

Overexcitation limiter model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.OverexcitationLimiterDynamics

Cardinality

0..1

Type

OverexcitationLimiterDynamics

Inherited from

ExcitationSystemDynamics

PFVArControllerType1Dynamics

Power factor or VAr controller type 1 model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.PFVArControllerType1Dynamics

Cardinality

0..1

Type

PFVArControllerType1Dynamics

Inherited from

ExcitationSystemDynamics

PFVArControllerType2Dynamics

Power factor or VAr controller type 2 model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.PFVArControllerType2Dynamics

Cardinality

0..1

Type

PFVArControllerType2Dynamics

Inherited from

ExcitationSystemDynamics

pid1max

Controller follow up gain (PID1max). Typical value = 2.

URI

cim:ExcELIN2.pid1max

Cardinality

0..1

Type

PU

PowerSystemStabilizerDynamics

Power system stabilizer model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.PowerSystemStabilizerDynamics

Cardinality

0..1

Type

PowerSystemStabilizerDynamics

Inherited from

ExcitationSystemDynamics

PropertiesCIMDataObject

The single CIM data object in the appropriate dataset context.

URI

cim:IdentifiedObject.PropertiesCIMDataObject

Cardinality

0..1

Type

ChangeSetMember

Inherited from

IdentifiedObject

seve1

Exciter saturation function value at the corresponding exciter voltage, Ve1, back of commutating reactance (Se[Ve1]) (>= 0). Typical value = 0.

URI

cim:ExcELIN2.seve1

Cardinality

0..1

Type

PU

seve2

Exciter saturation function value at the corresponding exciter voltage, Ve2, back of commutating reactance (Se[Ve2]) (>= 0). Typical value = 1.

URI

cim:ExcELIN2.seve2

Cardinality

0..1

Type

PU

SynchronousMachineDynamics

Synchronous machine model with which this excitation system model is associated.

URI

cim:ExcitationSystemDynamics.SynchronousMachineDynamics

Cardinality

1

Type

SynchronousMachineDynamics

Inherited from

ExcitationSystemDynamics

TargetingCIMDataObject

Data objects registered.

URI

cim:IdentifiedObject.TargetingCIMDataObject

Cardinality

0..*

Type

ChangeSetMember

Inherited from

IdentifiedObject

tb1

Voltage controller derivative washout time constant (Tb1) (>= 0). Typical value = 12,45.

URI

cim:ExcELIN2.tb1

Cardinality

0..1

Type

Seconds

te

Time constant (Te) (>= 0). Typical value = 0.

URI

cim:ExcELIN2.te

Cardinality

0..1

Type

Seconds

te2

Time Constant (Te2) (>= 0). Typical value = 1.

URI

cim:ExcELIN2.te2

Cardinality

0..1

Type

Seconds

ti1

Controller follow up deadband (Ti1). Typical value = 0.

URI

cim:ExcELIN2.ti1

Cardinality

0..1

Type

PU

ti3

Time constant (Ti3) (>= 0). Typical value = 3.

URI

cim:ExcELIN2.ti3

Cardinality

0..1

Type

Seconds

ti4

Time constant (Ti4) (>= 0). Typical value = 0.

URI

cim:ExcELIN2.ti4

Cardinality

0..1

Type

Seconds

tr4

Time constant (Tr4) (>= 0). Typical value = 1.

URI

cim:ExcELIN2.tr4

Cardinality

0..1

Type

Seconds

UnderexcitationLimiterDynamics

Undrexcitation limiter model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.UnderexcitationLimiterDynamics

Cardinality

0..1

Type

UnderexcitationLimiterDynamics

Inherited from

ExcitationSystemDynamics

upmax

Limiter (Upmax) (> ExcELIN2.upmin). Typical value = 3.

URI

cim:ExcELIN2.upmax

Cardinality

0..1

Type

PU

upmin

Limiter (Upmin) (< ExcELIN2.upmax). Typical value = 0.

URI

cim:ExcELIN2.upmin

Cardinality

0..1

Type

PU

ve1

Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve1) (> 0). Typical value = 3.

URI

cim:ExcELIN2.ve1

Cardinality

0..1

Type

PU

ve2

Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve2) (> 0). Typical value = 0.

URI

cim:ExcELIN2.ve2

Cardinality

0..1

Type

PU

VoltageCompensatorDynamics

Voltage compensator model associated with this excitation system model.

URI

cim:ExcitationSystemDynamics.VoltageCompensatorDynamics

Cardinality

1

Type

VoltageCompensatorDynamics

Inherited from

ExcitationSystemDynamics

xp

Excitation transformer effective reactance (Xp). Typical value = 1.

URI

cim:ExcELIN2.xp

Cardinality

0..1

Type

PU